ALL WORK DONE UNDER THIS CONTRACT SHALL BE IN COMPLIANCE WITH THE FLORIDA BUILDING CODE, RESIDENTIAL (FBCR}, 5TH <br />EDITION (2014) AND IN CONJUNCTION WITH ASCE 7-10. <br />2. THE MINIMUM SUPERIMPOSED DESIGN LOADS ARE AS FOLLOWS; <br />A FLOOR LIVE LOADS R301.5 (PSF) <br />1. SLEEPING ROOMS 30 <br />II. ATTICS W/ STORAGE 20 <br />III. ATTICS W/OUT STORAGE 10 <br />IV. POOLROOMS 75 <br />V. BALCONIES AND DECKS 40 <br />VI. STAIRS 40 <br />VII. ALL OTHER ROOMS 40 <br />B. FLOOR DEAD LOADS R301.4 15 (PSF) <br />C. ROOF LIVE LOADS R301.6 <br />I. "MINIMUM ROOF LIVE LOADS SHALL COMPLY WITH TABLE R301.6 OF THE FBCR 5TH EDITION (2014) <br />D. ROOF DEAD LOAD (PSF) <br />I. FIBERGLASS SHINGLES <br />17 (TCDL 7 & BCDL 10) <br />II. CONCRETE TILES <br />25 (TCOL 15 & BCDL 10) <br />E. WIND LOAD CRITERIA <br />I. BASIC WIND SPEED <br />VOLT--150 MPH, VASD=116 MPH <br />II. EXPOSURE CATEGORY <br />B <br />III. WIND DIRECTIONALITY FACTOR (KD) <br />0.85 <br />IV. INTERNAL PRESSURE COEFFICIENT (GCPI) <br />ENCLOSED BUILDINGS <br />t0.18 <br />V. RISK CATEGORY <br />II <br />F. WHERE BUILDING LOCATIONS ARE DETERMINED TO BE IN WIND BORNE DEBRIS REGIONS, ALL EXTERIOR BUILDING <br />OPENINGS SUCH AS WINDOWS AND DOORS SHALL BE PROTECTED AGAINST WIND BORNE DEBRIS BY THE INSTALLATION <br />OF STRUCTURAL PANELS OR IMPACT -RESISTANT GLASS. THESE OPENING PROTECTIONS SHALL BE DESIGNED AND <br />INSTALLED IN ACCORDANCE WITH CHAPTER 3, SECTION R301.2.1.2 OF THE FLORIDA BUILDING CODE, RESIDENTIAL, 5TH <br />EDITION (2014). <br />3. DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO WORK <br />PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />4. THE CONTRACTOR SHALL BRING ERRORS AND OMISSIONS WHICH MAY OCCUR IN CONTRACT DOCUMENTS TO THE ATTENTION OF THE <br />ARCHITECT IN WRITING AND WRITTEN INSTRUCTIONS SHALL BE OBTAINED BEFORE PROCEEDING WITH THE WORK. THE CONTRACTOR <br />WILL BE HELD RESPONSIBLE FOR THE RESULTS OF ANY ERRORS, DISCREPANCIES OR OMISSIONS IN THE CONTRACT DOCUMENTS, OF <br />WHICH THE CONTRACTOR FAILED TO NOTIFY THE ARCHITECT BEFORE CONSTRUCTION AND/OR FABRICATION OF THE WORK. <br />5. THE ARCHITECTIENGINEER SHALL NOT BE RESPONSIBLE FOR THE SAFETY AND CONSTRUCTION PROCEDURES, TECHNIQUES, <br />OR THE FAILURE OF THE BUILDER TO CARRY OUT THE WORK IN ACCORDANCE WITH THE DRAWINGS OR THE REQUIRED CODES. <br />6. THE STRUCTURAL DESIGN IS BASED ON THE INTERACTION OF ALL PARTS OF THE COMPLETED BUILDING. THE CONTRACTOR SHALL <br />SOLELY BEAR THE RISK FOR PROVIDING ADEQUATE STABILITY AND SAFETY OF THE STRUCTURE DURING CONSTRUCTION UNTIL <br />PERMANENT MEMBERS ARE