GABLE -RAID <br />ROOF WIND DESIGN PRESSURES <br />NET(GROSS) ASIDE 7-10 <br />ZONE 1 e 8.97 PSF (19.97) <br />ZONE 2 = 17.98 PSF (27,98) <br />ZONE 3 = 33.53 PSF (43.53) <br />W. 4'-O" END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE: "B" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT +- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7116" <br />O.S.B. OR 1/2' CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 618 COX EXT. PLYWOOD, WITH SO RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND SO RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE ENO FRAME USE <br />Sol GUN NAILS 0 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE <br />END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA. <br />SHANK <br />TENSILE STR, <br />SWANK <br />8d <br />RING SHANK, <br />21/Z' <br />0.120' <br />170,000 <br />ING <br />SNGS <br />CREW SHANK <br />(PER 2NCIH) <br />8d <br />SCREW SHANK <br />2 1/2" <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (]SANTA) ESR-1639 <br />EXTERIOR SHEATHING <br />USE 1/Z CDX OR 7/16" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND 80 RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUP SPECS.) SEE DETAIL. <br />Z W <br />Z 8 <br />uJ <br />Z <br />�o <br />2 <br />8d RING SHANK GUN NAILS 0 4" O.C. <br />., TOP & BOTTOM EDGES .. <br />Z <br />f U <br />. <br />9 to <br />� <br />Y <br />Z <br />0 <br />19 <br />Z2 <br />w <br />Z <br />f7 W <br />Y <br />10 <br />mO <br />Z <br />w <br />L•s <br />sJ <br />Y 8 W N <br />Q <br />_CC 8 <br />(((N��� W <br />Wcj <br />Tyi < o <br />W m <br />R <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />RmAFT�ER OR TRUSS <br />---_.' <br />.—__ EN <br />11 <br />ONE 1`' <br />„ <br />__, <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />C8d RING SHANK GUN NAILS <br />0 6' O.C. IN FIELD \ <br />8d RING SHANK GUN NAILS a 12' O.C. N <br />FIELD or 8d x 2 10 SCREW SHANK <br />PNEUMATIC SCREW -NAILS 0 12- 0.8.)N <br />FIELD J\ <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC33. MAXIMUMAGGREGATE SIZE SKILL BE3W.. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WTH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVDE B%AIR ENTRAINED CONCRETE EXPOSED TO EARTH ORWEATFBt <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAW NGS. APPLICABLE BUILD N C STANDARDS: f 2017 <br />O CODE ST NDARDS. BGR , Bth EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3/C. <br />ILEDGERS, <br />ALL WOOD FOR BEAMS, BEAR NG WALLS, SOLE PLATES, TOP PLATES, BRACING. BLOCKING, <br />ACI 316-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. FD = 1100 PSI AND MODULUS OF <br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 5.13 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE 84AL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SUB6ON-ORWID WHERE IIDICATm ON <br />ELASTICITY :ILLS, <br />PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLO-FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />DRAWINGS SEAMS UPPED B INCHES AND SEALED WITH ADHESIVE TAPE. <br />PRESSURE TREATED, PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />SHALL BE TO RETENTION LEVELS OF 0,25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORMWORK: <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORMWORK,SHORING, MI SRING, D BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WTH ACI 347, <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORMWORK <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD, DO NOT SCALE THE <br />DRAW NGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, eth EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK, <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WTH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAS-ON-GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS, <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: UVE LOAD FLOOR: LIVE LOAD 40 Pet <br />20 pef TOP CHORD -non—ounent <br />10 pef BTM CHORD non<onwrtmn <br />DEADLOAD DEAD LOAD <br />15 pcf TOP CHORD 20 psf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) (10 PO W/ No GYPCRETE) <br />10 pef BTM CHORD 5 pef BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opaf <br />BALCONY LIVE LOAD 60 pW <br />STAIRS LIVE LOAD 40 pet <br />W ND: DEAD LOAD SPEED =15D MPH 3- SECOND GUST <br />(ASCE 7-10 (FBC R2017) EXPOSURE 8, RISK CATEGORY IH <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO <br />THE ARCHITECT. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. <br />SHOP DRAWINGS IN THE FORM OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAW NGS (COW <br />TRACT DOCUMENTS) ARE PROHIBITED WITHOUT THE EXPRESS WRITTEN PERMISSION FROM <br />THE ENGINEER. <br />IN ALL INSTANCES, THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAW NGS <br />CHECKED, UNLESS OTHERWISE SPECIFIED IN WRITING BY THE ARCHITECT, <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf. <br />FOOTING EXCAVATIONS AND SLAB SUB GRADE SHALL BE COMPACTED TO A DRY DENSITY <br />OF AT LEAST 95%OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN <br />ACCORDANCE WTH ASTM D-1557. TREAT ALL SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER <br />TO VERIFY SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS, LOCATIONS <br />FAILING TO MEET THE GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND <br />RETESTED AT THE CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN <br />CERTIFICATION THAT THE MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION <br />REQUIREMENTS HAVE BEEN MET SHALL BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SUB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB <br />CONTRACTOR SHALL SUBMT PROPOSED PAX DESIGNS, WITH HISTORICAL STRENGTH DATA <br />FOR EACH SEPARATE MIX PRIOR TO CONCRETE PLACEMENT. CONCRETE SLUMP SHALL <br />NOT EXCEED 6 N-PRIOR TO THE ADDITION OF PLASTICIZER. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF AO 301 AND ASTMC44 OR <br />MEASURING, MIXING, TRANSPORTING,ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED <br />WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS ADDED <br />TO THE ALLY UNRL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES. <br />IF FOR ANY REASON THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN <br />90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE RESPONSIBILITY OF <br />THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON COMPLIANCE WITH THE <br />ABOVE. <br />REOMRED CONCRETE COVERAGE OVER REBAR SMALL BE AS FOLLOWS: <br />A 3- FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />8, FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER <br />WIT FOR 06 AND SMALLER <br />7 FOR AS AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3W FOR SLABS, WALLS AND JOISTS <br />1-VY FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES STIRRUPS <br />WELDED WIRE MESH. <br />WELDED W RE MESH, SHALL BE ASTM Al85, GRADE 65 AND BE PLACED IN ACCORDANCE WTH THE ACI <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES, WRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2' CHAIRS SPACED T-0" OC, EACH WAY. <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM A615 GRADE 60 DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN <br />ACCORDANCE W THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND <br />SPECIFICATIONS. CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO <br />FABRICATION, HORIZONTAL AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE <br />SUBJECT TO ENGINEER'S REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #8 BAR - 38" <br />#5 BAR - 30' #7 BAR - 42" <br />PROVIDE 38' x 3W CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WTH THE "NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS, <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A448, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14,'DESIGN NATIONAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "TPIN TCA SCSI 1" <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WTH ANSI ASSA4982. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />WALL. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />MASONRY: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />PLAN SHOW NG COMPONENT LAYOUT, SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />"SPECIFICATION MASONRY STRUCTURES" (ACI 530/ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />LICENSED PROFESSIONAL ENGINEER. <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE, <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />PROVIDED BY THE TRUSS ENGINEER. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE Tm= 1500 PSI, BLOCK SHALL BE PLACED USING <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE 8EAMS BEFORE <br />OF THE DELEGATED TRUSS ENGINEER. WHO UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />AND CLADDING WHO LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />SPECIFICALLY NOTED OTHERWSE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318" <br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USP STRUCTURAL <br />COURSE AGGREGATE, AND SHALL BE PLACED W/A SLUMP OF 8" TO 1Or. USE ONLY MECHANICAL VIBRATION <br />CONNECTORS" BY USP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS <br />TO CONSOLIDATE GROUT. <br />WITH THE SIZE AND NUMBER OF BOLTSINAILS AS RECOMMENDED BY THE MANUFACTURER IN THE <br />TYPE "M' OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />LATEST CATALOG. <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED, REMOVE MORTAR M IONS THAT EXTEND INTO <br />PROTRUSIONS US <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL RESAR S X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36, Fy = 36 kei FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B, <br />Fy = 46 W. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE B, TYPE E OR S, Fy = 35 kei. TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BEASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL, J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPDGTKIN <br />9ZE <br />TYPE <br />SPACBG <br />REMAPo6 <br />­- <br />1—FOR WTO <br />G9EHARDENWCOIL <br />86G <br />GARAGE DOOR BUCK <br />BEE DETML <br />SEE DETAIL <br />SEf DETML <br />BEE DETML <br />MASONRY/LONG. <br />NAIL 11Y['LONO. <br />OMASONRYgONC. <br />SOD, AL EKT. DOORS <br />GSE FNROENEDCgL <br />8'O'C <br />WINOOWr000RIfASTENW <br />GARAGE DOOR BACK <br />6EE DETAIL <br />9EE DETAIL <br />9EE DETML <br />BEE DETAIL <br />tx Pf, BEE NOTES <br />NAIL 11R'LONO. <br />S_.ERW <br />INTO MPSONRYiCorvc. <br />TOM/SONRYINNC. <br />vANDowBuaL <br />CASE MNHD@1WCgl <br />voo <br />vnNwMeroow FAsrErffD <br />METALB—To <br />CONTACT THIS ENGINEER FOR SPACING <br />. Pr. sEE Nore9 <br />NNL1 VS LONG. <br />eTAooERW <br />INro MAeoNRYAxNc. <br />MAsoNRrlcoNc. <br />REQUIREMENTS <br />EM.BwN000OR <br />(1)118'gA <br />"TAPOOM <br />18'� <br />11I1"EMBED. B'EIU. <br />NON-BEAPoNO WOOD <br />TIC° ExPrT- <'EMSED<"ENO <br />ie QC <br />BDG(91 PT, BEE NOTES <br />NO VIA3lIER <br />FA9TNFR <br />gST.,11IZ'EDGEgST. <br />—To— .9lAB <br />WI WABlIFR qST., 9"EDGE DIET. <br />Bx PT WINOOV/BUCN p.138'PAFx31A' a"OC 4END. O'Si.,I1R'• <br />PT T09TEELCtt., SEE wl WA8t1ER 9TAGOEF£D EDDE qST. <br />ND ee <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, W NDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5, FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NGA OR THE SPACING DETAILED ABOVE <br />8, W NDOW AND DOOR BUCKS SHALL BE AS WIDE OR WDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SW NG DOOR WTH A WOOD DOOR FRAME. lx MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W TAPCONB OR PAF TO THE SUBSTRATE. <br />1 <br />1441 N. RONALD REAGAN BLVD <br />LONGWOOD, FL 32750 <br />PH: 407-774,8078 <br />FAX- 407-774-4078 <br />www.Bbde6lgngroup.00m <br />AA N: 0003328 <br />qS <br />U <br />9: <br />a <br />SWODM k LOT <br />SILVERADO <br />LOT #56 <br />BLK #6 <br />PROJECT# <br />04128.002-56061 <br />MODEL: n <br />4ENB <br />t <br />1751- NEUVILLE <br />GARAGE SWING: <br />LEFT <br />PAGE: <br />DETAILS <br />50 MPH EXP. <br />A. <br />L AR NO 93M J <br />DATE:R 01/17/19 <br />SCALE: 1/4"=1'-0" <br />°HICs N1 <br />