<br />ROOF WIND DESIGN PRESSURES
<br />NET ASCE 7-10
<br />ZO.V'ROSS) 8.97 PSF (19.97)
<br />ZONE 2 17.98 PSF (27.98)
<br />ZONE 3 33.53 PSF (43.53)
<br />'A"V-O"END ZONE DISTANCE
<br />BASIC WIND SPEED: 150 MPH
<br />WIND EXPOSURE: "B"
<br />RISK CATAGORY: 11
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT - 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16"
<br />O.S.B. OR 112" COX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. W CDX EXT. PLYWOOD, WITH 8d RING
<br />SHANK GUN NAILS AT 4"O.C. AT SUPPORTED
<br />PANEL EDGES AND Scl RING SHANK GUN NAILS
<br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />8d GUN NAILS @ 4" D.C. EDGEWISE 2X4
<br />BLOCKING ALL PANEL JOINTS Wl IN 4'OF GABLE
<br />END,
<br />ROOF WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN. DIA
<br />SHANK
<br />TENSILE STIR.
<br />SHANK
<br />8d
<br />RING SHANK,
<br />2 1/2"
<br />OA20"
<br />170,000
<br />TlwT_
<br />6-20 RINGS
<br />SCREW SHANK
<br />INCH)
<br />8d
<br />SCREW SHANK
<br />2 112"
<br />0,120*
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION (ISANTA) ESR-1539
<br />EXTERIORSHEATHUNG
<br />USE 1/2" COX OR 7116" O.S.B. PLY WITH 8d RING
<br />SHANK GUN NAILS AT 4" D.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4"O.C, TOP &
<br />BOTTOM PANEL AND Sd RING SHANK GUN
<br />NAILS AT 6"O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7/16"ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />8d RING SHANK GUN NAILS @ 4" 0,C.
<br />TOP & BOTTOM EDGES
<br />11 r
<br />LU
<br />Z
<br />LU
<br />Z
<br />z
<br /><
<br />d
<br />0
<br />z
<br />z
<br />fr
<br />TO
<br />cn
<br />LU
<br />z 0
<br />:D 0
<br />0 LU
<br />�d TO
<br />Z
<br />z
<br />�c
<br />P d
<br />051 ci
<br />z L:U
<br />z
<br />TOP CORD BLOCKING AT 4'
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END
<br />RAFTERORTRUSS
<br />ROOF SHEATHING
<br />mmm WIN
<br />EMMMML k
<br />milill
<br />BUILDING LENGTH
<br />ROOF SHEATHING LAYOUT
<br />ANO=ALLDRACING
<br />r
<br />FOR z H FRAMM
<br />8d RING SHANKGUN NAILS
<br />S' O.C. IN FIEUCf
<br />CSd IiING SHANK GUN �AILS @ 12" D.C. IN
<br />FIELD or Sd x 2 1 02"SCREW SHANK
<br />PNEUMATIC SCREW -NAILS @ 1 Z' 0.
<br />FIELD 7
<br />. . I I TYP. 3f4"T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS, APPLICABLE BUILDING CODE STANDARDS: FBCR 2017,6th EDITION
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, ACT 530-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011. ASCE 7-10 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO A14Y SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN�
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMUM AGGREGATE SIN SHALL BE 30r.
<br />PROVIDE S%AIR 841PAINED CONCRETE EXPOSED TO EARTH OR WEATHER
<br />ALL EMBED EDGES OF CONCRETE ARE TO BE CHAMFERED We.
<br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR HARRIER MEMBRANE UNDER ALL SUki3SONGROM WHERE INDICATED ON
<br />DRAWINGS SEAMS LAPPED 6 INCHES AND SEALED NTH ADHESIVE TAPE.
<br />FORWWOM
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 341,
<br />'RECOMMENDED PRACTICE FOR CONCRETE FOWWORK.
<br />WOOD:
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />CRIPPLERS ' SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0-25 PCF OF A SORATE PRESERVATIVE TREATMENT: DISODIUM
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS. SPIKE. BOLTS USED
<br />W, DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />CONTAINS MORE THAN WOF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2017, ft EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND MOD COLUMNS WITH 2X STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS,
<br />SYP 02.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE ILDING .11 ITS COMPONENTS
<br />WELDED WRE MESH:
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES,
<br />DURING ERECTION' THIS WORK INCL.D.:UTHE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GLTYS OR TtE-DOWNS.