COMPLETELY INSTALLED. <br />7. DETAILS SHOWN ON THE DRAWINGS ARE TO BE CONSIDERED TYPICAL FOR ALL SIMILAR CONDITIONS. <br />8. THE CONTRACTOR SHALL MAKE NO STRUCTURAL CHANGES WITHOUT WRITTEN APPROVAL FROM THE ARCHITECTIENGINEER. <br />9. NO STRUCTURAL MEMBERS ARE TO BE CUT FOR PIPES, DUCTS, ETC. UNLESS SPECIFICALLY DETAILED. <br />10, FLOOR ELEVATIONS AT REQUIRED EGRESS DOOR SHALL MEET PROVISION OF FBCR R311.3.1. <br />11. THE MINIMUM NET CLEAR OPENING HEIGHT WIDTH FOR EGRESS WINDOWS SHALL BE 24INCHES PER FBCR310.1.2. <br />12. THE MINIMUM NET CLEAR OPENING WIDTH WIDTH FOR EGRESS WINDOWS SHALL BE 20INCHES PER FBCR310.1.3. <br />GARAGES AND CARPORTS <br />1. GARAGE DOOR <br />A. ENGINEERED FOR 150 MPH MIN. WIND LOAD. <br />B. DETAIL TO BE SUPPLIED BY GARAGE DOOR SUPPLIER <br />C. DETAIL TO BE ATTACHED TO PERMIT PACKAGE BY BUILDER <br />2. PER FBCR 5TH EDITION (2014) R302.5.1: OPENINGS FROM A PRIVATE GARAGE DIRECTLY INTO A ROOM USED FOR SLEEPING PURPOSES <br />SHALL NOT BE PERMITTED. OTHER OPENINGS BETWEEN THE GARAGE AND RESIDENCE SHALL BE EQUIPPED WITH SOLID WOOD <br />DOORS NOT LESS THAN 1318INCHES IN THICKNESS, SOLID OR HONEYCOMB CORE STEEL DOORS NOT LESS THAN 1-3/8 INCHES THICK, <br />OR 20-MINUTE FIRE -RATED DOORS AND MUST BE EQUIPPED W/ A SELF -CLOSING DEVICE PER R302.5.1 OF FBCR (2014). <br />3. PER FBCR 5TH EDITION (2014) R302.5.2: DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS OR CEILINGS SEPARATING <br />THE DWELLING FROM THE GARAGE SHALL BE CONSTRUCTED OF A MINIMUM NO.26 GAGE (0.48 MM) SHEET STEEL 1- MIN. RIGID <br />NON-METALLIC CLASS OR CLASS i DUCT BOARD OR OTHER APPROVED MATERIAL AND SHALL HAVE NO OPENINGS INTO THE GARAGE. <br />4. PER FBCR 5TH EDITION (2014) R302.6 & TABLE R302.6: THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ITS ATTIC <br />AREA BY NOT LESS THAN %-INCH GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES BENEATH HABITABLE ROOMS <br />SHALL BE SEPARATED FROiv1 ALL HABITABLE ROOMS ABOVE BY NOT LESS THAN 518 -INCH TYPE X GYPSUM BOARD OR <br />EQUIVALENT. WHERE THE SEPARATION IS A FLOOR -CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE SEPARATION SHALL <br />ALSO BE PROTECTED BY NOT LESS THAN %rINCH GYPSUM BOARD OR EQUIVALENT. <br />SITE WORK <br />1. REFER TO THE SOILS REPORT FOR SPECIFIC DESIGN REQUIREMENTS. <br />2. REFER TO THE CIVIL DRAWINGS FOR LOCATION OF BUILDING WORKING POINTS, ROUGH GRADING, ON -SITE UTILITIES, SITE <br />IMPROVEMENTS, SITE RETAINING WALLS, AND SPECIFIC GENERAL NOTES. THE SOILS REPORT AND CIVIL DRAWINGS SHALL OVERRIDE <br />CONFLICTS WITH SITE WORK NOTED HEREIN.SEE LANDSCAPE DRAWINGS FOR FINAL FINISH GRADES, PLANTING AND IRRIGATION. <br />3. RATIONAL ANALYSIS WAS PERFORMED TO DETERMINE SIZE AND STEEL REINFORCING FOR ALL FOUNDATIONS. DESIGN WAS BASED ON <br />AN ALLOWABLE SOIL BEARING CAPACITY OF 2,000 PSF. TRANSFER REINFORCING (TOP STEEL) HAS BEEN DELETED UNLESS NOTED <br />OTHERWISE. <br />4. ELEVATIONS SHOWN ON THE SITE DRAWINGS ARE MINIMUM REQUIRED DEPTHS, IF DIFFERENT CONTACT THE ARCHITECT. <br />5. NO EXCAVATION SHALL BE MADE WHOSE DEPTH BELOW THE FOOTING IS GREATER THAN %THE HORIZONTAL DISTANCE FROM THE <br />NEAREST EDGE OF THE FOOTING. <br />7. COMPACTION BY FLOODING OR JETTING IS STRICTLY PROHIBITED. <br />8. DO NOT BACKFILL UNTIL SLABS HAVE CURED OR HAVE BEEN PROPERLY BRACED. (WHERE APPLICABLE) <br />9. EXCAVATIONS TO BE A MINIMUM OF 3'- 0" BEYOND NEW FOOTING LINE. <br />10. THE GENERAL CONTRACTOR MUST TAKE MEASURES TO CONTROL SOIL EROSION AS PER ALL LOCAL AND STATE REQUIREMENTS. <br />11. THIS BUILDING IS NOT DESIGNED TO BE CONSTRUCTED WITHIN A FLOOD ZONE, UNO. CONTRACTOR IS TO VERIFY THE ELEVATION <br />OF THE FINISHED FLOOR SLAB WITH THE SIGNED AND SEALED SURVEY WHICH COMPLIES WITH ALL LOCAL CODES HAVING <br />JURISDICTION, INCLUDING ALL APPLICABLE STATE, CITY, AND COUNTY BUILDING AND ZONING CODES. <br />12. SWIMMING POOL, DECK, SPA, AND ASSOCIATED WORK IS TO BE PERMITTED SEPARATELY BY ENGINEERED SHOP DRAWINGS. <br />CONCRETE <br />1. ALL CONCRETE WORK SHALL COMPLY WITH THE LATEST EDITION OF THE STANDARD SPECIFICATION FOR STRUCTURAL CONCRETE <br />IN BUILDINGS, ACI 301, AND THE BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, ACI 318-11. <br />2. ALL CONCRETE FOR THE FOOTINGS, SLABS ON GROUND, AND MISCELLANEOUS ITEMS SHALL HAVE A MINIMUM COMPRESSIVE <br />STRENGTH OF 2500 PSI AFTER 28 DAYS, UNLESS NOTED OTHERWISE ON THE DRAWINGS AND PROVISIONS OF R402.2. <br />3. ALL AGGREGATES USED IN CONCRETE SHALL CONFORM TO ASTM C3303. MAXIMUM AGGREGATE SIZE SHALL BE'/,'. <br />4, PROVIDE 61% AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER. <br />5. BRACE FOUNDATION WALLS, RETAINING WALLS, DURING BACKFILLING AND TAMPING OPERATIONS. LEAVE BRACING IN POSITION <br />UNTIL PERMANENT RESTRAINTS ARE INSTALLED. <br />6. ALL EXPOSED EDGES OF CONCRETE SHALL BE CHAMFERED/4. <br />I. ENGINEERED WOOD CONSTRUCTION GUIDE <br />F. AMERICAN WOOD PRESERVERS ASSOCIATION STANDARDS <br />2. ALL STRUCTURAL LUMBER SHALL BE SOUTHERN YELLOW PINE #2 (MIN.) MACHINE GRADED LUMBER, UNO. <br />Fb =1,100 PSI Fv =175 PSI E=1.400,000 PSI <br />STRUCTURAL LUMBER SHALL CONSIST OF, BUT NOT LIMITED TO; RAFTERS, VERTICAL STRONGBACKS, LEDGERS, BEAMS, <br />HEADERS, AND POSTS. <br />3. LUMBER FOR INTERIOR BEARING WALLS OR EXTERIOR WALLS SHALL BE SOUTHERN YELLOW PINE #2 (SYP #2) OR BETTER (UNLESS NOTED <br />OTHERWISE). <br />4. ALL LUMBER EXPOSED TO WEATHER, OR AGAINST SOIL, CONCRETE OR MASONRY MUST BE PRESSURE TREATED. <br />5. MINIMUM NAILING PER FBCR, 5TH EDITION (2014), SEE TYPICAL NAILING SCHEDULE ON PLANS. <br />6. ALL BOLTS SHALL HAVE MINIMUM 7 SQUARE STANDARD CUT WASHERS UNDER HEADS AND/OR NUTS WHERE IN CONTACT WITH WOOD. <br />7. NOTCHING OR CUTTING OF FRAMING MEMBERS SHALL CONFORM TO SECTION R602.2.3 & R802.14 OF THE FBCR 5TH EDITION (2014). <br />B. FOR ASPHALT SHINGLE ROOFS, SHEATHING SHALL BE STRUCTURAL GRADE 7116" OSB EXPOSURE-1 OR 112" CDX PLYWOOD SHEATHING. <br />PROVIDE PANEL -CUPS AT MID -SPAN FOR SPANS GREATER THAN 16' ON CENTER AND AT ALL UNBLOCKED EDGES OF PLYWOOD SHEATHING. <br />9. FOR CEMENTITIOUS TILE ROOFS, SHEATHING SHALL BE 5/8" CDX PLYWOOD. 5/8' CDX SHEATHING SHALL BE INSTALLED WITH THE <br />STRENGTH AXIS RUNNING PERPENDICULAR TO THE TRUSSES AND SHALL SPAN A MINIMUM OF TWO TRUSS BAYS. PROVIDE PANEL -CLIPS <br />AT MID -SPAN FOR SPANS GREATER THAN 16" ON CENTER AT ALL UNBLOCKED EDGES OF PLYWOOD SHEATHING. <br />10. FLOOR SHEATHING SHALL BE APA RATED ''/." SUBFLOOR T & G INTERIOR PLYWOOD, GLUED AND SCREWED. ADHESIVES CONFORMING <br />WITH PERFORMANCE SPECIFICATION AFG-01 SHALL ONLY BE USED. <br />11, WALL SHEATHING SHALL BE STRUCTURAL GRADE 7/16" OSB EXPOSURE-1 OR 1/2" CDX PLYWOOD SHEATHING. <br />7. PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS -ON -GROUND WHERE INDICATED ON 12. MINIMUM DIMENSION OF ANY PLYWOOD SHEET SHALL BE 24' AND THE MINIMUM AREA SHALL BE 8 FT . SQ. <br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALED WITH ADHESIVE TAPE, <br />13. PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND COLUMNS WITH b STRUCTURAL LUMBER SYP #2. <br />8. CONTRACTORiOWNER TO PROVIDE SOIL REPORT TO ARCHITECT PRIOR TO ANY CONSTRUCTION. <br />14. TRUSS MANUFACTURER SHALL PROVIDE COMPLETE CALCULATIONS SHOWING INTERNAL LAYOUT, MEMBER FORCES AND STRESS CONTROL <br />MASONRY POINTS AND SUBMIT TO THE BUILDING DEPARTMENT FOR APPROVAL AND TO THE STRUCTURAL ENGINEER FOR REVIEW. ALL CALCULATIONS <br />1. MASONRY CONSTRUCTION SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS OF SECTION 606 OR WITH SHALL BE SIGNED AND SEALED BY A PROFESSIONAL CIVIL OR STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE PROPOSED <br />PROVISIONS OF TMS 4021 ACI 5301 ASCE 5. CONSTRUCTION. <br />2. CONCRETE MASONRY UNITS SHALL BE GRADE "N" TYPE II OR EQUAL AND, IN ACCORDANCE WITH