.ME — f__2i_f <br />w <br />ROOF WIND DESIGN PRESSURES <br />NET (UROSS) ASCE 7-10 <br />ZONE 1 8.97 PSF (19.97) <br />ZONE 2 17.98 PSF (27.98) <br />ZONE 3 33.53 PSF (43.53) <br />"A7- 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE:"B' <br />RISK CATAGORY: H <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT , 0.18 <br />ROOF DIAPH <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16" <br />O.S.B. OR 1/2"CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. SfB COX EXT, PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4"O,C. AT SUPPORTED <br />PANEL EDGES AND Sd RING SHANK GUN NAILS <br />AT 6"0 * C ' AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />8d GUN NA LS @ 4" O.C. EDGEWISE 2X4 <br />BLOCKING AL PANEL JOINTS W/ IN 4'OF GABLE <br />END, <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. CIA <br />SHANK <br />TENSILE STR. <br />SHANK <br />Sd <br />RING SHANK, <br />2 1/2" <br />0. 120" <br />170,000 <br />RING <br />6_2G RINGS <br />SCREW SHANK <br />ER INCH) <br />Scl <br />SCREW SHANK <br />2 1/2" <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />I NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTUtM SHEATHING <br />USE 1/2"COX OR 7/1 6"O.S.B. PLY WITH Sd RING <br />SHANK GUN NAILS AT 4" D.C. AT PANEL SIDES <br />AND 8d RING SHANK GUN NAILS 4"O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT 6� D.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16"ZIP SHEATHING SYSTEM (INSTALLED <br />PERMANUF . SPECS.) SEE DETAIL. <br />R <br />Z LU <br />Z a <br />C3 <br />ul <br />zo <br />m d <br />0) <br />8d RING SHANK GUN NAILS @ 4- O.C. <br />TOP & BOTTOM EDGES <br />. . . . . . . . . <br />. . <br />zs <br />z <br />z z <br />2, <br />c <br />L) <br />z <br />. . . . . . . . . <br />. .. <br />Lu <br />M 0 <br />0 w <br />Nd a <br />z <br />�d <br />to d <br />'Lu <br />a <br />0 <br />UJ <br />z <br />CL <br />TOP CORD BLOCKING AT 4' <br />D.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END <br />RAFTERORTRUSSn <br />OR <br />§ <br />ROOF SHEATHING LAYOUT <br />AND <br />POR "NDWA==G <br />No <br />8d RING SHANK'GUN NAILS <br />6' O.C. IN FIELD <br />Scl FiING SHANK GUN NAILS @ 12" D.C. IN <br />FIELD or 8d x 2 112" SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 12" 0. <br />FIELD 7 <br />ryp. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS, CONSULT <br />A Ftr <br />_HITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017. ft EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, ACI 530-131ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD�FORMED STEEL STRUCTURAL MEMBERS 2011. ASCE 7-10 AND AISC SPECIFICATIONS <br />ALLDE ILS AND SECT ONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />TA I( <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN, <br />ALL DIMENS DNS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />I( <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE4)OWNS. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC33. MAXIMUM AGGREGATE SIZE SHALL BE 3W <br />SUPPORTED TWOC EACH <br />ROOF SHEATHING LAYOUT <br />AND <br />POR "NDWA==G <br />No <br />8d RING SHANK'GUN NAILS <br />6' O.C. IN FIELD <br />Scl FiING SHANK GUN NAILS @ 12" D.C. IN <br />FIELD or 8d x 2 112" SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 12" 0. <br />FIELD 7 <br />ryp. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS, CONSULT <br />A Ftr <br />_HITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017. ft EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, ACI 530-131ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD�FORMED STEEL STRUCTURAL MEMBERS 2011. ASCE 7-10 AND AISC SPECIFICATIONS <br />ALLDE ILS AND SECT ONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />TA I( <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN, <br />ALL DIMENS DNS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />I( <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE4)OWNS. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC33. MAXIMUM AGGREGATE SIZE SHALL BE 3W <br />SUPPORTED TWOC EACH <br />WOOD: <br />PROVIDE Q%AIR 89MNED CONCRETE EXPOSED TO EARTH ORINEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3W. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING. <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDERALL SLABSON-GIRCIUND WHERE INDICATED ON <br />CRIPPLERS ' SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF <br />ELASTICITY = 1.400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />DRAWINGS. BEAMS LAPPED 6 INCHES AND SEALED WITH ADHESIVE TAPE. <br />PRESSLRE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0,25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />FORM -WORK <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />FORM -WORK. SHORING. AND BRACING FOR ALL CONCRETE BEAMS, SLABS. COLUMNS. WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS. SPIKE, BOLTS USED <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH AC 1347, <br />W DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN %* OF HEARTWOOD. <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 20`17,6th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION. FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAILDEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH ZX STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />UNTREATED WOOD SKALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WELDED WIRE MESH, SHALL BE ASTM Al 85, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />WOOD TRUSSES: <br />TYPICAL DETAILS, MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIFE MESH FOR SLABS SHALL BE <br />WITH TCHAIRS SPACED WAY <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE 'NATIONAL DESIGN SPECIFICATIONS FOR <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />STRESS -GRADE LUMBER AND ITS FASTENINGS'SY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />00 NOT SCALE DRAWINGS , THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0,036* AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A815 GRADE 40 IN CONCRETE DEFORMED BARS. REBAR SHALL BE ASTM A615 <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL. SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOAM: <br />W1 THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE. AND ERECT MOD TRUSSES IN ACCORDANCE WITH TPI-14,"DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION, HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND 'TPVWTCA BCSI V <br />ROOF: LIVE LOA FLOOR: LIVE LOAD 40 <br />AND VERTICAL BARS SHALL LAP 8 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />pf <br />20 psf TOP CHORD --rt <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR 36" <br />WOOD TRUSSES. <br />10 psf BTM CHORD �nl <br />#5 BAR - 30" #7 BAR 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36* x 36"CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982. <br />15 pal TOP CHORD 20 PST TOP CHORD <br />Q FIT - ASPHALT SHINGLES) (10 psfwl No GYPCRETE) <br />ALL VERTICAL REINFORC ING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 POT BTM CHORD 5 psf STM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WHO UPLIFT: IOPSI <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 PSI <br />WALL. <br />TRUSSESIGIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 Par <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />WIND: DEAD LOAD SPEED =1 60 MPH 3. SECOND GUST <br />(ASCE 7-10 (FOC R2017) EXPOSURE B, RISK CATEGORY 11) <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10p.1, UNINHABITABLE ATTIC WITH LIMITED <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20pf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30pV, BALCONIES (EXTERIOR) <br />Do NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40prf, GUARDS AND HANDRAILS: 200pd, GUARD IN -FILL COMPONENTS: 50Pf. PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40pef, SLEEPING ROOMS: 30p.1, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40psf <br />MMONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING P"EW <br />"SPECIFICATION MASONRY STRUCTURES"LACI 530/ ASCE HITMS 402, BUILDING CODE REQUIREMENTS FOR <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SH P DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />0 <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER, <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH. ELEVATIONS. DIMENSIONS, ETC. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />A LL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE f. = 2000 PSI. BLOCK SHALL BE PLACED USING <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C-476 . AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 2a DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIF ICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3w <br />WRITING BY THE ARCHITECT, <br />COURSE AGGREGATE , AND SHALL BE PLACED W/A SLUMP OF S"TO 10'. USE ONLY MECKANICALVtBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATIOW SITE PREPARATION: <br />TYPE'M"OR"S"MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHAUL BE <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 Pat FOOTING <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE <br />SHALL BE 3/8'THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM 0-1557, TREAT ALL <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANDIOR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />REINFORCING, <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR e X BAR NO. (48 BAR DIAMETERS).. U.N.O. <br />CONTRACTORS EXPENSE. AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />STRUCTUM STEEL <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHAll SUBMIT PROPOSED WX DESIGNS, WITH HISTORICA STRVWTH DATA FOR EACH SEPARATE WX PRIORTO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5'q. PROR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY NTH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C-04 OR MEASLRING, MIXING, TRANSPORTING, E TO <br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS HATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS <br />ADDED To THE MX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SH&L NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS A <br />DELAY IN SUCH THAT A HATCH IS HELD FOR LOWER THAN 90 MINUTES, THE CONCRETE W&L NOT BE PLACED. IT SHALL BE THE <br />RESPONSIBILITY OF THE TESTING LA80RATORY TO NOTIFY THE OWNERS REPRESENTATIVE A14D THE CONTRACTOR OF ANY NON <br />COMPLONCE WITH THE ABOVE, <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />k 7 FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONSY. <br />B. FOR CONCRETE EXPOSED TO EARTH ANDOR WEATHER: <br />I-10FORMISANDSMAU.0 <br />FOR 03 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3fe FOR SLABS, WALLS AND JOISTS <br />I-1,2"FOR SM AND COLUMN PRIMARY REINFORCEMENT, TIES. STIRRUPS <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION. BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />ASS. Fy . 36 k6l FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE 8, <br />Fy - 46 ks]. STRUCTURAL PIPE SHALL BE ASTWS3, GRADE B, TYPE E OR 8, Fy = 35 ksi. TUBE AND PIPE <br />COLUMNS SHALL BE OONCRETE-FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325­N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT, BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL, J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />E. <br />— <br />I <br />— <br />..E <br />I — <br />14IF—EWTO <br />DAE.—E.— <br />G—E— <br />To—y—D. <br />1A.D.. <br />ER <br />­y <br />E—ENER <br />I-EMSED.A-E ..T., <br />_.. Or <br />-.AL E­ <br />W-0—TEW <br />E­­ <br />1— <br />IE—D.,'E- T.. <br />1.1,E..TE. <br />mill— <br />TA..E— <br />To__ <br />7 EWE DOT <br />W—W.. <br />­111 <br />CONTACT THIS ENGINEER FOR SPACING <br />—.5—TE. <br />mIL 1 1— <br />EIAWERED <br />REQUIREMENTS <br />q)�­ <br />_­ <br />is-WD <br />1 ­EMBE.,IrE�. <br />EXIZ- 18MED.— <br />..I.EI,IGTE6 <br />NO —ER <br />1.1— <br />D.T., I_ EDGE DOT. <br />—0— <br />T D*T., 3- EDGE DOT. <br />STEEL 1E. Im <br />IT. — E I o, Wl TADZEED ED. D.T., I <br />e DIET <br />"GM <br />I . STAPLES $HALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO F RAMING SUCKS SHALL BE AS PER MANUFACTURERS SPECS AND OR NOA <br />3� APLL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4 AF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE N0A OR THE SPACING DETAILED ABOVE <br />6 WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR ODER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. lx MEMBERS ARE NAILED AND <br />N MEM13ERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE, <br />C T 8 <br />MrA <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FIL 32750 <br />PH: 407-774-6078 <br />FAX: 407-774-4078 <br />www.abdosigngroup.com <br />AA 111: 0003325 <br />r DRAFnNG BY: <br />A.B. DESIGN GROUP <br />DRAFTING INC. <br />5439 BEAUMONT CENTER BLVD. <br />SUITE 1004 <br />TAMPA. FLORIDA 33634 <br />PH; 813-886-2628 <br />FAX: 8134MO-2802 <br />o <br />m—lay <br />llu <br />rBUBDIV. 89 LCM`4 <br />SILVERADO <br />LOT #23 <br />BLK #10 <br />Pft0"wT# <br />03719.000-23101 <br />MODZU <br />2795— F <br />C;AP.AGZ 8`1111117NO: <br />RIGHT <br />PAGZ: <br />DETAILS <br />150 MPH EXP. B <br />F'PPANT 10/30 <br />DATE: <br />BCALIIII: 1/4"=l'—O" <br />811=T <br />SN1 <br />