Laserfiche WebLink
GAaLE-Ero ��` <br />x A <br />HF ROOF <br />ROOF WIND DIGN PRESSURES <br />ET (GROSS) ASCE 7-10 <br />ZONE 1 = 8.97 PSF (19.97) <br />ZONE 2 =17.98 PSF (27.98) <br />ZONE 3 = 33.53 PSF (43.53) <br />"A"=4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE: "B" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT -- 0.18 <br />ROOF DUWN4AGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16- <br />O.S.B. OR 12" CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 518 CDX EXT. PLYWOOD, WTH Bd RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE <br />8d GUN NAIWI LS @ 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL PANEL JOINTS W IN 4' OF GABLE <br />END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA <br />SHANK <br />TENSILESTR. <br />SHANK <br />8d <br />RING SWANK <br />2 12' <br />0.120" <br />170,000 <br />RING <br />(16-20 RINGS <br />SCREW SHANK <br />PER INCH) <br />8d <br />SCREW SHANK <br />2 12' <br />0.1201 <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (]SANTA)ESR-1539 <br />EXTERIOR SHEATHING <br />USE 1/2" CDX OR 7/16" O.S.B. PLY WITH Sd RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND Bd RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT S. <br />O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />8d RING SHANK GUN NAILS @ 4"O.C. <br />.. TOP & BOTTOM EDGES <br />z9 <br />z <br />Q U <br />N O . <br />O <br />z <br />U) <br />2 <br />7 . <br />: <br />(0 <br />Y <br />rn <br />. <br />2 <br />m- <br />0 <br />ZN <br />W <br />Z s <br />� W <br />Z <br />jU <br />fN 0 <br />O < <br />Y N <br />Q W <br />w � <br />It <br />W L)W <br />U r U <br />of O <br />aLu <br />m W <br />IL <br />TOP CORD BLOCKINGAT V <br />O.C. MAX. IN FIRST FRAMING <br />SPACES AT EACH END. <br />RAFTEROR�USS <br />NO <br />.Mr.02 <br />1, <br />��m� ` \ll <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />Bd RING SHANK GUN NAILS <br />@ 6" O.C. IN FIELD'` <br />81 RING SWANK GUN NAILS @ IT O.C. IN <br />FIELD or 8d x 2 12' SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ IT O(,�IN <br />FIELD J\ <br />FYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL ODWORM TO ASTM C33. MAXIMUM AGGREGATE SIZE SHALL BE 3M. <br />STRUCTURAL DRAWINGS SWILL BE USED IN CONJUNCTION WTH JOB SPECIFICATIONS AND <br />PROVIDE 6%AIR ENTRAINED CONCREfEDOOSEDTO EARTH ORNEATHBR <br />WOm� <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />NONBEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWNGS. APPLICABLE BUILDING CODE STANDARDS: FBCR 2017, 6th EDITION <br />ALLEXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 314'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC,, SHALL BE SOUTHERN PINE NO.2 OR BETTER Fb = 1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, ACI 530-131ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE IINDERALL SLABSONC4 0M V#ERE INDICATED ON <br />ELASTICITY = 1,400.GOO PSI, ALL WOOD IN CONTACT NTH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALED WITH ADHESIVE TAPE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />SHALL BE RATEDTO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIU M <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDEDTO BE TYPICALAND <br />FORMWORK <br />CORROBORATE TETRAHEDRAL (DOT). MOD FOR STRUCTURAL USE THAT SWILL BE TREATED FORANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORMWORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SWILL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. WAILS, SPIKE, BOLTS USED <br />EXCEPT MERE A DIFFERENT DETAIL IS SHOWN <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WTH AG 347, <br />WI DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORWWDRK. <br />CONTAINS MORE THAN Y.' OF HEARTWOOD <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD DO NOT SCALE THE <br />DRAWNGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />anconcurreM <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, 61h EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHTECT PRIOR TO PROCEEDING NTH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAYBE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTERTHE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDW WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE: ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE-0OW4S. <br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WTH THE ACI <br />WOW TTW.�S: <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC, EACHWAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE NTH THE WATIONAL DESIGN SPECIFICATIONS FOR <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />LUMBER AND ITS FASTENINGS' THE NFPA. TRUSS DESIGNS SHALL SIGNED AND <br />SEALED <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWNGS. <br />BY <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND <br />REBAR SHALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 601N MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DEEM LOADS; <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP D RANNGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL-PLATECONNECTED-WOOD TRUSS CONSTRUCTION:, AND "TPIAVTCA BCSI 1" <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />ROOF' LIVE LOAD FLOORLIVE LOAD 40 psf <br />REVIEW <br />WOOD TRUSSES. <br />20 psf TOP CHORD nonconcunerd <br />P <br />10 sf BTM CHORD <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />IS 'n <br />R NREINFORCINGBAR CONTINUOUSLY LAPPE AT SPLICES AND AROUND CORNERS DOWEL <br />#5 BAR - 30" #7 BAR - 42" <br />PROVIDE 36' x 36'CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />TRUSS MANUFACTURER W LL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEADLOAD <br />DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WTHANSI A58.1-1982. <br />15 psf TOP CHORD <br />20 psf TOP CHORD <br />(7 paf w/ ASPHALT SHINGLES) <br />(10 PST w/ No GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 psf BTM CHORD <br />5 PST BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WND UPLIFT: IOW <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 Psf <br />WALL. <br />TRUSSESIGIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />ROOF& FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USEDAS A GUIDE FOR BEARING <br />WIND DEAD LOAD SPEED =188 MPH 3- SECOND GUST <br />(ASCE 7-10 (FBC R2017) EXPOSURE B, RISK CATEGORY o) <br />U S D <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LIVE LOADS: UNINHABITABLE ATTIC WTHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WTH LIMITED <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 3OpSf, BALCONIES (EXTERIOR) <br />00 NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFlEDTO THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WTHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM' 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40psf <br />MMONW. <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WTH ALL REQUIREMENTS OFTHE <br />LICENSED PROFESSIONAL ENGINEER <br />SHOP DRAWING REVIEW; <br />"SPECIFICATION MASONRY STRUCTURES" (ACI 5301 ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACIUTATE THE <br />SHOP DRAWNGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIESL AS <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER <br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />OF THE DELEGATED TRUSS ENGINEER. W ND UPLIFT VALUES HAVE SEEN BASED ONASCE 7,10 COMPONENT <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHOTECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-80, GRADE fm = 1500 PSI. BLOCK SHALL BE PLACED USING <br />AND CLADDING W ND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWNGS SUBMITTED WTHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWSE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS 70 TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CONTRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAVS, UNLLESS <br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "LISP STRUCTURAL <br />DOCUMENTS WLL GOVERN OVER THE SHOP DRAWNGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPEOFICHLLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />CONNECTORS" BY USP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED N A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION <br />WITH THE SIZE AND NUMBER OF BOLTS/NAILS AS RECOMMENDED BY THE MANUFACTURER IN THE <br />TO CONSOLIDATE GROUT. <br />LATEST CATALOG. <br />FOUNDATION SITE PREPARATION' <br />TYPE 'M" OR'S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 pSf, FOOTING <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />SHALL BE 318' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WTH ASTM D-1557. TREATALL <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANDIOR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTEDAT TIME <br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TBIRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIORTO <br />CONCRETE PLACEMENT CONCRETE SLUMP SHALL NOT D(CEED 5' 4-PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COWLY WTH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C-94 OR MEASRIRING, MANG, TRANSPORTING, ETC <br />CONCRETE TICKEFS UHALL B=TIMES7AMPED WHEN CONCRETE M BATCHED. THE MAY MUM TIME ALLOWED FROM WHEN WATER IS <br />ADDED TO THE MX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES IF FOR ANY REASON THERE ISA <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE RACED. IT SHALL BETHE <br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE WITH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLYSTOSED TO EARFH ¢OWN DATKI" <br />a FOR CONCRETE EXPOSED TO FNRHAHOIOR WEATH ER <br />1-12 FOR AND SMALLER <br />Y FOR G AND LARGER <br />C FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4-FOR SLABS, WALLS AND JOISTS <br />1AW FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TES STIRRUPS <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.RO <br />STRUCTURAL STEEL; <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WTH THE <br />SPECIFlCATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILD NGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36, Fy = 36 ksi FOR ANGLES, PLATES, AND V"HAPES. STRUCTURAL TUBI NG SHALL BE ASTM A500, GRADE S, <br />Fy = 46 kSi. STRUCTURAL PIPE SHALL BE ASTM63, GRADE B, TYPE E OR S, Py = 35 W. TUBE AND PIPE <br />COLUMNS SHALL 8E CONCRETEFILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURNOFF-THE-N Ulr METHOD, <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JSOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />APPDGTICN <br />61]F <br />SMPNG <br />REMAiM.9 <br />FPPt1UTON <br />SIB <br />ttPE <br />SRWaNG <br />REMALC4 <br />tIQ PTft1RRW0 TO <br />M/30HRY/CgiC <br />GSEINfAEN®COIL <br />NAt,t?LCPL. <br />B OF <br />GAUGEDOOR 91at <br />M49JKtYlOONC <br />SEE DETAL <br />SEE DETAL <br />SEE DETAL <br />SEE GETNL <br />SGD EXT. DCOR9 <br />CASE MNiOB1ED COIL <br />POC <br />WINGDNbPDCRI-ENED <br />--E--SUa( <br />SEE DETAL <br />SEE DETNL <br />SEE DETAL <br />SEE DETAL <br />PTTL,SEENOTEB <br />S_.. <br />INTONasONRY/ANC. <br />A <br />wwoow000w Pnsrea® <br />CONTACT THIS ENGINEER FOR SPACING <br />+rw®NGO. <br />sTn R D <br />NroNse�lmrKaNc <br />"�" %m_ <br />REQUIREMENTS <br />LICK 3z �� E. <br />RNo\W9� <br />-PSI <br />,PAC <br />;7 ®GE0�16T. <br />wn9WER zTbC <br />wwmwa,� �•„u z, Bad sTs, <br />PTT 01w,wAsie+� oce <br />NOTES <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILT] X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. W NDOW AND DOOR BUCKS SHALL BE AS WIDE OR W DER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR NTH A WOOD DOOR FRAME. 1. MEMBERS ARE NAILED AND <br />N MEMBERS ARE SECURED W/TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32751 <br />PH: 407-7746078 <br />FAX:407-774-4078 <br />www.abdes4ftroup.com <br />AA #: 0003325 J <br />W <br />N <br />Z <br />> <br />0 <br />ZZ <br />O <br />1 <br />• <br />O <br />� <br />A <br />J <br />W <br />h <br />M1 <br />aas <br />19PJMT# <br />V do MAT. <br />ILVERADO <br />LOT #10 <br />BLK #7 <br />04128.002-10072 <br />MODZU- <br />4EAB <br />"1672- ARIA" <br />GARAGM aV►ING: <br />LEFT <br />PAGM: <br />DETAILS <br />50 MPH EXP. 51 <br />S; . CANTNIEi.L <br />NG =* i <br />rD 07/10/19 <br />91CAXX: 1//4"=1'-0" <br />l <br />