ASTM C90.1 ib, STANDARD <br />SPECIFICATIONS FOR HOLLOW LOAD -BEARING CONCRETE MASONRY UNITS, MINIMUM COMPRESSIVE STRENGTH OF F'm =1500 <br />PSI. <br />1 OPEN-END BLOCK MAY BE SUBSTITUTED FOR STANDARD TWO CELLED BLOCK. <br />4. MORTAR SHALL BE TYPE M OR S IN ACCORDANCE WITH ASTM C270-082, STANDARD SPECIFICATIONS FOR MORTAR FOR MASONRY. <br />5. MORTAR JOINTS FOR ALL BED AND HEAD JOINTS ARE TO BE 3181NCH THICK. THE BED JOINT OF THE STARTING COURSE MAY <br />VARY BUT IT SHALL NOT BE LESS THAN'/.INCH AND NOT MORE THAN %INCH, REFER TO FBCR 5TH EDITION (2014), SECTION R607.2.1 <br />FOR MORTAR JOINT THICKNESS TOLERANCES. <br />6. GROUT SHALL BE IN ACCORDANCE WITH ASTM C476, STANDARD SPECIFICATIONS FOR GROUT FOR MASONRY, OR 2500 PSI PEA <br />ROCK CONCRETE PER SPECIFICATIONS AND PROVISIONS OF SECTION R609.1.2.OF THE FBCR 5TH EDITION (2014). <br />7. FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL REINFORCING. <br />8. MASONRY WALLS SHALL BE LAID IN A RUNNING BOND PATTERN OR, IF A STACK BOND PATTERN IS TO BE USED 9 GA. LADDER TYPE <br />HORIZONTAL JOINT REINFORCEMENT IS TO BE INSTALLED IN THE BED JOINTS SPACED AT 16" ON CENTER (MAX). <br />REINFORCING STEEL <br />1. ALL CONCRETE AND MASONRY STEEL REINFORCEMENTS SHALL CONFORM TO THE MANUAL OF STANDARD PRACTICE FOR DETAILING <br />REINFORCED CONCRETE STRUCTURES, ACI 315; THE STANDARD SPECIFICATIONS FOR STRUCTURAL CONCRETE IN BUILDINGS, <br />ACI 301; AND THE BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, ACI 318-11. <br />2. REINFORCING BARS SHALL BE OF INTERMEDIATE GRADE CONFORMING TO ASTM A615, GRADE 40 (UNO). <br />3. WELDED WIRE FABRIC SHALL BE 6" X 6"- WiA X W1 A AND SUPPLIED IN FLAT SHEETS OR ROLLS CONFORMING TO ASTM A185. LAP <br />SIDES AND ENDS A MINIMUM OF 12". LOCATE WWF 7 FROM THE TOP OF THE SLAB, UNLESS OTHERWISE NOTED ON THE PLANS. <br />THIS REINFORCEMENT SHALL BE SUPPORTED PER SECTION R506.2.4 <br />4. ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, THICKENED SLAB, BEAM OR LINTEL <br />SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS <br />THROUGHOUT THE HEIGHT OF THE WALL, WITH LAP SPLICES OF AT LEAST 25'. <br />5. RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL INTO INTERSECTING WALLS AND <br />HOOK AT ENDS. STAGGER SPLICES AT LEAST 25" WHEREVER POSSIBLE. <br />6. CLEARANCE OF MAIN REINFORCING BARS FROM ADJACENT CONCRETE SURFACES SHALL BE: <br />A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3" <br />B. CONCRETE EXPOSED TO EARTH OR WEATHER: <br />I. #5, W31 OR D31 AND SMALLER 2" <br />C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND: <br />I. #11 