GABLE -ENO <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-10 <br />ZONE 1 = 8.97 PSF (19.97) <br />ZONE 2 =17.98 PSF (27,98) <br />ZONE 3 = 33.53 PSF (43.53) <br />"A'= 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE: "W <br />RISK CATAGORY: It <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT , 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16" <br />O.S.B. OR 1/2" COX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. &8 COX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND Sd RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />8d GUN NAILS @ 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE <br />END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. CIA. <br />SHANK <br />TENSILE STR. <br />SHANK <br />Bd <br />RING SHAH K <br />2 12" <br />0.120" <br />170,000 <br />RING <br />(16-2RINGS <br />SCREW SHANK <br />I <br />PER NCH) <br />8d <br />SCREW SHANK <br />21/7' <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL 8 TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTERIOR SHEATHNG <br />USE 12" COX OR 7/16" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP 8 <br />BOTTOM PANEL AND Sd RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />TOP CORD BLOCKING AT W <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />RAFTER OR TRUSS --`` <br />k <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />8d RING SHANK GUN NAILS @ 4" O.C. FOR GABLE END FRAMM <br />TOP & BOTTOM EDGES <br />rn <br />J <br />GG <br />ZS <br />� w , <br />z <br />S U <br />GO <br />U) <br />J <br />Yir <br />a <br />N <br />CO . <br />z <br />w <br />O w 8d RING SHANK GUN NAILS <br />Z 7($ 8" O.C. INFIELD <br />U <br />O <br />z 'v <br />z <br />. <br />.. TO BE STRUCTURAL GRADE) <br />Q <br />LU <br />6 LU <br />M <br />tiU w <br />C <br />W U <br />U ¢ L? <br />Sd RING SHANK GUN NAILS @ 12" O.C. IN <br />FIELD or 8d X 2 12" SCREW SHANK <br />CO 2 O <br />PNEUMATIC SCREW -NAILS Q 12" 0.G,IN <br />ip <br />U.1 <br />z <br />a <br />FIELD J\ <br />TYP. 314" T8G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS, APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 681 EDITION <br />ACI 318.14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 5.13 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC33 MAXIMIMAGGFEGATE SIZE SHALL BE 3w4 <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CFWMFERED 31C. <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEA®RANE UNDER ALL SLASSONO1 OUNO WHERE INDICATED ON <br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALEDWITH ADHESIVE TAPE. <br />FORM -WORK: <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />WOOD: <br />NON -BEARING WOOD WALLS TOP PLATES S STUDS CAN BE SPF. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. FE = 1100 PSI AND A MODULUS OF <br />ELASTICITY :ILLS, <br />PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.26 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />CONTAINS MORE THAN IT OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, 681 EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTORS RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH' <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />WOOD TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 7 CHAIRS SPACED Y-O* OC, EACH WAY. <br />DESIGN SPECIFICATIONS FOR <br />TOE DESIGNED AND FABRICATED IN ACCORDANCE WITH A. TRUSS DESINALGNS <br />STRESS -GRADE LUMBER AND ITS FASTENINGS'BY THE NFPA. TRUSS DESIGNS SHALL SIGNED AND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS, <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS, <br />O <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND, <br />REBAR SHALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED, <br />GRADE 60IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14,'DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND 'TPUWTCA SCSI 1' <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL-PLATE-CCNNECTED <br />20 psf TOP CHORD -rrorl-continent <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />WOOD TRUSSES. <br />10 psf BTM CHORD-nonconananl <br />#5 BAR - 30" #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36' X 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM RESAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982. <br />15 psf TOP CHORD 20 psf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) psf w/ No GVPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />5 p <br />10 psf BTM CHORD 5 psf BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opef <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 psf <br />WALL. <br />TRUSSESIGIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF A FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />WIND: DEAD LOAD SPEED =ISO MPH 3. SECOND GUST <br />(ASCE EXPOSURE B, RISK CATEGORY 10 <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY 5 ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />BIT BLE(FBATTIC <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf UNINHABITABLE ATTIC WITH LIMITED <br />LAYOUT, SPANS a ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20pa/, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL 70 ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND <br />AND DECKS: 40p8f, GUARDS AND HANDRAILS: 200pef, GUARD IN -FILL COMPONENTS: BODO, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50ps1, OTHER THAN SLEEPING ROOM: 40pst, SLEEPING ROOMS: 30pe, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />MASONRY, <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />-SPECIFICATION MASONRY STRUCTURES-(ACI 530/ ASCE SYTMS 402, BUILDING CODE REQUIREMENTS FOR <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm = 20DO PSI. BLOCK SHALL BE PLACED USING <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM G476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318" <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 1 V. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATIOW SITE PREPARATION' <br />"S' <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL SEARING PRESSURE OF 2,000 pet, FOOTING <br />TYPE "M' OR MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1567. TREAT ALL CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS <br />2.600 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, NTH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5' 44- PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REGUIREMENTS OF ACI 301 AND ASTM C44 OR MEASURING, MIXING, TRANSPORTING, ETC <br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOYED FROM WHEN WATER IS <br />ADDED TO THE MX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON THERE IS A <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE <br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE WITH TIE ABOVE, <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A. T FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER <br />I:Ur FOR #6 AND SMALLER <br />2' FOR WAND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3" FOR SLABS, WALLS AND JOISTS <br />1-IQ" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />STRUCTURAL STEEL: <br />THE MATERIAL FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36, Fy = 38 ksl FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B, <br />Fy = 46 kel. STRUCTURAL PIPE SHALL BE ASTIk53, GRADE 8, TYPE E OR S, Fy = 35 MI. TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A3254N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL, J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APRKATNIN <br />SQE <br />TYPE <br />3PACNG <br />APPLIGATpN <br />9� <br />TYPE <br />PACMx; <br />REMARKS <br />1. PT FURRING TO <br />MASONRY/RING. <br />CASE HARDENED COB <br />NAIL +1lCLONG. <br />a WG <br />GARAGE DOOR 8- <br />TO H EmRYCONC. <br />1IPOK <br />NO WASHER <br />TAPCON M,lSO1RV <br />FASTENER <br />+VY EMBED„1•ENO pST.. <br />I - EDGE DOT. <br />SOD. AL. EXT. DNPS <br />CASEHARDENEDCOIL <br />W'O'c <br />WIND-NED <br />GARAGE DOOR SUCK <br />tYl ..Wl <br />EKPANe..-T <br />24'OIC <br />4"EMBED., 4"END DUST <br />a PT, SEE NOTE. <br />NAIL I 1-STAGGERED <br />INTO MASONRVAXINC. <br />To MASCNRYI�IIC. <br />WASHER <br />S-EDGEDOT. <br />wlNDow Bux <br />_NARO _cox <br />- <br />wlNoow,D FASTENED <br />MErAL STIUPro <br />CONTACT THIS ENGINEER FOR SPACING <br />+a PT.9EE NDTEe <br />e11?LONG. <br />STAGGERED <br />Oro MASONRVATYIC. <br />MAsorwY+CONC. <br />REQUIREMENTS <br />Exr. SWwD D00R <br />(2)SheOU. <br />'TAPCON' <br />1. dC <br />ttR• EMBED,B'ENO. <br />NON-I-WOCD <br />+/Y- EXPANSION 4'EMBED.'N' <br />34 dC <br />BIlCN 2s m,9EE NOTES <br />NDWASHER <br />FASTNER <br />DUST., 11WEDGEDOT. <br />WALLTO CONG 9lA9 <br />WIWASHER BOLT DOT.,T EDGE DOT. <br />2xEE GIW., PAF Ve' 9.O/G LEND, DOT.. 11(s" <br />P0STSi L COLWBUCK, bEE A2 <br />. STAGGERED EDGE DIET. <br />TEB <br />NOW <br />1ES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILT[ X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NGA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE, <br />pin <br />WLG G <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774.6078 <br />FAX: 407-7744078 <br />www.abdesigngroup.eom <br />AA N: 0003325 <br />DRAFTING BY: <br />A.B. DESIGN GROUP <br />DRAFTING INC. <br />5439 BEAUMONT CENTER BLVD. <br />SUITE 1004 <br />TAMPA, FLORIDA 33634 <br />PH: 8134MM-262S <br />FAX: 8134M&2802 <br />s9mm <br />UHDIV. Ae LOT <br />SILVERADO <br />LOT #4 <br />BLK #14 <br />PROJECT# <br />03719.000-04141 <br />MODEL: <br />2795- D <br />GARAGE BVING: <br />RIGHT <br />PAGE: <br />DETAILS <br />150 MPH EXP. B <br />DATTErRD. 10/30/20 <br />BCAL C: 1/4"=1'-0" <br />SHEET <br />S N1 <br />