Laserfiche WebLink
GABLE -END <br />ROOF WIND DESIGN PRESSURES <br />NET(GROSS) ASCE -10 <br />ZONE 1 •8.97 PSF (19.97) <br />ZONE 2 - 17.98 PSF (27.98) <br />ZONE 3 -33.53 PSF (43.53) <br />"A"• 4'-O" END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE: "B" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT+ 0.18 <br />ROOF DIAPHRAGM <br />FOR AS SHINGLE ROOF, USE MIN 7/16' <br />O.S.B. OR 1/2" CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 518 CDX EXT. PLYWOOD, WTH Bd RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHAWGUN NAILS <br />AT 6" O.C, AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE <br />8d GUN NAILS (9 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL PANEL JOINTS W/ IN W OF GABLE <br />END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. CIA <br />SHANK <br />TENSILE STR. <br />SHANK <br />8d <br />RING SHANK <br />2117' <br />0.120' <br />170,000 <br />RING <br />SCREW SHANK <br />(16-20 RINGS <br />PER INCH) <br />8d <br />SCREW SHANK <br />212" <br />0.120' <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTERIOR SHEATHING <br />USE 112" CDX OR 7116" O.S.B. PLY WITH Sd RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND Bd RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Bd RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUR SPECS.) SEE DETAIL <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />TOP & BOTTOM EDGES <br />s <br />9r-,\ <br />J W . <br />Y Z <br />U <br />J <br />C) O <br />z <br />a y <br />IS <br />Jz <br />C7 n <br />C W <br />\.J <br />z <br />N U <br />A. <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />RAFTER OR TR^SS <br />Emmm��� 1� <br />-___-' '1 <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAmm <br />8d RING SHANK GUN NAILS <br />8" O.C. IN FIELD'\ <br />8d RING SHANK GUN NAILS (912' O.C. IN <br />FIELD or Bd x 2 12' SCREW SHANK <br />PNEUMATIC SCREW -NAILS 0 12' O. WLJ <br />FIELD J\ <br />TYP. 3/4" T&G SUS -FLOOR DECKING GLUED TOALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOVrN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC4R 2017, 6th EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDEDTO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ONTHE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAW NGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIEZOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REOUREMENTS AND SLAB-CN�GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMUM AGGREGATE S1ZE SHALL BE Mr. <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAmm <br />8d RING SHANK GUN NAILS <br />8" O.C. IN FIELD'\ <br />8d RING SHANK GUN NAILS (912' O.C. IN <br />FIELD or Bd x 2 12' SCREW SHANK <br />PNEUMATIC SCREW -NAILS 0 12' O. WLJ <br />FIELD J\ <br />TYP. 3/4" T&G SUS -FLOOR DECKING GLUED TOALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOVrN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC4R 2017, 6th EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDEDTO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ONTHE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAW NGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIEZOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REOUREMENTS AND SLAB-CN�GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMUM AGGREGATE S1ZE SHALL BE Mr. <br />PROVIDE 8%AIR ENTRAINED CONCRETE EIPOSEOTO EARTH OR WEATHER <br />WOOD: <br />NORBEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ALL EPOS® EDGES OF CONCRETE ARE TO BE CHAMFER® 31r.. <br />ALL WOOD FOR BEAMS, 8EARI NG WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS,ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER Fb= 1100 PSI AND A MODULUS OF <br />PROVIDE B-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL 3UBSONGRDUDWERE INDICATED ON <br />ELASTICITY - 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />DRAWINGS. SEAMS LAPPED B INCHES AND SEALED WITH ADHESIVE TAPE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />SHALL BE RATEDTO RETENTION LEVELS OF 0.25 POP OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />FORMWORK <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />FORM -WORK, SHORING, AND 8RACING FOR ALL CONCRETE BEAMS, SLABS, COLL#MNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN %* OF HEARTWOOD. <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, 6th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WTH 2z STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUTARE BY OTHERS. <br />SYP #2. <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WTHOUT WOODEN TOP PLATES. <br />WELDED W RE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WTH THE ACI <br />WOOD TRUSSES: <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2' CHWIRS SPACED 3'A- OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA, SEE NOTED FOR SHOP DRAWNGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR REINFORCING STEEL: CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED. AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. REBAR SHALL BE ASTM A615 GRADE 60 DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -UPPED GALVANIZED, <br />ACCORDANCE W THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND <br />DESION LOADS: SPECIFICATIONS, CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />FABRICATION. HORIZONTAL AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE STANDARDS FOR METAL -PLATE -CONNECTED WOOD TRUSS CONSTRUCTION:, AND 'TPINJTCA BCSI V <br />SU&IECT TO ENGINEERS REVIEW. COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36' <br />20 psf TOP CHORD+Lon-con—t WOOD TRUSSES. <br />10 psf BTM CHORD-non-conwrront <br />DEAD LOAD DEAD LOAD <br />15 psf TOP CHORD 20 psf TOP CHORD <br />(7 psf WASPHALT SHINGLES) (10 Psf W/ No GYPCRETE) <br />10 psf BTM CHORD 5 psf BTM CHORD <br />DEAD LOAD TO RESIST W ND UPLIFT: I Opsf <br />BALCONY LIVE LOAD SO psf <br />STAIRS LIVE LOAD 40 psf <br />WIND DEAD LOAD SPEED =180 WH 3- SECOND GUST <br />(ASCE 7-10 (FBC R2017) EXPOSURE B, RISK CATEGORY 11) <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC <br />ALL SWOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO <br />THE ARCHITECT. DRAWINGS SUBMITTED WITHOUT REVIEW W LL BE RETURNED UNCHECKED. <br />SWOP DRAWINGS IN THE FORM OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON- <br />TRACT DOCUMENTS) ARE PROHIBITED WITHOUT THE EXPRESS WRITTEN PERMISSION FROM <br />THE ENGINEER. <br />IN ALL INSTANCES, THE CONTRACT DOCUMENTS W LL GOVERN OVER THE SHOP DRAWINGS <br />CHECKED, UNLESS OTHERWISE SPECIFIED IN WRITING BY THE ARCHITECT. <br />FOUNDATIOW SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, <br />FOOTING CG EXCAVATIONS AND SLAB SUERADE SHALL BE COMPACTED TO A DRY DENSITY <br />OF AT LEAST 95% OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN <br />ACCORDANCE WTH ASTM D-1557. TREAT ALL SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER <br />TO VERIFY SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS <br />FAILING TO MEET THE GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RECOMPACTEDAND <br />RETESTED AT THE CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WBTTEN <br />CERTRCATfON THAT THE MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION <br />REQUIREMENTS HAVE BEEN MET SHALL BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLABCNGRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS WITH HISTORICAL STRWGGTH DATA <br />FOR EACH SEPARATE MIX PRIOR TO CONCRETE PLACEMENT. CONCRETE SLUMP SHALL <br />NOT EXCEED S./- PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C44OR <br />MEASURING, WIND, TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE TIME AMA <br />WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS ADDED <br />TO THE MX UNTIL IT IS DEPOSITED W ITS FINAL POSITION SHALL NOT EXCEED 90 MNITES <br />IF FOR ANY REASON THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN <br />90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE RESPONSIBILITY OF <br />THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATVE AND THE CONTRACTOR OF ANY NON COMPLIANCE WITH THE <br />ABOVE <br />REQUIRED CONCRETE COVERAGE OVER RBWRSHALL BE AS FOLLOWS <br />A 3" FOR CONCRETE CAST AGAINST AND PERMANWTLYE)WOSEDTO EARTH (FOU DATIONSY. <br />& FOR CONCRETE EXPOSED TO EARTH ANDADRWEATHEt <br />1402' FOR 05 ANDSWLER <br />2'FOR 06 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />314' FOR SLABS, WALLS AND JOISTS <br />1412'FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />05 BAR - 30' #7 BAR - 42" <br />PROVIDE 36'x 38' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION, <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WTHANSI A58.1-/982. <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS, <br />WALL. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />ROOF S, FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />DO NOT OUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />WITHOUT THE APPROVAL OF THE ENGINEER <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PUNS SHALL BE NOTIFIED TO THE <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />MASONRY: <br />PROVIDE ENGINEERED SHOP DRAWNGS OF EACH INDIVIDUAL TRUSS AND FULLY DIMENSIONED ERECTION <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAW NGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />"SPECIFICATION MASONRY STRUCTURES" NCI 530/ ASCE 5TMS 402, BUILDING CODE REQUIREMENTS FOR <br />LICENSED PROFESSIONAL ENGINEER <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDEDTO FACILITATE THE <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />PROVIDED BY THE TRUSS ENGINEER. <br />MANUFACTURED IN CONFORMANCE WTH ASTM C-90, GRADE fm = 1500 PSI. BLOCK SHALL BE PLACED USING <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />OF THE DELEGATED TRUSS ENGINEER. W ND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />AND CLADDING W ND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ASTM C-478, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN, THE GROLF MIX SHALL HAVE A MAXIMUM 318" <br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USP STRUCTURAL <br />COURSE AGGREGATE, AND SHALL BE PLACED W A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION <br />CONNECTORS" BY USP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS <br />TO CONSOLIDATE GROUT. <br />WITH THE SIZE AND NUMBER OF BOLTS/NAILS AS RECOMMENDED BY THE MANUFACTURER IN THE <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />LATEST CATALOG. <br />PROPORTIONED AND MIXED AS OUTLINED LNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOLID WTH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANDOR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O <br />STRUCTURALSTEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WTH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />ASS, Py = 36 W FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-M, GRADES, <br />Fy = 46 ksL STRUCTURAL PIPE SHALL SE ASTM-83, GRADE B, TYPE E OR S, Fy = 35 IMS. TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WTH THE TURNOFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />APPUGIION <br />SITE <br />1. <br />.—No <br />REMA— <br />APPUGTON <br />SITE <br />T" <br />SPACING <br />REMARxB <br />1—TfURRINOTO <br />CASE HAFDBJ®WL <br />S"CVO <br />OMAGE ODOR 9A. <br />S DETNL <br />SEE DETNL <br />SEE DETNL <br />SEE DETNL <br />MPSOIJRY/GONG <br />NNLI1?LOFT;. <br />MA.--. <br />SOD, AL, EXT DOORS <br />CAGE HARDBJ®COAL <br />B•OC <br />--EN' <br />GARADEDOCRAxx <br />SEEDETNL <br />SEE DETNL <br />SEE DETNL <br />SEE DEi <br />1a PT. SEENOTE8 <br />NNLII LONG, <br />STAOGEREO <br />INTO MAR NRY/ODFL <br />To MARNRYIWFG <br />WINDOWS.- <br />CNSEHARDENEDCOIL <br />B•OIC <br />WNDOWNDORIFASTENED <br />METAL 11-1 <br />CONTACT THIS ENGINEER FOR SPACING <br />Ix PT —NOTES <br />NNLI-LONG. <br />STAwERED <br />INTO MARMrIODNC <br />MA0011RYICONC <br />REQUIREMENTS <br />EXt. SWING DOOR <br />(2)3MS•M <br />'TAPCOM <br />11n"EMBEfAB'END <br />NON6EARNG HOOD <br />1T ExPANSw 1"EMBED. 4"END <br />SUCK U PT. SEENDTEB <br />NO WASHER <br />FASTNER <br />18"C� <br />.'ET.. 1Y2"EDSm, <br />WA-LN C. SLAB <br />W/WA91ER Sq.T 2—DIST., 3°EDGEDIST <br />2a Pf —W ELIIX 0130°PAF r 21S' B•dG 1-END..1.1 1? <br />PT I. STEEL COL., bEE W,I W,� STAOGH2ED EDGE DI AT. <br />NOTES <br />I.STAP SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / OR RDA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIEDHEREIN <br />& FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. W NDOW AND DOOR BUCKS SHALL BE AS WIDE OR W DER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SW NG DOOR WITH A WOOD DOOR FRAME, 1. MEMBERS ARE NAILED AND <br />Zx MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />C <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32780 <br />PH: 407-7748078 <br />FAX: 407-774-4078 <br />www.abd"kgngroup.wm <br />AA8:0003325 <br />a <br />D <br />O <br />T <br />os�s� <br />sVSDIV. as LOT•. <br />SILVERADO <br />LOT #59 <br />BLK #06 <br />4 .002-59 61 <br />)1LOD�Lt <br />4EAB <br />"1672- ARIA" <br />OARAGZ DW515 <br />RIGHT <br />PAOI M <br />DETAILS <br />50 MPH EXP. Bj <br />L AR NO 93723 i <br />a 03/11/19 <br />91CALM 1/4"=1'-O" <br />sNI <br />