AND SMALLER 'b' <br />D. BEAMS, COLUMNS: <br />I. PRIMARY REINFORCEMENT, TIES, STIRRUPS, SPIRALS 1'/:" <br />7. DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS WITHOUT THE <br />APPROVAL OF THE ARCHITECT. <br />TIMBER <br />1. ALL WOODS AND WOOD CONSTRUCTION SHALL COMPLY WITH SPECIFICATIONS AND CODES MODIFICATIONS AS SPECIFIED HEREIN: <br />A. AMERICAN INSTITUTE OF TIMBER CONSTRUCTION (STANDARDS MANUAL) <br />B. NATIONAL FOREST PRODUCTS ASSOCIATION: <br />I. NATIONAL DESIGN SPECIFICATIONS INDS) FOR WOOD CONSTRUCTION <br />C. SOUTHERN PINE INSPECTION BUREAU: <br />I. STANDARD GRADING RULES FOR SOUTHERN PINE LUMBER <br />D. TRUSS PLATE INSTITUTE: <br />I.NATIONAL DESIGN STANDARDS FOR LIGHT METAL PLATE CONNECTED WOOD TRUSSES (TPI-1-07) <br />15. TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF LOCATIONS WITH GUSSETS, <br />CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR INTERSECTIONS OF HIGHER OR LOWER ROOFS IN <br />ACCORDANCE WITH ANSI A58.1-1982. <br />i6. PREFABRICATED TRUSS TOP AND BOTTOM CHORD LOADS SHALL BE PER THE RECOMMENDED MINIMUM DESIGN LOADS IN APPENDIX B OF <br />THE ANSI/TPI 1-2007 NATIONAL DESIGN STANDARD FOR METAL PLATE CONNECTED WOOD TRUSS CONSTRUCTION. LIVE LOAD DEFLECTIONS <br />SHALL BE LIMITED TO U360. DEAD PLUS LIVE LOAD DEFLECTIONS SHALL BE LIMITED TO U240. <br />17. THE CONNECTIONS FOR ALL TIMBER EXPOSED TO EXTERIOR ELEMENTS OR TO PRESSURE TREATED LUMBER SHALL BE GALVANIZED OR <br />PAINTED WITH A CORROSION RESISTANT POLYMER PAINT. <br />18. ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "SIMPSON" STRONG -TIE BY SIMPSON CO., OR EQUAL. UNLESS <br />NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS WITH THE SIZE AND NUMBER OF BOLTS/NAILS AS RECOMMENDED BY THE <br />MANUFACTURER IN THE LATEST CATALOG. <br />19. DRAFTSTOPPING SHALL BE PROVIDED IN ACCORDANCE WITH SECTION R302.12. OF THE FBCR 5TH EDITION (2014). <br />PLUMBING <br />1. SANITARY LINES SHALL BE OF CAST IRON OR PVC (SCHEDULE 40) AS APPROVED BY THE BUILDING OFFICIAL. <br />2. WATER SUPPLY LINES SHALL BE CPVC OR UPONOR PEX "A' (CROSS -LINKED POLYETHYLENE) WITH F1960 FITTINGS, <br />3. CONDENSATION LINES SHALL BE MINIMUM'/." PVC (SCHEDULE 40), INSULATED WITH W AMAFLEX. <br />4. SHOWER HEADS SHALL HAVE A FLOW CONTROL DEVICE TO GIVE A MAXIMUM FLOW OF 3 GPM EACH. <br />5. ALL CLEANOUTS SHALL BE FLUSH WITH GRADE, <br />6. NO VENT STACKS SHALL PASS THROUGH ROOF CRICKETS, VALLEYS, OR RIDGES. <br />7. SIZE AND LOCATION OF CLEANOUTS SHALL CONFORM TO SECTION P3005.2 OF THE FBCR 5TH EDITION (2014). <br />8. FIXTURE SUPPLY SIZES SHALL CONFORM TO SECTION P2903 