_kDOF WIND DESIGN NSSURES
<br />NET(GROSS) ASCE 740
<br />ZONE 1 •8.97 PSF (1927)
<br />ZONE 2 • 17.98 PSF (27.98)
<br />ZONE 3 •33.53 PSF (43.53)
<br />"A"• 4'-0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 150 MPH
<br />WIND EXPOSURE:"B"
<br />RISK CATAGORY: 11
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT * 0.18
<br />ROOF DMPHRAOM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 711T
<br />O.S.B. OR 1/2" COX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 5/8 COX
<br />EXT. PLYWOOD, WTH Sd RING
<br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED
<br />PANEL EDGES. AND 8d RING SHANK GUN NAILS
<br />AT 8" O.C. AT INTERMEDIATE SUPPORTS, SEE
<br />DETAIL
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />Sd GUN NAILS 0 4" O.C. EDGEWISE 20
<br />BLOCKING ALL PANEL JOINTS W IN 4' OF GABLE
<br />END.
<br />w F
<br />ROOF/ WALU FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN, DIA
<br />SHANK
<br />TENSILE STIR.
<br />SHANK
<br />8d
<br />RING SHANK
<br />212'
<br />0, 12W
<br />170,ODO
<br />RING
<br />SCREW SHANK
<br />(PER IONCHH)
<br />8d
<br />SCREW SHANK
<br />2 12'
<br />0.12U'
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION ([SANTA) ESR-1539
<br />EXTERIOR BNEATHRIO
<br />USE 112" COX OR 7/16" O.S.B. PLY WTH Sd RING
<br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP&
<br />BOTTOM PANEL AND Bd RING SHANK GUN
<br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7116" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUR SPECS.) SEE DETAIL,
<br />J
<br />Z
<br />D W
<br />O@
<br />� O
<br />m
<br />8d RING SHANK GUN NAILS 0 4" O.C.
<br />TOP & BOTTOM EDGES
<br />Y Z
<br />O
<br />J
<br />i
<br />Y
<br />C7
<br />Q2
<br />2 -
<br />N
<br />v
<br />ao
<br />TOP CORD BLOCKING AT 4'
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END.
<br />RAFTER OR TRUSS -__
<br />i---11
<br />mmm 11
<br />I111,111.1111,111.111.111'`,
<br />..
<br />ROOF SHEATHINGLAYOUT
<br />AENDWALL BRACING
<br />GABLE 94D PAAM140
<br />Bd RING SHANK GUN NAILS
<br />W' O.C. IN FIELD'
<br />8d RING SHANK GUN NAILS a 170.C. IN
<br />FIELD or Bd x 2 12' SCREW SHANK
<br />PNEUMATIC SCREW -NAILS 0170.C�I[J
<br />FIELD J\
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TOALL EXPOSED MEMBERS
<br />QENEM NOTIEs:
<br />ALL AGGREGATE USED IN CONCRETE SHALL ODWRM TO ASTM C3& MAXIMUM AGGREGATE SIZE SHALL BE34'.
<br />STRUCTURAL DRAWINGS SWILL BE USED IN COWUMCTION WTH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />S%AR ENTRAINED CONCRETEEYP(XSB)70 EIRRiRNEATIIER
<br />:
<br />Wow:PROVIDE
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAVANGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBCR2017, ft EDITION
<br />ALLE7010S®EDGE30F CONCRETE ARE TO BE CHAMFERED
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, SLOCKNG,
<br />ACI 316-14, BUILDING CODE REQUIREMENTS
<br />CRIPPLERS, BILLS, ETC., SWILL BE SOUTHERN PINE NO. 2 OR BETTER. Fb =11DO PSI ANDA MODULUS OF
<br />FOR STRUCTURAL CONCRETE, ACI 530.13/ASCE SA3 AISI SPECIFICATION FOR THE DESIGN OF
<br />PROVIDE 64AIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANEI#DERALL %AB50KR0U D WIBiE INDICATED ON
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS
<br />DRAWINGS. SEAMS LAPPED 6INCHES AND SEALED WITH ADHESIVE TAPE
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONLSTRUCTURAL USES
<br />ARE INTEND BE TYPICAL AND
<br />ALL DETAILS AND SECTIONS SHOW ON THE
<br />FORM -WORK
<br />SHALL BE TO TE
<br />CRROBORATEDTETTRAEDRAL(DOT). WOOD FOR STRUCTURAL USE SHALL VE7TREATED FORANY UM
<br />SIMILAR SITU HER
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK, SHORING, AND BRACING FOR All CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SWILL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT MERE A DIFFERENT DETAIL IS SHOWN
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WTHAU 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BLM14G TREATED LUMBER THAT
<br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY, ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLWKM FROM THESE PLANS:
<br />MINIMUM NAILING PER FBR 2017, 6N EDITION SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WTH 2, STRUCTURAL LUMBER
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORT] NG AND STABLE AFTER THE BUILDING
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP #2.
<br />IS COMPLETE. IT IS THE CONTRACTORS RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH:
<br />AT BEARING LOCATIONS WTHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE-0OWMS.
<br />WELDED W RE MESH, SHALL BE ASTM ALBS, GRADE 55 AND BE PLACED INACCORDANCE VNTHTE ACI
<br />WOW TRUSSES:
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. W RE MESH FOR SLABS SHALL BE
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />SUPPORTED WITH 2' CHAIRS SPACED T-0' OC, EACH WAY.
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SWILL BE SIGNEDAND
<br />REQUIREMENTS AND SLAB-0NGRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWNGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THCKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SWILL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A815 GRADE 60 DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN
<br />ACCORDANCE W THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND
<br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -UPPED GALVANIZED.
<br />DESIGN LOADS:
<br />SPECIFICATIONS. CONTRACTOR SHALL SUBMIT REBAR SHOP DRAW NGS FOR REVIEW PRIOR TO
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WTH TPI-14, "DESIGN NATIONAL
<br />FABRICATION. HORIZONTAL AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE
<br />STANDARDS FOR METAL-PLATE-CONNECTEDWOOD TRUSS CONSTRUCTION:, AND "TPWVrCA SCSI 1"
<br />SUBJECT TO ENGINEER'S REVIEW.
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METALfLATE-CONECTED
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 cf
<br />P
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #8 BAR - 36'
<br />WOOD TRUSSES.
<br />20 psf TOP CHORD+Tonconcum t #5 BAR - 30" #7 BAR - 42"
<br />10 pcf BTM CHORD ttonconcunmd PROVIDE 36' x 36' CORNER SARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />DEAD LOAD DEAD LOAD
<br />15 pat TOP CHORD 20 pcf TOP CHORD
<br />(7 pcf w/ ASPHALT SHNGLES) (10 Paf 114 No GYPRETE)
<br />10 pcf BTM CHORD 5 psf BTM CHORD
<br />DEAD LOAD TO RESIST W NO UPLIFT: 1 Opaf
<br />BALCONY LIVE LOAD 60 paf
<br />STAIRS LIVE LOAD 40 psf
<br />WIND: DEAD LOAD SPEED -IS MPH 3-SECOND GUST
<br />(ASCE 740 (FBC R2017) EXPOSURE B, RISK CATEGORY II)
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WTH THE DESIGNING INTENT
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO
<br />THE ARCHITECT. DRAWINGS SUBMITTED WTHOUT REVIEW WILL BE RETURNED UNCHECKED.
<br />SHOP DRAWNGS IN THE FORM OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON.
<br />TRACT DOCUMENTS)ARE PROHIBITED WITHOUT THE EXPRESS WRITTEN PERMISSION FROM
<br />THE ENGINEER.
<br />IN ALL INSTANCES, THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWNGS
<br />CHECKED, UNLESS OTHERWSE SPECIFIED IN WRITING BY THE ARCHTECT.
<br />FOUNDATIOW SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FORAN ALLOWABLE SOIL BEARING PRESSURE OF 2,ODO Paf,
<br />FOOTING EXCAVATIONS AND SLAB SUBGRADE SHALL BE COMPACTED TO A DRY DENSITY
<br />OF AT LEAST 95% OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN
<br />ACCORDANCE WTH ASTM D-1557. TREAT ALL SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER
<br />TO VERIFY SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS
<br />FAILING TO MEET THE GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RECOMPACTEDAND
<br />RETESTED AT THE CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN
<br />CERTIFICATION THAT THE MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION
<br />REQUIREMENTS HAVE BEEN MET SHALL BE MADE BY THE GEO-TECK ENGINEER.
<br />CONCRETE SHALL ACHIEVE MINIMUM 26 DAY COMPRESSIVE STRENGTHS AS FOLLOWS
<br />2,500 PSI REGULAR VrEIGHT FOR FOOTINGS, AND SLASON13RADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TEPACE SUS
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS WITH HISTORICAL STRENGTH DATA
<br />FOR EACH SEPARATE MIX PRIOR TO CONCRETE PLACEMENT. CONCRETE SLUMP SKALL
<br />NOT EXCEED S J-PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY NTH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C44 R
<br />MEASURING, MIXING, TRANSPORTING, ETC, CONCRETE TICKETS SHALL BE TIME -STAMPED
<br />PED
<br />WHEN CONCRETE IS BATCHED. THE MAXIMA TIME ALLOWED FROM WHEN MTER IS ADDED
<br />TO THE LOX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXC® 90 MMITES.
<br />IF FOR ANY REASON THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LOWER THAN
<br />90 MINUTE$ THE CONCRETE SHALL NDT BE PLACED. IT SHALL BE TIE RESPONSHBKffY OF
<br />THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON COMPLIANCE WTH THE
<br />ABOVE
<br />REWIRED CONCRETE COVERAGE OVER REBNRSHWLLSEASFOLLOWS
<br />A F FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH UFOLNDATOAM
<br />B FOR CONCRETE EXPOSED TO EARTH ROM YEATFER
<br />1-tn' FR #5 AND SMALLER 2. FOR #S AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />314' FOR 8L/8S. WALLS AND JOISTS
<br />I4/:' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES STIRRUPS
<br />TRUSS MANUFACTURER W LL PROVIDE CALCULATIONS INDCATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WTH GUSSETS, CRICKETS AND VALLEY LOCATIONS RED URIN O ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HGHER OR LOUVER ROOFS IN ACCORDANCE WTH ANSI A58.1-1982.
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />HURRICANE STRAPS SMALL BE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS.
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />WALL.
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWNGS FOR ALTERNATE CONNECTION DETAILS AT
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FORAPPROVAL
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGER SPUCES WHEREVER POSSIBLE.
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USEDAS A GUIDE FOR BEARING
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINIAL
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />WTHOUT THE APPROVAL OF THE ENGINEER
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />MASONRY:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ER
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WTH ALL REQUIREMENTS OF THE
<br />PLAN SHOW NG COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />"SPECIFICATION MASONRY STRUCTURES" (ACI 5301 ASCE 5RMS 402, BUILDING CODE REQUIREMENTS FOR
<br />LICENSED PROFESSIONAL ENGINEER
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDEDTO FACILITATE THEPUBLISHED
<br />BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />MANUFACTURED IN CONFORMANCE WITH ASTM CSC, GRADE fYn = 1500 PSI. BLOCK SHALL BE PLACED USING
<br />OF THE DELEGATED TRUSS ENGINEER, W NO UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT
<br />RUNNING BOND UNLESS OTHERW SE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />AND CLADDING W FOR
<br />LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE F
<br />PLACING CONCRETE FOR INANALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />ASTM '476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8"
<br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USP STRUCTURAL
<br />COURSE AGGREGATE, AND SHALL BE PLACED W A SLUMP OF S" TO 10. USE ONLY MECHANCAL VIBRATION
<br />CONNECTORS" BY LISP,OREQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS
<br />TO CONSOLIDATE GROUT
<br />WITH THE SIZE AND NUMBER OF BOLTS/NAILS AS RECOMMENDED BY THE MANUFACTURER IN THE
<br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THS PROJECT. MORTAR SWILL BE
<br />LATEST CATALOG.