<br />WELDED WIRE MESH. SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACT
<br />WOW TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SMALL BE
<br />SUPPORTED WITH 2"CHAIRS SPACED T-O' OC, EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE *NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS'BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />REQUIREMENTS AND SLA13-ON-GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />DESIGN LOADS:
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 pf
<br />20 pst TOP CHORD �curra"l
<br />10 p.1 STM CHORD ---Mt
<br />DEADLOAD DEADLOAD
<br />15 pEf TOP CHORD 20 pst TOP CHORD
<br />(7 pfW ASPHALT SHINGLES) (10 psf Wl No GYPCRETE)
<br />10 pf 8TM CHORD 5 pst BTM CHORD
<br />DEAD LOAD TO RESIST WIND UPLIFT: 1OPf
<br />BALCONY LIVE LOAD 00 PSI
<br />STAIRS LIVE LOAD 40 pef
<br />WIND: DEAD LOAD SPEED =150 MPH 3- SECOND GUST
<br />(ASCE 7-10 (FBC R2017) EXPOSURE B, RISK CATEGORY 11)
<br />LIVE LOAD& UNINHABITABLE ATTIC WITHOUT STORAGE: lOpEf, UNINHABITABLE ATTIC WITH LIMITED
<br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30pf, BALCONIES (EXTERIOR)
<br />AND DECKS: 40pef, GUARDS AND HMDFWLS: 200psf, GUARD IN -FILL COMPONENTS: 50pEf, PASSENGER
<br />VEHICLE GARAGES: SOpf, ROOMS OTHER THAN SLEEPING ROOM: 40pEf. SLEEPING ROOMS: SOW. STAIRS:
<br />40W
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />OF THE CONTRACT DOCUMENTS ONLY. IT $HALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS. ETC
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO T14E ARCHITECT.
<br />DRAWNGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />WRITING BY THE ARCHITECT.
<br />FOUNDATION/ SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PEI!, FOOTING
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557, TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />REINFORCING STEEL:
<br />REBAR SHALL BE ASTM A6`15 GRADE 40 IN CONCRETE DEFORMED BARS. REBAR SHALL BE ASTM A6`15
<br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />Wt THE TYPICAL SENDING DIAGRAM AND PLACING DETAILS OF THE ACT STANDARDS AND SPECIFICATIONS.
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS
<br />REVIEW.
<br />TYP. MIN LAPS SHAUL BE AS FOLLOWS: #4 BAR 25' #6 BAR 36'
<br />#5 BAR 30" 07 BAR 42"
<br />PROVIDE 36'x 36* CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />WALL.
<br />RUN REINFORCING BARS C014TINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />WITHOUT THE APPROVAL OF THE ENGINEER,
<br />MASONRY:
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />"SPECIFICATION MASONRY STRUCTURES' (ACT 5301 ASCE 517M$ 402, BUILDING CODE REQUIREMENTS FOR
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />MANUFACTURED IN CONFORMANCE NTH ASTM C-90, GRADE f. - 1600 PSI. BLOCK SHALL BE PLACED USING
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />ASTM C-476 AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8'
<br />COURSE AGGREGATE. AND SHALL BE PLACED W/ A SLUMP OF 8'TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />TYPE 'M"OR"S"MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL BE 318"THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUS1014S THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHN ICAL ENGINEER TO VERIFY
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANDIOR VERTICAL
<br />REINFORCING.
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS, LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY. AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />TR TURAL TE
<br />S UC S EL:
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />CON0%-rE:
<br />S PECIFICATIONS FOR THE DESIGN. FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS.
