HIP
<br />_ LPL
<br />ROOF WIND DESIGN PRESSURES
<br />NET(GROSS) ASCE 7-16
<br />ZONE 1 = 23.79 PSF (33.79)
<br />ZONE 2 = 39.48 PSF (4948)
<br />ZONE 3 = 67.16 PSF (77:16)
<br />"A"= 4'-0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />WIND EXPOSURE: "C"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT w 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32" STRUCTURAL SHEATHING
<br />EXP 1 (4020). FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN.
<br />19/32" STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD
<br />AND EDGE SPACING) SEE DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN
<br />NAILS @ 4" O.C. EDGEWISE 2X4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF
<br />GABLE END.
<br />ROOF/ WALU FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />[AICNTc
<br />SIZE
<br />HEAD
<br />LENGTH
<br />DI.
<br />TENSILE STR.
<br />SHANK
<br />ASTM
<br />10d
<br />RING SHANK,
<br />212"
<br />0.131
<br />1697
<br />SCREW SHANK
<br />170.000
<br />RING
<br />(16-20 RINGS
<br />RSRS-03
<br />Sd
<br />RING SHANK,
<br />2 3/9'
<br />0.113
<br />F1667
<br />SCREW SHANK
<br />PER INCH)
<br />RSRS-01
<br />8d
<br />RING SHANK,
<br />PNEUMATIC
<br />2319'
<br />0.113
<br />Fi667
<br />SCREW-WULS
<br />RSRS-01
<br />HAY I EH UK I HUb
<br />ROOF SHEATHING
<br />EXTERIOR SHEATHING
<br />USE 12" COX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4"
<br />O.C. AT PANEL SIDES AND $d RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND Sd RING SHANK GUN NAILS AT 6" O.C. AT
<br />INTERMEDIATE SUPPORTS OR 7/16"ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.I SEE DETAILAk . BUILDING LENGTH
<br />IV
<br />ROOF SHEATHING LAYOUT
<br />AND ENOWALL BRACING
<br />FOR GABLE END FRAMING
<br />NOTE GABLES-OROP GABLE END & (1) ADD'L DROPPED
<br />TRUSS 2X4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING @
<br />16"O.C. IF NO DROPPED GABLE END, ATTACH 2X4 #2 SYP
<br />BLOCKING @ 16" O.C. FIRST 4 BAYS WI (2)12d NAILS EA.
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/
<br />BLOCKING PER NAILING SCHEDULE
<br />ZONE 1: 10d NAILS @ 4" O.C. ON EDGE AND 6" O.C. IN FIELD
<br />ZONE 2e, 2n, 2r 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />ZONE 3,3e, 3r. I Od NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />8d RING SHANK GUN NAILS @ 4" O.C.
<br />„ TOP & BOTTOM EDGES .1
<br />N
<br />w
<br />z ❑
<br />O,W
<br />z o
<br />x0= O
<br />E7
<br />z
<br />. 10d RING SHANK GUN NAILS
<br />SEE "ROOF SHEATHING ATTACHMENT'
<br />TABLE FOR FIELD SPACING 1
<br />C#8 2" DECK SCREWS @ 6-4r O.C. MAX '@
<br />EDGES & 17 O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING `
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORMTO ASTM C3VC33M MADMUYAG(MEGATE SIZE SHALL BE 3W.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />WOOD.
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />pppwpE B%A82 ENTRAINED CONCRETE EXPOSED TO EARfHORWEA7HER
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBCR 2020, 7th EDITION
<br />ALL EXpPEDGES OF CONCRETE ARE TO BE CHAMFERED 3M'.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />CRIPPLERS. SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER FIS =1100 PSI AND A MODULUS OF
<br />FOR STRUCTURAL CONCRETE, TMS 402JO02-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER YEMBRAfE UNDER ALL SLAB.SONGFOUD WIEIE INDICATED ON
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016. ASCE 7-16 AND AISC SPECIFICATIONS
<br />PROVIDES. SEAMS NAPPED 6INCHEAND SEALED WITHRRIERADHESIVE TAPE.
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORMWORK:
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE, NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN X' OF HEARTWOOD.
<br />ALL OWENSIDNS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCL j`)ONS FfM THESE PLANS:
<br />MINIMUM NAILING PER FBOR 2020, 71h EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION. FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2X STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP #2.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WARE MESH"
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE
<br />WELDED WIRE MESH, SHALL BE ASTM A1064/AI064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE
<br />WOOD TRUSSES:
<br />-DOWNS.
<br />ACI TYPICAL DETAILS. MINIMUM LAP $HALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />BE SUPPORTED WITH 2' CHAIRS SPACED Y-O' OC, EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />T N CONTRACTOR AN SUBCONTRACTOR SWILL VERIFY ALL DIMENSIONS PRIOR
<br />DO NO SCALE DRAWINGS. THE COAT OR D B
<br />REINFORGNG STEEL
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS AND MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />SHALL BE ASTM GRADE 40 IN CONCRETE DEFORMED BARS, SHALL ASTM A615
<br />A E A, A A
<br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SWILL BE HOT-0IPPED GALVANIZED.
<br />GREBARRADE DEFORMED AND PLACED A
<br />GRADE BO IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />DESIGN LOADS:
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TP-14,'DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT RESAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND 'BCSI LATEST EDITION"
<br />AND U VERTICAL BARS SHALL LAP 6 X BAR NO. UNSCHEDULED FIELD PS ARE SUBJECT TO ENGINEERS
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 PSI
<br />REVIEW,
<br />WOOD TRUSSES.
<br />20 psf TOP CHORD+wIFmnclafent
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: 94 BAR - 25' #6 BAR - 36'
<br />10 Pat BTM CHORD -ron-m iC nl
<br />#5 BAR - 30" 97 BAR - 42"
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 36' X 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM RESAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990.
<br />15 pef TOP CHORD 20 PST TOP CHORD
<br />IT pst w/ ASPHALT SHINGLES) (10 pef wl NO GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS.
<br />10 psf BTM CHORD 5 psf BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opsf
<br />MINIMUM 101NCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 paf
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 psf
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />WIND: DEAD LOAD SPEED=10) MPH SU SECOND GUST
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />(NICE (FBA EXPOSURE C, RISK CATEGORY ID
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />BIT UNINHABITABLE ATTIC WITH LIMITED
<br />LAVE LOADS: UNINHABITABLE TABLE ATTIC WITHOUT STORAGE:
<br />ATTIC
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUR ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />WITH BALCONIES (EXTERIOR)
<br />STORAGE:: ATTICS AND ATTICS SERVED WITH FIXED STAIRS:
<br />WITHOUT THE APPROVAL Of THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />NTS:
<br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: SOpsi, PASSENGER
<br />40p f,HABITABLEGUDS
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS:
<br />MASONRY:
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />40psf
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW;
<br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH. ELEVATIONS, DIMENSIONS, ETC.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE nn = 2D00 PSI. BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BE BEFORE
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PU ING CONCRETE FOR IN -WALL COLUMNS, GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318"
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8' TO 10", USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATIOW SITE PREPARATION:
<br />TYPE'M" OR'S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PSI, FOOTING
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM 0-1557, TREAT ALL CELLS TO BE FILLED.
<br />SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />250D PSI REGULAR WEIGHT FOR FOOTINGS AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />CONTACTOR SHALL SUBMT PROPOSED MX DESIGNS WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED T-4-PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REOUREMENTS OF ACI 318AND ASTM Q)VC MM OR MEASURING, MIXING, TRAKSP(MONG,
<br />ETC. CONCRETE TICKETS SWILL BE TIMESTAAPEDWHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN
<br />WATER IS ADDED TO THE MO( UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FDA ANY REASON
<br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL
<br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPL ANCE WITH THE ABOVE.
<br />RED RED CONCRETE COVERAGE OVERREBAR $HALL BE AS FOLLOWS:
<br />A 3- FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS)
<br />B. FOR CONCRETE EXPOSED TO EARTH ANDQRWEATHER
<br />1-17Y FOR 85 AND SMALLER
<br />7 FOR US AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3/4' FOR SLABS, WALLS AND JOISTS
<br />1-1!!' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL RESAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />STRUCTURAL STEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36/A38M, Fy = 36 ksl FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />ASDO/A500M, GRADE B, Fy = 46 ksl. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S. Fy =
<br />35 kN. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS
<br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APRIGTIDNSUETYPE
<br />SPACNG
<br />REMAPo(3
<br />APPLIGTpN
<br />SITE
<br />TYPE
<br />SPACING
<br />IRFIAAR(S
<br />FURRwG TO
<br />1NASIXIRYI CONE
<br />—E HMOEIEOOOX
<br />NAIL 11?LOAD.
<br />S�
<br />GAMGE COORSIICK
<br />TO MASONRYICONO.
<br />tq' DU.
<br />NO WASHER
<br />TAPCON NASIXAY
<br />FASTENER
<br />e„
<br />E.D6r.,
<br />11/Y EDGE DIST,
<br />--DOORS
<br />l T,SEE NOTES
<br />CASENARDENEDODL
<br />11?LONG.
<br />OIC
<br />AGGEREO
<br />WcnowmaaaFASTENED
<br />INTO UAWMYAANC.
<br />GARAGEDOM—
<br />TO NMWNRYM.ONO.
<br />N 'LAWN
<br />WASHEA
<br />EJIPN19pN BOtT
<br />O�
<br />/•ENABED.. A•ENOOBT_
<br />EDGE DISi.
<br />wsnvW awX
<br />DOSE NAADEAEDDDE
<br />wsaovuooaw PABTENEO
<br />EE__TO
<br />CONTACT
<br />THIS ENGINEER FOR SPACING
<br />. Pr. sEE NOTEe
<br />1IS LONG.STA
<br />RED
<br />MO MASOMYI c.
<br />MASONRY ICONO.
<br />REQUIREMENTS
<br />El(T. SWING DOOR
<br />BUIX pT,EEE_.
<br />(2)3H89U.
<br />NOWASHER
<br />TAPCpI-
<br />FASTNER
<br />1H'�
<br />11I3•EMIED,CEND.
<br />.11rz'EDGE 06T.
<br />NON6EARNGwOOD
<br />WALL TO LONG. SLAB
<br />1/Y EXPANSION PEMBED.YEND
<br />WI WASHER BOLT sd dG DIST.,3E-E06T.
<br />9i PT WwDOW&1CI( 0N3B°PAFA2ll3• POIC END.GIST,I—
<br />PTTOSTEEL COL.,SEE W/WASHER STAGGERED EDGE DBT.
<br />NOTES
<br />NOW
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW ANO DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. I MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD
<br />LONGWOOD, FL 32750
<br />PM: 407-774-6078
<br />FAX: 407-7741078
<br />wwwAbdesigngroup.com
<br />AA #: 0003325
<br />W
<br />4
<br />�
<br />q
<br />aUEMIV. Ae Lotil
<br />ABBOTT PARK
<br />LOT #3
<br />BLK #11
<br />PitOJECT#
<br />04181.000-03111
<br />i[ODEL
<br />4EBB
<br />"1828-CALI"
<br />GAP—*.GZ awtrrG:
<br />LEFT
<br />PAGE:
<br />DETAILS
<br />160 PH W. C
<br />A.
<br />DP 01/19/21
<br />SCALE: 1/4"=1'-0"
<br />SHEET
<br />s N1
<br />
|