• <br />• <br />* <br />ROOF VIAND DESIGN <br />PRESSURES* <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 6120 PSF (7120) <br />ZONES = 70.70 PSF (80.70) <br />ZONE 2e = 70,70 PSF (80.70) <br />ZONE 3e = 82.90 PSF (92.90) <br />ZONE 2n = 82.90 PSF (92.90) <br />ZONE 3r = 90.80 PSF (100.80) <br />ZONE 2r = 82.90 PSF (92.90) <br />"A"- 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: 11 <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: 1- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/3Z' STRUCTURAL SHEATHING <br />EXP 1 4020 FOR CEMENTITIOUS TILE AND METAL ROOFING USE MIN. <br />19l32" STRUCTURAL SHEATHING EXP 1 (402O).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 101 RING SHANK GUN <br />NAILS Q 4" O.C. EDGEWISE 2X4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />Meu Pr:nl NocucuTo <br />SIZE <br />HEAD <br />LENGTH <br />DIA <br />TENSILE STR. <br />SHANK <br />ASTM <br />10d <br />RINGSHANK, <br />21fY' <br />0131 <br />F168 <br />SCREW HANK <br />170,000 <br />RING <br />RINGS <br />1ER <br />RSRS-03 <br />Bd <br />RING S A <br />H NK <br />2 3!S' <br />0.113 <br />F1667 <br />SCREW SHANK <br />I <br />PER INCH) <br />RSRS-Ot <br />8d <br />RINGSHANK, <br />PNEUMATIC <br />2 3/9' <br />0.113 <br />F1667 <br />RSRS-01 <br />SCR <br />REW-NAILS <br />cnnc Q.—Tu n 1— <br />EXTERIOR SHEATHING <br />USE 12" COX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND Bd RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6' O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />BUILDING LENGTH <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />ZONE 1: 10d NAILS G 4" O,C. ON EDGE AND &' O.C. IN FIELD <br />ZONE 2e, 2n, 2r: 1 Od NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r: 1Od NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />i <br />S <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />M RING SHANK GL¢J NAILS 0 4-C. <br />TOP & BOTTOM EOOES <br />J <br />z <br />z <br />On <br />z W . <br />S � <br />cl <br />z O <br />Ft io <br />- <br />■=�Mb_qwMOO <br />■►�'II <br />ii --_—i <br />'1 <br />NNOM GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2X4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING <br />19'0.C. IF NO DROPPED GABLE END, ATTACH 2X4 #2 SYP <br />BLOCKING 0 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />10d RING SHANK GUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT' <br />TABLE FOR FIELD SPACING <br />_ #8 2' DECK SCREWS 0 6"-W O.C. MAX <br />EQGES & 12' O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />1 YP. 314" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33IC3314 MAXIMUM AGGREGATE SIZE SMALL BE 3W. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE B%AIR ENTRAINED CONCRETE EXPOSED TO FIRTH ORWEATHER <br />NON43EARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3W. <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, TMS 402/602-18 AISI SPECIFICATION FOR THE DESIGN OF <br />BARRIER MEMBRANE UNDER ALL SLABSON-GROUND WHERE INDICATED ON PROVIDE 6#IIL CONTINUOUS POLYETHYLENE VAPOR B <br />VAPOR <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb - 1100 PSI AND A MODULUS OF <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS <br />DRAWINGSSEAMS TAPPED S INCHES ANDSE <br />. LED ADHESIVE TAPE. <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED, WOOD FOR NONSTRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -MARK SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN %' OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY, ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL. DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2X STRUCTURAL LUMBER <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED W000 SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH- <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED <br />WELDED WIRE MESH, SHALL BE ASTM A1064JA1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE <br />WOOD TRUSSES' <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND S1TE PREPARATION <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WITH 2" CHAIRS SPACED 3'-0" OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NA710NAL DESIGN SPECIFICATIONS FOR <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS, <br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A61 SA615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />MEETING THE REQUIREMENTS OF ASTM A448IA448M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 601N MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WTH TPI-14,'DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "SCSI LATEST EDITION" <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 pe1 <br />AND VERTICAL BARS SHALL LAP 6 z BAR UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL•PLATE-CONNECTED <br />20 psf TOP CHORD non -concurrent <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />WOOD TRUSSES. <br />10 p on-conof BTM CHORD -ncumnt <br />#5 BAR - 30' #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36'x 38' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOVER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990. <br />15 ptTOP CHORD 20 paf TOP CHORD <br />ALT <br />(7 pf s.1 ASPHALT