Laserfiche WebLink
HVAC NOTES <br />L ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH PROPER CLEARANCE, FOR SERVICING, PER <br />MFG. REQUIREMENTS. <br />2. ALL DUCT SYSTEMS INSTALLED IN NON -CONDITIONED AREAS SHALL BE CONSTRUCTED OF A VALUE <br />OF NO LESS T44EN R-6 RATING. ALL SEAMS SHALL BE SEALED WITH GLASS FA15 4 MASTIC. AND <br />INSTALLED AS PER FBC 6TH EDITION (2011) MECHANICAL BLDG. CODE SECTION 603. <br />3. ALL FLEX DUCTS SHALL BE APPROVED UL 181 CLASS I AIR DUCT AS PER N°PA WA 2-3.1 <br />4. FRESH AIR INTAKES SHALL NOT. BE LOCATED CLOSER THAN 10 FT. FROM ANY CHIMNEY OR VENT <br />OUTLET, OR SANITARY SEWER VENT OUTLET <br />5. ALL EXHAUST AND OUTSIDE AIR INLET DUCTS, SMALL BE CONSTRUCTED OF SMOOTH GALV. METAL. <br />OR OTHER MATERIALS AS PER FBC 6TW EDITION (2011) MECHANICAL CODE SECTION 603 <br />6. ENCLOSED SUPPORT PLATFORMS SHALL 15E CONSTRUCTED IN ACCORDANCE TO FBC 6TH EDITION <br />(20f1) MECHANICAL CODE 603.1 <br />1. BATHROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR BATHING FIXTURES SHALL BE <br />MECHANICALLY VENTED IN ACCORDANCE WITH POO 6TH EDITION (2011) MECHANICAL CODE SECTION <br />403. <br />8. ALL EXHAUSTED BATH ROOMS, SHALL NAVE UNDER -CUT DOORS FOR MAKE-UP AIR TO BE <br />RETURNED, TO EQUAL AIR EXHAUSTED. <br />S. ALL FIRE RATED CEILINGS AND WALLS SHALL HAVE AN APPROVED FIRE OR FIRE/SMOKE <br />DAMPER'S LOCATED AT CEILING OR WALL PENETRATION AND BE SLEEVED WITH ACCESS DOORS TO <br />RESET DAMPER ALL DAMPERS SHALL 6E INSTALLED TO MFG. RECOMM1ENDATICNO AND MC 6TH <br />EDITION (2011) MECHANICAL CODE SECTION 601. <br />10, GRILLES AND DIFFUSERS SHALL BE PROVIDED WITH BALANCING DAMPERS. <br />II. DRYER BOOSTER TO BE A FANTECH DBF BOOSTER FAN OR EQUAL. <br />FANTECH DBF 110 DRYER BOOSTER CAPACITY 60 LINEAR FEET WITH MAX SIX ELBOWS. <br />ATTIC <br />AIR SUPPLY �—�L <br />1 <br />AIR HANDLER <br />EVAP. TRAY <br />NOTE <br />ALL HVAC TO HAVE PROPER <br />PANS W/ DRAINS <br />ERIOR WALL <br />RETURN <br />SUCTION AND LIQUID <br />REFRIGERANT LINES <br />EXTERIOR WALL <br />3/4' PVC OONDENSATE DRAIN LINE <br />PVC SLEEVE TO LINES BELOW SLAB <br />t REFRIGERANT LINES TO <br />RETURN <br />RIt/ /_ <br />CONDENSING UNIT <br />TRAP DRAIN LINE AND TERMINATE <br />IN AN APROVED DRAIN, AS PER <br />POOR 6TH EDITION (2011) <br />MECHANICAL DLM CODE <br />SECTION 3012.4 <br />HVAC DRAINS <br />LEGEND <br />® <br />SUPPLY AIR DIFFUSER <br />m <br />RETURN AIR GRILL <br />® <br />SIDE -WALL OR I WAY DIFFUSER <br />— <br />SOLID LINE- SUPPLY TRUNK <br />— <br />BROKEN LINE- RETURN TRUNK <br />1 <br />BALANCING DAMPER OR OBD <br />O <br />CEILING EXHAUST FAN <br />CEILING EXHAUST FAN 4 LIGHT <br />O/A <br />OUTSIDE AIR <br />® <br />THERMOSTAT <br />m <br />PASS-THRJ AIR GRILL <br />SECURE STRAP TO CONC. <br />W/ (2)-3/**X2' TAPCONS CONUNIITR SIMPSON WB ROLL STRAP <br />OR EQUAL <br />4' CONCRETE SLAB SECURE STRAP TO UNIT W/ (2) <br />13XI 1/4' SHT. MTL. SCREWS <br />CONDENSER UNIT <br />CONNECTION TO PAD <br />NOTE: MAIN COND. DRAIN 3/4' DIA <br />OVER HEAD • 12' FROM STRUCTURE <br />COUNTERSUNK <br />SCORIATED NICKEL <br />FIN. FLOOR <br />C.O. PLUG <br />BRONZE FL. PL. <br />OR WALL <br />` SEE SPEC, <br />1'-8'X8' CONC. <br />BRASS PLUG <br />FIN. GRADE <br />OR PAVING <br />FITTING OR EXTENSION TO <br />SOIL WASTE AS <br />FITTING OR <br />IM <br />REQUIRED <br />EXTENSION TO SOIL <br />OR WASTE AS <br />WADE 8240-K JOSAM 560" <br />REQUIRED <br />INSIDE <br />SERIES NICKEL BRASS TOP <br />CAULK <br />P.V.0 OPTI/8PEC <br />FLOOR SLAB CLEAN -OUT (TYP� XT. <br />nEGROUND CLEAN -OUT (TYP. ) <br />MECHANICAL PLAN <br />SCALE 1/4 " P-0' <br />■ <br />6 <br />A R C M I T 1 0 T• <br />Grou�� <br />1441 N. RONALD REAOAN BLED. <br />LONGWOOD, FL32750 <br />PH: 407-774,6078 <br />FAX: 407-7744078 <br />www.abdeWgngroup.eom <br />AA k: 0003326 <br />amm; <br />StJHDM ae I+OT: <br />SILVERADO <br />LOT #3 <br />BLK, #13 <br />PROJECTp <br />03719.000-03132 <br />MODau <br />"2045-LANTANA" <br />GARAGE ETRNG: <br />RIGHT <br />PAGE: <br />MECHANICAL <br />PLAN <br />150 MPH EXP. B"ff <br />