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL SE 3/8" THCK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />FILL CMU CELLS SOLID WTH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR BX BAR NO. (48 BAR DIAMETERS)., U.N.O
<br />STRUCTURALSTEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WTH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION STRUCTURAL STEEL SHALL BEASTM
<br />A36, Fy = 36 k9i FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM A-600, GRADE B,
<br />Fy - 48 kcl. STRUCTURAL PIPE SHALL BE ASTM53, GRADE B, TYPE E OR S, Fy - 35 ksi. TUBE AND PIPE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURNOFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR B CK FASTENERS
<br />FASTENER
<br />APPLIGTpI
<br />&¢
<br />ttPE
<br />SPAdNG
<br />REMARxB
<br />HFLICAMIN
<br />big
<br />ttPE
<br />SPACINGI
<br />REMARI®
<br />-PTRIRRINGTO
<br />CASENAROENEDCOIL
<br />B CA:
<br />GARAOEDOOR-
<br />SEE DETAIL
<br />SEE GETAE
<br />SEE OETNL
<br />SEE DETAI
<br />MABONRYICONC.
<br />1ILONG.
<br />TO Mg80NRYroONC.
<br />EIIT. DOORS
<br />CASENUroB1EDCOL
<br />YOA:
<br />WWDOWIOOORI FABfENED
<br />GPAAOE DOIXi BUG(
<br />SEE DETNL
<br />BEE.E-
<br />SEE DETNL
<br />1. PT, SEENOTEB
<br />NNL1f?LONG.
<br />a TA-M.
<br />INTOMASONtYICONC.
<br />TO MABONtYIWI.C.
<br />SEE-
<br />wWoowax:x
<br />cABE NAROENEo coIL
<br />e ac
<br />wWoowuoom FABre.IEo
<br />METALS -To
<br />CONTACT THIS ENGINEER
<br />FOR SPACING
<br />I. PT, 9EI-,
<br />_111ILONG.
<br />BT ENEO
<br />IMOMABDNRYIC w
<br />MASg1RY/CONC
<br />REQUIREMENTS
<br />EM. 61N0JG DOOR
<br />TAPCOM
<br />QC
<br />tt/2'EMB®.B'EMJ.
<br />NONAEARING WOOD
<br />I. -SON21- 4"EMBED P@ID
<br />BUcxh PT. SEENOTES
<br />N43118_
<br />OWASIER
<br />I TAB_
<br />1B
<br />OIST.,1 IIEDGEOIST
<br />WKLTOCONC.BVB
<br />W/WASIHi OIBT., "EOG-
<br />2BPfWW00WBUCK O1 G0'PAFx21.9' 0'OC 1"END. DIET.III
<br />PT TO STEEL WL..9EE w,I,��� BTAGGEREO EDGE CIBF
<br />NOTED
<br />HIM
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPUCATONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND /OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE RAND FRAMED
<br />4. PAF SHALL BE HILT[ XZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />8. W NDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NALED AND
<br />2x MEMBERS ARE SECURED W/ TAPGONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL 32750
<br />PH: 407-774-6078
<br />FAX: 407-7744078
<br />wwwAbdeslgngroup.com
<br />AA M: 0003325
<br />amm
<br />s11m irv. Ss Loll
<br />SILVERADO
<br />LOT #55
<br />BLK. #6
<br />PIlOJlICT
<br />42. 0 - 506
<br />4EHB
<br />"2605- HAYDEN"
<br />GARAGN SWIN 3:
<br />RIGHT
<br />PMAdL':
<br />DETAILS
<br />150 MPH EXP. B
<br />
|