OF THE FBCR 5TH EDITION (2014). <br />9. THE PLUMBER IS TO DIVERT ALL VENTS TO REAR ELEVATION WHEN POSSIBLE. <br />10. DRILLING & NOTCHING OF WOOD FRAMED STRUCTURAL MEMBERS SHALL FOLLOW PROVISIONS OF SECTION P2603.2 OF THE FBCR 5TH <br />EDITION (2014). <br />EXTERIOR WALL COVERINGS <br />1. ALL EXTERIOR WALL COVERINGS AND SOFFITS SHALL BE CAPABLE OF RESISTING THE DESIGN PRESSURES SPECIFIED FOR THE WALLS FOR <br />COMPONENTS AND CLADDING LOADS IN ACCORDANCE WITH TABLE R301.2(2) AS MODIFIED BY TABLE R301.2(3), MANUFACTURED SOFFITS <br />SHALL BE TESTED AT 1.6 TIMES THE DESIGN PRESSURE <br />EXTERIOR FINISHES <br />1. WHEN PLASTERING WITH CEMENT, PLASTER SHALL NOT BE LESS THAN THREE COATS, %' THICK, OVER FRAMED WALLS APPLIED OVER <br />PAPER BACKED METAL LATH OR WIRE FABRIC LATH AND WITH TWO LAYERS OF VAPOR BARRIER, NOT LESS THAN 2 COATS, 1/2' THICK, <br />WHERE APPLIED OVER MASONRY OR CONCRETE. <br />2. STUCCO OR PORTLAND CEMENT PLASTER SHALL BE INSTALLED, PROPORTIONED AND MIXED IN ACCORDANCE WITH ASTM-C926-1la & <br />ASTM-C1063-12a. <br />3. LATH & ACCESORIES PER ASTM-C-1063-11A & R703.6.1 OF THE FBCR, 5TH EDITION (2014). ALL STUCCO APPLICATION DETAILS, INCLUDING BUT NOT <br />LIMITED TO'. <br />-- ALL STUCCO CONTROL JOINTS -- KICK -OUT DETAILS <br />-- 'L' FLASHING -- HORIZONTAL LATH AND PAPER DETAILS <br />-- PIPE PENETRATION DETAILS - VENT PENETRATION DETAILS <br />-- WEEP SCREED DETAILS -- CONDUIT PENETRATION DETAILS <br />-- CASING BEAD DETAILS - DRIP EDGE DETAILS <br />-- CANTILEVER DRIP EDGE DETAILS - CORNER BEAD DETAILS <br />-- WINDOW CASING DETAILS -• STUCCO TO SIDING TRANSITION DETAILS <br />-- WINDOW FLASHING DETAILS <br />4. SHALL BE INSTALLED PER ASTM-C1063 -11A AND R703.6.1 OF THE FBCR, 5TH EDITION (2014) <br />2-STORY GYPSUM BOARD <br />UNDER STAIR PROTECTION: <br />1. ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS, UNDER STAIR SURFACE AND ANY SOFFITS PROTECTED ON THE <br />ENCLOSED SIDE WITH 1/2' GYPSUM BOARD. FBCR R302.7. <br />CONTROL DATE: 02/08/17 <br />A R C H I T H C T S <br />6 <br />Desirn <br />Grou .a <br />141 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-7744078 <br />W W W.Mbdesigngroup.com <br />AA #: 0003325 <br />ti <br />a <br />0 <br />0 <br />o <br />� <br />DVBDIV. a X,OT <br />SILVERADO <br />LOT 1 <br />BLK 7 <br />PaoixcT#1 <br />04128.000-00171 <br />MODWLo <br />4EAB <br />"1672- ARIA" <br />GAItAGZ 91WWO: <br />RIGHT <br />PAGM <br />GENERAL <br />NOTES <br />150 MPH EXP. B <br />ARcHrri-77 <br />OF FLOMDA <br />Kc) <br />2 o1? <br />AR N 93 23 C tiA <br />/19/17 <br />/4"=l'-O" <br />8T8r 1� <br />