q <br />i w <br />HIPROOF <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-10 <br />ZONE 1 = 8.97 PSF (19.97) <br />ZONE 2 = 17.98 PSF %.98) <br />ZONE 3 = 33.53 PSF 43.53) <br />"A"= 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE:'B' <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT w 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16" <br />O.S.B. OR 1/2"CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 5/8 CDX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND Sd RING SHANK GUN NAILS <br />AT 6' O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />Sd GUN NAILS @ 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL PANEL JOINTS W/ IN *OF GABLE <br />END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA. <br />SHANK <br />TENSILE STR. <br />SHANK <br />Sd <br />RING SHANK, <br />2 1/2" <br />0.120" <br />170,000 <br />RIN <br />(i6-20 RINGS <br />SCREW SHANK <br />PER INCH) <br />8d <br />SCREW SHANK <br />2 12" <br />0.120" <br />PNEUMATIC <br />-SCREW-NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTERIOR SWA71-ING <br />USE 1/2" CDX OR 7116" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND