<br />GABLE -ENO �-'��
<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCE 7-10
<br />ZONE 1 = 8.97 PSF (19.97)
<br />ZONE 2 •17.98 PSF (27.98)
<br />ZONE 3 •33.53 PSF (43.53)
<br />"A'• 4'-0' END ZONE DISTANCE
<br />BASIC WIND SPEED: 150 MPH
<br />WIND EXPOSURE: "B"
<br />RISK CATAGORY: It
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT +- 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16'
<br />O.S.B. OR 12' COX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 518 COX EXT. PLYWOOD, WITH Sd RING
<br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED
<br />PANEL EDGES AND 8d RING SHANK GUN NAILS
<br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />8d GUN NAILS 0 4" O.C. EDGEWISE 214
<br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE
<br />END:
<br />ROOF/ WALU FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN. DIA.
<br />SHANK
<br />TENSILE STR.
<br />SHANK
<br />8d
<br />RING SHANK
<br />21/7'
<br />0.120"
<br />170,000
<br />RI G
<br />SCREW SHANK
<br />(16-20 RINGS
<br />PER INCH)
<br />8d
<br />SCREW SHANK
<br />21/T
<br />0.120"
<br />PNEUMATIC
<br />SCREW-7NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION (ISANTA) ESR-1539
<br />EXTERIOR SHEATHING
<br />USE 1/7COX OR 7/16" O.S.B. PLY NTH Sd RING
<br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN
<br />NAILS AT S" O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7/16
<br />' ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />V
<br />1w
<br />z8
<br />Lu
<br />Z
<br />QU
<br />NO
<br />z
<br />8d RING SHANK GUN NAILS (Q 4" O.C.
<br />TOP & BOTTOM EDGES
<br />J
<br />Z9
<br />Z
<br />U
<br />Z
<br />a
<br />N
<br />Z
<br />�1
<br />rm
<br />TOP CORD BLOCKING AT 4
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END,
<br />RAFTER OR TRUSS
<br />RET(1F SHEATHING
<br />,1
<br />.___-IML61,1 ril[ill
<br />k!
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />CStl RING SHANKGUN NAILS .
<br />S' O.C. IN FIELD `
<br />TYP. EXT. SHEATHING ATTACHMENT O 9067 9HEATHING (O.S.B.
<br />TO BE STRUCTURAL GRADE
<br />W RING SHANK GUN NAILS 0 12' O.C. IN
<br />FIELD or Sd x 2 10 SCREW SHANK
<br />PNEUMATIC SCREW -NAILS a 17, 0.7
<br />FIELD
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMUM AGGREGATE SIZE SWILL BE Y4.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION NTH JOB SPECIFICATIONS AND
<br />WOOD.
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />pROWDEB%AIR ENTRAINED CONCRETE EXPOSED TO EARTH ORWEA7HER
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />EXPOSED EDGES OF CONCRETE ARE TOBECHAMFEF¢O YC.
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, BIH EDITION
<br />ALL
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACT 318.14, BUILDING CODE REQUIREMENTS
<br />PROVIDES -MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS-0GROUND-GROIMDWHERE INDICATED ON
<br />VAPOR BARRILED METAPE.
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. Fb= 1100 PSI AND A MODULUS OF
<br />FOR STRUCTURAL CONCRETE, ACT 530-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF
<br />B INCHESANDSE NTH E
<br />ELASTICITY - 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7.10 AND AISC SPECIFICATIONS
<br />DRAWINGS. SEAMS UPPED
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: OISODIUM
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORM -WORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN,
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACT 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2017, 661 EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP #2.
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH'
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACT
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE
<br />SUPPORTED WITH 2' CHAIRS SPACED T-0- OC, EACH WAY.
<br />70 BE DESIGNED AND FABRICATED IN ACCORDANCE NTH THE 'NATIONAL DESIGN SPECIFICATIONS FOR
<br />THE NFPA. TRUSS DESIGNS SHALL SIGNED AND
<br />STRESS -GRADE LUMBER AND ITS FASTEENGINEER
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />REGISTERED O
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036'ANO BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A61S GRADE 60 DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN
<br />ACCORDANCE W THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACT STANDARDS AND
<br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />DESIGN LOADS:
<br />SPECIFICATIONS. CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL
<br />FABRICATION. HORIZONTAL AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND 'TPIIWTCA SCSI 1"
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 sf
<br />P
<br />SUBJECT TO ENGINEER'S REVIEW.
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />20 psf TOP CHORD -n-wounent
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36"
<br />WOOD TRUSSES.
<br />10 pef BTM CHORD
<br />#5 BAR - 30" #7 BAR - 47
<br />PROVIDE 36'. 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />FOR ADDITIONAL INFORMATION.
<br />LOCATIONS NTH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE NTH ANSI A58.1-1982.
<br />15 psf TOP CHORD 20 pet TOP CHORD
<br />(7 pdw/ASPHALT SHINGLES) (10 psfw/ No GYPCRETE)
<br />10 psf BTM CHORD 5 paf BTM CHORD
<br />DEAD LOAD TO RESIST WIND UPLIFT: I Opsf
<br />BALCONY LIVE LOAD 60 Psf
<br />STAIRS LIVE LOAD 40 psf
<br />WIND: DEAD LOAD SPEED -150 MPH 3- SECOND GUST
<br />(ASCE 7.10 (FBC R2017) EXPOSURE B, RISK CATEGORY II)
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC
<br />ALL SHOP DRAWNGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO
<br />THE ARCHITECT. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED.
<br />SHOP DRAWINGS IN THE FORM OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON-
<br />TRACT DOCUMENTS) ARE PROHIBITED WITHOUT THE EXPRESS WRITTEN PERMISSION FROM
<br />THE ENGINEER.
<br />IN ALL INSTANCES, THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS
<br />CHECKED, UNLESS OTHERWISE SPECIFIED IN WRITING BY THE ARCHITECT.
<br />FOUNDATION/ SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2.00D pd,
<br />FOOTING WERE
<br />AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY
<br />OF AT LEAST 95%OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN
<br />ACCORDANCE NTH ASTM D-1557. TREAT ALL SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER
<br />TO VERIFY SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS
<br />FAILING TO MEET THE GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND
<br />RETESTED AT THE CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN
<br />CERTIFICATION THAT THE MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION
<br />REQUIREMENTS HAVE BEEN MET SHALL BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS.
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5' STRUCTURAL TERRACE SUB.
<br />CONTRACTOR SHALL SUBMIT PROPOSED NIX DESIGNS, WITH HISTORICAL STRENGTH DATA
<br />FOR EACH SEPARATE MIX PRIOR TO CONCRETE PLACEMENT. CONCRETE SLUMP SWILL
<br />NOT EXCEED S' N- PRIOR TO THE ADDITION OF PLASTICIZER.
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C94 OR
<br />MEASURING, MIXING, TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED
<br />WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS ADDED
<br />TO THE MIX UNTIL IT IS DEPOSITED W ITS FINAL POSMON SHALL NOT EXCEED 90 MNUTES.
<br />IF FOR ANY REASON THERE IS DELAY IN SUCH THAT A BATCH IS HEW FOR LONGER THAN
<br />90 MNUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE RESPONSIENUTY OF
<br />THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON COMPLIANCE WITH THE
<br />ABOVE
<br />REQUIRED CONCRETE COVERAGE OVER REBAR BFWLL BE AS FOLLOWS:
<br />A P FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER
<br />I:lf2' FOR 05 AND SMAU.ER
<br />2' FOR IB AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3/4' FOR SUBS, WALLS AND JOISTS
<br />1-172" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />WALL.
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />MASONRY:
<br />PROVIDE ENGINEERED SHOP DRAW NGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM NTH ALL REQUIREMENTS OF THE
<br />PLAN SHOW NG COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />"SPECIFICATION MASONRY STRUCTURES" (ACT 530/ ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR
<br />LICENSED PROFESSIONAL ENGINEER.
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm - 1500 PSI. BLOCK SHALL BE PLACED USING
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />OF THE DELEGATED TRUSS ENGINEER. WND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7.10 COMPONENT
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />AND CLADDING WND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />ASTM C-076, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318"
<br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USP STRUCTURAL
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF W TO 10". USE ONLY MECHANICAL VIBRATION
<br />CONNECTORS" BY USP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS
<br />TO CONSOLIDATE GROUT,
<br />WITH THE SIZE AND NUMBER OF BOLTS/NAILS AS RECOMMENDED BY THE MANUFACTURER IN THE
<br />TYPE W" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />LATEST CATALOG.
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SWILL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />FILL CMU CELLS SOLID NTH GROUt AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />STRUCTURALSTEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BV THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36, Fy = 36 ksl FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B.
<br />Fy = 46 k41. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE B, TYPE E OR S, Fy = 35 W. TUBE AND PIPE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JSOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPLICAliON
<br />811E
<br />ttPE
<br />SPACING
<br />APPDCArroN
<br />SUS
<br />TYPE
<br />I SPACIFp
<br />IREMMI{e
<br />1#PT FURRING IO
<br />CASE MARCENED�L
<br />9•Q'C
<br />GARAGE DOOR-
<br />SEE DETAIL
<br />SEEDETNL
<br />6SS DETAIL
<br />SEE DETNL
<br />MPeONRY/WNC.
<br />NNLI II2'LONO.
<br />TOMASGNRYpDNC.
<br />BW. N.ExT.000Re
<br />CASE N4R0@IEDODL
<br />B'Ox:
<br />WINOOAIOOOIU FASTENED
<br />ONuOEDOOR BUDc
<br />9EE DETAIL
<br />BEE DETAIL
<br />sEE OETaI
<br />BEE DETAIL
<br />9EE Noree
<br />NaL11?LONo.
<br />STAGGERED
<br />1Nro AASONT',LONC.
<br />ro MASONRY/ttxdC.
<br />WINDONBIICI(
<br />usEHARDENmoaL
<br />e•oc
<br />LMNODwm«MFASTENED
<br />METa.IT- I
<br />CONTACT THIS ENGINEER FOR SPACING
<br />tr fT, 9EE NDTEe
<br />NVL11? LONG.
<br />sTAGGEREo
<br />1NroALneoNRrmFc.
<br />MavDNRrlcoNc
<br />ExT. evBND DooR
<br />1213118 'DA
<br />'TAP 1
<br />1B"OF
<br />1I?'EASED, C END.
<br />NON-BEARND WOOD
<br />ur= ExPANs1oNEQUIREMENTS
<br />2A OF <"EMBED. x"EeD
<br />DUCK 2r PT, SEE NOTES
<br />NO WARNER
<br />FA 1-
<br />DST., 11?EDGE DST.
<br />WALL TO GONG. BLAB
<br />Wl WASHER BOLT DST., 3-EDGE DST.
<br />h PT W1NOOVI SUCK 1•END DST., I t?
<br />8.138'PAF�211C YdC
<br />P T081EEL COL.. BEE w1 WASHER 9TA(iOERED EDDE Dst.
<br />NO Ee
<br />11. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI XZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR NWO NTH A OD DOOR FRAME. lx MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W TAPCONS OR PAF TO THE SUBSTRATE.
<br />BA41 N. RONALD REAGAN BLVD,
<br />LONGWOOD, FL 32750
<br />PH: 407-7745078
<br />FAX 407-774.4078
<br />www.abdesigngroup.com
<br />AA 0: 0003325
<br />yh
<br />O
<br />4
<br />C
<br />aUDDIV. Se r oT:
<br />SILVERADO
<br />LOT #5
<br />BLK #7
<br />PROJECTIV
<br />04128.002-05071
<br />HODELA
<br />4ENB
<br />"1751-NEUVILLE"
<br />GARAGE OWING:
<br />LEFT
<br />PAGE:
<br />DETAILS
<br />50 MPH EXP.
<br />19
<br />A.
<br />I'RINT
<br />DATE Oi/17/19
<br />SCALE: 1/4"=1'-0"
<br />s>�,, N 1