q <br />IF—�F <br />ROOF WIND DESIGN PRESSURES <br />HEY (GROSS) ASCE 1 <br />ZONE 1 = 23.79 PSF (33.79) <br />ZONE 2 = 39.48 PSF (49.48) <br />ZONE 3 = 67.16 PSF (77.16) <br />"A"= 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />WIND EXPOSURE: "C" <br />RISK CATAGORY: 11 <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT - 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16" STRUCTURAL <br />SHEATHING EXP 1(24/16) or 15/32" STRUCTURAL SHEATHING EXP 1 <br />(32f16), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE 15/3T <br />STRUCTURAL SHEATHING EXP 1 (32/16) .(SEE TABLE FOR FIELD AND <br />EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 8d RING SHANK GUN <br />NAILS @ 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' <br />OF GABLE END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL REQUIREMENTS <br />SIZE <br />HEAD <br />LENGTH <br />DIA. <br />TENSILE STR. <br />SHANK <br />ASTM <br />8d <br />RING SHANK, <br />2318' <br />0.113 <br />170Opp <br />(16-20 RINGS <br />F1667 <br />RSRS41 <br />SCREW SHANK <br />PER INCH) <br />SO <br />RING SHANK, <br />PNEUMATIC <br />23/8" <br />0.113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 112" CDX OR 711 6"O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT <br />4" O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Sd RING SHANK GUN NAILS AT 6" O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM <br />(INSTALLED PER MANUR SPECS.) SEE DETAIL. <br />ROOF SHEATHING ATTACHEAMENT SPACNG <br />ZONE V Bd NAILS @ 4- O.C. ON EDGE AND S" O.C. IN FIELD <br />ZONE 2e, 2n, 2r: 8d NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r: 8d NAILS Q 4" D.C. ON EDGE AND 4" O.C. IN FIELD <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />.. TOP & BOTTOM EDGES ,. <br />1i ' <br />RAFTER OR TRUSS _ <br />ROOF SHEATHING <br />■mm 11 <br />. ��u�' 11 <br />■��==L 11 <br />mm_m► 111111 . . <br />BUILDING LENGTH <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2X4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING <br />16"O.C. IF NO DROPPED GABLE END, ATTACH 2X4 #2 SYP <br />BLOCKING G 16" O.C. FIRST 4 BAYS Wf (2)12d NAILS EA <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />C8d RING SHANK GUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT" <br />TABLE FOR FIELD SPACING <br />(—#8 2- DECK SCREWS 0 6"-8" O.C. MAX G <br />EDGES & 12" O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />TYP. 314" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES. DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBCR 2020.71N EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, TMS 402J602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SfTUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE: ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK - <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTORS RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC33C33G1. MRXIMMAGGREGATE SIZE WALL BE 3W. <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO FARM OR WEATHER <br />WOOD: <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ALL EXPOSED EDGES OF CONCRETE AFETO BE CIMAFERED 3W <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. F6 = 1100 PSI AND A MODULUS OF <br />PROVIDE CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRME UNDER ALL WHERE SIABS-0NGRIX#ID INDICATED ON <br />ROVIDE 6 <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />RAWMGG. SEAMS LAPPED S INCHES AND SEMID WITH ADHESIVE E TAPE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />FORMWORK <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2, STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />WELDED WIRE MESH, <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WELDED WIRE MESH, SHALL BE ASTM A7064/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE <br />WOOD TRUSSES: <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE 'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS, THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A61WISM GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A616 <br />MEETfNG THE REQUIREMENTS OF ASTM A446/A446M, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE. AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOAM: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND -BCSI LATEST EDITION' <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 pN <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 psf TOP CHORD--r4 <br />REVIEW, <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25' #6 BAR - 3V <br />WOOD TRUSSES. <br />10 psf BTM CHORD t1Dn- .-rd <br />#5 BAR - 30" #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36" x 36" CORNER BARS, BOND SEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSUASCE 7 88: 1990. <br />p#f TOP CHORD p CHORD <br />STOP <br />(7 psf ASPHALT SHINGLES) pat GYPCRETE) <br />(7 (1 <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />5 p <br />10 BTM CHORD 5 psf BTM CHORD <br />S I C <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />D <br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 Psf <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />WIND: DEAD LOAD SPEED =2R2020) MPH SU SECOND GUST <br />(NICE EXPOSURE C. RISK CATEGORY II) <br />(FBCBLE <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />BIT ATTIC WITH LIMBED <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: <br />LAYOUT. SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20pst, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30Def, BALCONIES (EXTERIOR) <br />WITH FIXED STAIRS: 0psf, <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />MASONRY: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />40psf <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW. <br />'SPECIFICATION MASONRY STRUCTURES' (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBIUTY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM CAD, GRADE fM - 20M PSI. BLOCK SHALL BE PLACED USING <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL 13E RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERW SE NOTED. LAY�1P MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CONTRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318" <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8' TO 10'. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION: <br />TYPE 'M"OR"S'MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 FOOTINGANDPL <br />MIXEDASO OUTLINED UNDER ASTM HORIZONTAL <br />EXCAVATIONS AND SLAB BE COMPACTED TO A DRY DENSITY OF AT LEAST OF THE <br />THAT EXTEND INTO <br />SHALL BE THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />SHALL B 3/8" T ICI REMOVE M PROTRUSIONS <br />ENALL <br />MAXIMUM DRY 7. T <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM 61557. TREAT ALL <br />BE <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />`.� .E-�, <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />A36/A36M, Fy = 36 W FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />AS00/A500M, GRADE 8, Fy = 46 MI. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy = <br />2.500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />35 ksl. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTL#RAL TERRACE SLAB. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A3D7 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />CONTRACTOR $HALL SUBMIT PROPOSED MIX DESIGNS. WITH HISTORICAL STRENGTH DAT0. FOR EACH SEPARATE MU( PRIOR To <br />MI NS. HHIST M STRENGTHDATA FOREACH <br />$ ALL SURCONCRETE <br />OTHER BOLTS SHILL BE ASTM F3125IF3126M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />CONCRETE SLUMP SMALL EXCEED THE <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTMGAIC94M OR WASM6NG, MIXING, TRANSPORTING <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL.J-BOLTS ARE TO BE STEEL. <br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED W ITS FINAL POSITION SHA L NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALLBE <br />THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE YW TH THE ABOVE <br />REWIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A. TFOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATIONSr <br />& FOR CONCRETE EXPOSED TO EARTH AID/OR WEATHER <br />1.1rT FORM ANDSMALLER <br />2' FOR 05 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />31V FOR SUBS, WALLS AND JOISTS <br />I-12" FOR BEAM AND COLUMN PRIMARY FEJNFORCELENT, TIES, STIRRUPS <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />S#E <br />TYPE <br />SPACING <br />REAIAAKS <br />W-Tm <br />SITE <br />TYPE <br />SPACIAL <br />gEANIE6 <br />FUWtING To <br />IMASONRYICONC. <br />CA4E-El <br />NAX1t?LONG.% <br />e'ac <br />GARAGEOOORBUCK <br />10 BIASONRYI�NC. <br />Ir OW <br />NO WASHER <br />TAPCIXI AIASpRY <br />ASTENER <br />e. <br />MBED., r EW D.I. <br />YT EDGEDXIT. <br />SGO,AL.EM.�OORS <br />UPT.SEEN 6 <br />CASE NAROEH:O COIL <br />rOA <br />SiAGGEIED <br />WWC/w,DOOIL fA3TQff0 <br />INTO IMSONtYAXINO. <br />GARAGEDOORB110( <br />To1M9gtYWA]IIC. <br />1?IXl W/ <br />EIPANBIDNBOLT <br />2r O'C <br />rEA18ED.,rFIA 06T., <br />SEDGE DUST. <br />wsAaW eucK <br />CASE HARDEFFO colt <br />role <br />wx4wwmeow FASTENED <br />AA:rus T. <br />CONTACT THIS ENGINEER FOR SPACING <br />v Pr. SEE NorEs <br />XltrrLONc. <br />siAGGer<D <br />INTO M.soISUrAxxA. <br />AtAsoFar/ca+c. <br />REQUIREMENTS <br />EM.SWMG DOOR <br />BUCKH,PT,SEENOTEB <br />ITT Bn81xA. <br />NO WASHER <br />•iAFOOer <br />FASTNER <br />tS"OTC <br />11?EMBED,r END. <br />DIST.,—DGEDHT. <br />NON .G- <br />WALL TO GONG ERNE <br />1T EKPA- YT O,G 'EMSED.rENp <br />WIWASHER Bq,T D19T.,TEIX3E GIST <br />a PrwwDovYeucrc 8.1SS•PNxTIB• rCA rEND. DIST.,I IIY <br />PT TO STEEL CCU., SEE pSNER GGEREO EDGE DIST. <br />A Ee <br />NoTo <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HI TI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. W NDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. ix MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774.6078 <br />FAX 407-7744078 <br />www.abdesigngroup.com <br />AA #, 0003325 J <br />Y <br />666 <br />ib <br />O <br />ib <br />ib <br />$$s <br />BU13DIV. & LOT: <br />ABBOTT PARK <br />LOT #9 <br />BLK #11 <br />PROJECT/' <br />04181.000-09111 <br />MODEL" <br />4EBB <br />"1828-CALIF" <br />GARAGE SIFMG: <br />LEFT <br />PAGE: <br />DETAILS <br />16 PH XP. <br />aA <br />NO <br />ram a <br />DATE: 01/20/21 <br />SCALE: 1/4"=1F-0" <br />sFIEET <br />S N1 <br />TYP. EXT. SHEATHING ATTACHMENT <br />