GABLE-ENp <br />HWROOF <br />ROOF WIND DESIGN PRESSURES <br />7- <br />ZONE 1 = 18.31 PSF (28.31) <br />ZONE 2 = 31.68 PSF (41.68) <br />ZONE 3 = 54.88 PSF (64.88) <br />'A'= 4•-O' END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />WIND EXPOSURE:'C <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT H-0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32' STRUCTURAL SHEATHING <br />EXP 1 (4WD), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19/32" STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE I Od RING SHANK GUN <br />NAILS Q 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLEEND. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />DIA. <br />TENSILE STR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK, <br />212" <br />0.131 <br />Ft 7 <br />SCREW SHANK <br />170,000 <br />RING <br />(16-20 RINGS <br />RSRS-03 <br />Bd <br />RING SHANK, <br />2 3/8" <br />0.113 <br />F1667 <br />SCREW SHANK <br />PER INCH) <br />RSRS-01 <br />8d <br />RINGSHANK, <br />PNEUMATIC <br />23/8" <br />0.113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />nnr I tM un I nuaa -� <br />ROOF SHEATHING <br />EXTERIOR SHEATHING <br />USE 12" COX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Sd RING SHANK GUN NAILS AT 6" O.C. AT <br />INTERMEDIATE SUPPORTS OR 7116" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. BUILDING LENGTH <br />x <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADDL DROPPED <br />TRUSS 2.4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING 0 <br />16.O.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP <br />BLOCKING @ 16' O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />ROOF SHEATHM ATTACI'EMENT SPACING <br />ZONE 1: 10d NAILS @ 4" O.C. ON EDGE AND 6" O.C. IN FIELD <br />ZONE 2e, 20, 2, 1 Od NAILS G 4" O.C. ON EDGE AND 4" O.G. IN FIELD <br />ZONE 3,3e, 3r. 1 Od NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />TOP & BOTTOM EDGES <br />(n <br />a <br />li - <br />■mom===il- I ImmmmoI <br />Z N <br />z LWE�0 <br />c7 Ow C I. RING SHANK GUN NAILS <br />y SEE "ROOF SHEATHING ATTACHMENT" <br />ci TABLE FOR FIELD SPACING <br />Vl o <br />ZP <br />Oa. S AT NG ATTACHMEO FORST U <br />SHEATHING <br />N <br />¢ O #8 2- DECK SCREWS @ 6'-8" O.C. MAX Q <br />W EDGES & 12" O.C. MAX IN FIELD. UNTHREADED <br />Y SHANK TO EXTEND BEYOND THICKNESS OF <br />0 00 SUB -FLOOR SHEATHING ` <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: PSC-R 2020, 71h EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, TMS 402/602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016. ASCE 7-16 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM CnC33M. M k)0M1M AGGREGATE SIZE SHALL BE 3W <br />PROVIDE 5%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHRMFERED 3W <br />PROVIDE 6ML CONTINUOUS POLYETHYLENE VAPOR BARRIER AEABRANE UNDER ALL SABSONGROLMD WHERE 14MATED ON <br />DRAWINGS. SEAMS LAPPED B INCHES AND SEALEDMIH ADHESIVETME <br />FORM -WORK - <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORMWORK. <br />WOOD: <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FSCR 2020, 781 EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION. OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP 92, <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A1D64/Al064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE <br />WONT TRUSSES: <br />ETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />ACI TYPICAL DD <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE •NATIONAL DESIGN SPECIFICATIONS FOR <br />TION AND SITE PREPARATION <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION <br />H WAY, <br />SUPPORTE WITH 2"CWURS SPACED 3'-0"OC EACH <br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SWILL BE SIGNED AND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />T PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />O WORK <br />REBAR SHALL BE ASTM A615A615M GRADE 40 IN CONCRETE DEFORMED BARS REBAR SHALL BE ASTM A615 <br />MEETING THE REQUIREMENTS OF ASTM A446IA446M, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14. "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL-PLATE-CONNECTED-WOODTRUSS CONSTRUCTION:, AND "SCSI LATEST EDITION" <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 psf TOP CHORD-rpD-mnameM <br />RANDEVI <br />TYP, MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25' #6 BAR _ 36• <br />WOOD TRUSSES. <br />10 psf BTM CHORD -DON-m1lWrreet <br />fly BAR - 30' #7 BAR - 42" <br />MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING DEAD LOADS FOR THE ROOF <br />PROVIDE 36' x 36. CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATITRUSS <br />WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />REQUIRING AD <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />7 88: 1 <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSUASCE 7 88: 1990. <br />INTERSECTIONS <br />18 psf TOP CHORD 20 PST 70P CHORD <br />IT psf ASPHALT SHINGLES) psSf W/ No GYPCRE7E) <br />(1 <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS. <br />BTM CHORD 5 5 p psf BTM CHORD <br />10 PST13 <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />WALL. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />BALCONY LIVE LOAD 60 PST <br />STAIRS LIVE LOAD 40 Tod <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS DOWEL ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS AGUIDE FOR BEARING <br />WIND: DEAD LOAD SPEED =20) MPH SECOND GUST <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER LS RESPONSIBLE FOR FINAL <br />S <br />(NICE EXPOSURE C, RISK CATEGORY II) <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />BIT BLE(FBC ATTIC <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WITH LIMITED <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30pa/, BALCONIES (EXTERIOR) <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUST FABRICATOR SHALL <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />MIRY" <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BV A FLORIDA <br />4OW <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW; <br />'SPECIFICATION MASONRY STRUCTURES' (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm = 2000 PSI. BLOCK SWILL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE $HOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATIOW SITE PREPARATION: <br />"S" <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING <br />TYPE'M' OR MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE <br />SHALL BE 3W THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILLCM CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEOTECMNICAL ENGINEER TO VERIFY <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />CONCRETE: <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />BTH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, STRUCTURAL STEEL SHALL BE ASTM <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />/ F = 36 W FOR ANGLES PLATES AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A36 A36M Y <br />ASOD/A50 GRADE B F = 46 NN. STRUCTURAL PIPE SHALL BE ASTM A53/A53M GRADE BTYPE E OR S. F = <br />Y � � � Y <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />B <br />35 kel. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />3.000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />CONTRACTOR SHALL SUBMIT PROPOSED PAX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MX PRIOR TO <br />BOLTS TURNED ELEMENT. BOLTS <br />WASHERSUNDERMETH <br />OTHER BOLTS SHALL BE ASTMRDAN <br />CONCRETE RPCEENT. CONCRETE SLUMP SHALL NOT EXCEED SN- PRIOR TO THE ADDITION OF PLASTICIZER <br />EWIT HURNH D. <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM CWa4MOR MEASURING. MIXING. TRANSPORTING <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL.J-BOLTS ARE TO BE STEEL, <br />ETC. CDNCRETE TICKETS SMALL BE TI ESTAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM THE ALLOWED FROM MEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 98 MNUTES. IF FORANY REASON <br />THERE IS A DELAY N SUCH THWTA BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SWILL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A TFOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER: <br />1-10 FOR A5AND SMALLER <br />2'FOR XB AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />31C FOR SUBS, WALLS AND JOISTS <br />1-112" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APRICATgN <br />9¢E <br />TYPE <br />SPACMG <br />REAtARxS <br />APPLIGTAxtl <br />&2E <br />THE <br />AEMAPo6 <br />bQ fR FUNiNG TO <br />MASONRY/RING. <br />CASEHMOENED COIL <br />?LONG. <br />GARAGE DOIX2BUCX <br />TO MASONRYICCNC. <br />v�DY. <br />NO WASHER <br />TAMANMABONtY <br />FASTENER <br />I <br />11?EAx3E-0.,fEN005T., <br />t?EDGE 05T, <br />SGOpK.EJ(t. .. <br />tx T, 9EE NOlEB <br />NFD COB. <br />?LONG. <br />PIXC <br />STAGGERED <br />WMDGVA%1JR/FASTENED <br />MID NASOMTroONG <br />GARAGE DOORBUp( <br />TO NASONRYICONC. <br />1?DN.W/ <br />WASHER <br />EXPANBx1N BOLT <br />2-- <br />A•FMB GEDIST T <br />3'EDGE DUST. <br />wMDow aNtac <br />tx PT, sEE NOTEe <br />" 1?ianc: <br />sT ccERED <br />WMDr vAroow <br />Mro w,sorxr�coNc. <br />wTALSTRAPTG <br />AusoNRrlca+c. <br />CONTACT <br />THIS ENGINEER FOR SPACING <br />REQUIREMENTS <br />FXi.9WMGDWR <br />BUCK 2,f?. SEE NOTE6 <br />R�11189N. <br />WARIER <br />F-ER <br />FASTNER <br />16•� <br />tt?FM£0.8'END, <br />D5T.,11?EDGE DST. <br />NONBE0 WOW <br />WILL TO CONE 9lA8 <br />1? EXPANSION 24 dC �EABED.fEND <br />WI WASHER T BOLDUST., 3'EDGE 05T. <br />mPf WMOdN BUCK 8139'PAFa21A" TOC :END.DIBT.,t1? <br />T09TCOL.. SEE WI WABIiER 9TAGGERED EDGE DIBT. <br />I STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPUCATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILT] X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME, 1x MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />• <br />1441 N. RONALD REAGAN BLVD- <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-7744078 <br />www.abdesigngroup.com <br />AA #: 0003325 <br />4 <br />g <br />Y <br />U1 <br />o <br />Mg <br />C <br />j <br />og <br />Ll <br />_LLL <br />SUHDIV. a# TAT: <br />ABBOTT PARK <br />LOT #4 <br />BLK. #11 <br />1p'noizcT# <br />04181.000-04111 <br />HoDmi:" <br />3EAB <br />1504- ALLEX" <br />GARAGE SWING: <br />LEFT <br />PAGE: <br />DETAILS <br />1 PH E " C <br />