SHINGLES) (10 psfw/ No GVPCRETE) <br />(7 <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 psf BTM CHORD 5 psf BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: I Opsf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWANGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 80 psf <br />WALL' <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />WAND: DEAD LOAD SPEED= PH S- SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE 0) E <br />EXPOSURE C, RISK CATEGORY II) <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE, <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />BIT BLE ATTIC <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WITH LIMITED <br />LAYOUT, SPANS 8 ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />00 NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40paf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />MASONRY. <br />PLAN SHOWANG COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED By A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER, <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SMALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED THE CONTRACTORS PRIOR SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm = 2000 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-18 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />WILL <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />. S <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS, <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACNG CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM G-076, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W/A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM CQ70. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS, LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />S:.PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SUB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT CONCRETE SLUMP SHALL NOT EXCEED T d- PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94C94M OR MEASURING, MIXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNIJTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MNUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPUANCE MATH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SRALL RE AS FOLLOWS: <br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />S. FOR CONCRETE EXPOSED TO EARTH ANDX)R WEATHER <br />14,7' FOR MI AND SMALLER <br />Y FOR 06 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3W FOR SLABS, WALLS AND JOISTS <br />1-1/C FOR BEAM AND COLUMN PPMURY REINFORCEMENT, TIES, STIRRUPS <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL <br />C L S E BE ASTM <br />A38/A36M, Fy = 361s1 FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/A500M GRADE B F = 48 ksl. STRUCTURAL PIPE SHALL - <br />y S BE ASTM AS&A53M, GRADE B, TYPE E OR S, Fy - <br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS MATH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW ANO <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPIICATKXI <br />9¢ <br />TYPE <br />SPAgNG <br />REMARKS <br />APRKATION <br />SIZE <br />nPE <br />SPADING <br />REMPRI(e <br />tYt PT FIdtPoNOTO <br />MASONRY/HNC. <br />CASE HARpENEDCOK <br />11?LONG. <br />8"OIC <br />GARAGE DOOR Bt1CTt <br />MASONRT21'xD. <br />M"LTA <br />NO WASTER <br />TAPCON MAECNRY <br />FASTS <br />8OF <br />/!'EMBED, .V ENDDIST., <br />II?EDGE DST. <br />900AL. EXT. DOORS <br />CASE HPRDENEDGOIL <br />9°O'C <br />wNDOW1000R/FABTEVED <br />GARAGE COOR SICK <br />&e D 0. OR <br />IB"dC (0I0'DNI <br />4•EMBE0., 4"ENDOIsi., <br />Ix PT, SEE NOTES <br />I1?LONG. <br />STAGGERED <br />INTO-- <br />TO MABONRY,DONC. <br />IXPANSICN BOLT <br />31"CAC (1?'DIN <br />TEDGE DSi. <br />.I —auto <br />CASE HARDENED WR <br />a'x <br />WINOOW/OOOItF TENED <br />METN.STRAPTO <br />CONTACT THIS ENGINEER FOR SPACING <br />Ix PT, SEE wTee <br />LI ux'LONG. <br />siAG I. <br />INTO MasoNRTDone. <br />MAsoNRv/cDNc <br />REQUIREMENTS <br />ExT.SWING DOOR <br />�I 31181]IA <br />"iAPNI! <br />IB°dC <br />1?EMBED. e'END. <br />NqN eEAleNGWWD <br />1?' EXPANSION 4'EMBED.PE- <br />SUCK2IPT.—NOTES <br />NMBHER <br />F0.4TNEA <br />pei.,tt?FDGEOST. <br />OANC. etAe <br />W/WASHER BOLT }4 PC B"EDGEDST. <br />L Pf WNT BIKX O.t38°PPFx21A' 9°C/O 4°—.ST.,I t? <br />P o s� L ca., s� wnsHEa sTACGERED EDGE war. <br />TEe <br />NOTES <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE RAND FRAMED <br />4, PAF SHALL BE HILTf X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL SE AS AMIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR W TH A WOOD DOOR FRAME. lx MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED 1W TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD <br />LONGWOOD, FL 32750 <br />PH: 407-7746078 <br />FAX: 407-7744078 <br />www.abdosigngfoup.com <br />AA #: 0003325 <br />r <br />1<F <br />O <br />4 <br />SLTSDIV. S. LOT <br />ABBOTT PARK <br />LOT #27 <br />BLK. #9 <br />PROJECT# <br />04181.000-270 1 <br />MODEL: <br />3EEB <br />"2260—ELSTON" <br />GARAGE av►iNG: <br />RIGHT <br />PAGE: <br />DETAILS <br />N16Q MPH <br />03 <br />DAB 05/25/21 <br />SCALE: 1/4"=1'-0" <br />YP FXT RHPATH[Mr. ATTAC.HMF <br />SN1 <br />