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOULOW$:
<br />9 TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36, Fy - 36 ksl FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-W. GRADE B,
<br />Fy - 46 kel. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE 8, TYPE E OR S. Fy - 36 MI. TUBE AND PIPE
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAH-ON-GRADE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5- STRUCTURAL TERRACE SLAB,
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />CONTRACTOR SHAU. SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />OTHER BOLTS SHALL BE ASTM A326-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED T -i- PRIOR TO THE ADDITION OF PLASTICIZER
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND AS TIM C44 OR MEASURING, WONG, TRANSPORTING, ETC ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />CONCRETE TICKETS SHAU. BE TIME -STAMPED WHEN CONCRETE M HATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS
<br />ADDED To THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION $HALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS A
<br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT $HAUL BE THE
<br />RESPONSIBILITY OF THE TESTING U430RATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON
<br />COMPUANCE NTH THE ABOVE
<br />REWRED CONCRETE COVERAGE OVER RESAR SHALL BE AS FOLLOWS:
<br />A TFOR CONCRETE CAST AGAINST AND PERMANENTLY D"m TO EARTH (FOUNDATIONST
<br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER,
<br />I :1/2"FOR16ANDSWLER
<br />Z FOR #8 AND LARGER
<br />C� FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3/4, FOR SLABS, WALLS AND JOISTS
<br />I -Mr FOR BEAM AND COLUMN PRIMARY REINFORCEMENT. TIES, STIRRUPS
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036* AND BE MANUFACTURED FROM STEEL
<br />MEETING THE REQUIREMENTS OF ASTM A446. GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED.
<br />DESIGN. FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI14, MESIGN NATIONAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:. AND `TPINVTCA BCSI 1"
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />WOOD TRUSSES.
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A68.1-1982.
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />TRUSSESIGIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUT$ THAT
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />LICENSED PROFESSIONAL ENGINEER.
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER $HALL BE RESPONSIBLE FOR
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />3�
<br />T�
<br />SPACM
<br />RE�
<br />—E
<br />I —
<br />_F Doo.
<br />G—GE 00-8—
<br />—.7 `�
<br />c
<br />T.
<br />�l I c-c
<br />To —0—
<br />EFI
<br />FAETENER
<br />i 1� EDGE D
<br />HARDENED
<br />w—,—..
<br />—E---
<br />E
<br />I'l-ED,IE-0-,
<br />L I
<br />E1E.D
<br />�yl�
<br />r EDGE D
<br />—NED—
<br />I—F—ED
<br />--TO
<br />CONTACT THIS ENGINEER FOR SPACING
<br />SEE
<br />ETAGGE..
<br />_
<br />—,—c.
<br />REQUIREMENTS
<br />��) .,
<br />IAP—'
<br />c
<br />1. IDAEE.�N.
<br />—RINGWOOD
<br />I- I E 1. 1 EID
<br />�NGDOOR
<br />—P, SEENOTE.
<br />NO -.ER
<br />F
<br />Gl
<br />I-, I — EDGE -T
<br />To cmc.
<br />—ER MET, EDGE DIST
<br />. , wN_ — I .E=tLT,,�7]
<br />P-oSTEELCOL,-E
<br />NOTEB
<br />1, STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2 . FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO F RAMING 13UCKS SHALL BE AS PER MANUFACTURERS SPECS AND I OR NOA
<br />3 ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF $HALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />6 FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NQA OR THE $PACING DETMLED ABOVE
<br />B. DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1� MEMBERS ARE NAILED AND
<br />2x== SECURED W1 TAPCONS OR PAF TO THE SUBSTRATE.
<br />A RONIT ICTS
<br />6
<br />aNsoln
<br />gn
<br />Group,,
<br />441 N. RONALD REAGAN BLY
<br />LONGWOOD, FIL 32750
<br />PH: 407-774-6076
<br />FAX: 407-7744078
<br />www.abdesigngmup.com
<br />AA 111: 0003325
<br />DRAFTING BY:.
<br />A.B. DESIGN GROUP
<br />DRAFTING INC.
<br />5439 BEAUMONT CENTER BLVD.
<br />SUITE 1004
<br />TAMPA, FLORIDA 33634
<br />PH: 813408-2628
<br />FAX: 8134MG-28021
<br />lu
<br />FIEUDDIV. at LOT,
<br />SILVERADO
<br />LDT #25
<br />1
<br />BIK #10
<br />Pvt0jmcT#
<br />03719.000-25101
<br />MODZLS
<br />2795—D
<br />0ARAC;E 13WINCII:
<br />RIGHT
<br />PAGW.
<br />DETAILS
<br />150 MPH EV.
<br />mPp-l"T 7/28/20
<br />DA71M
<br />c
<br />L"r
<br />SN1
<br />
|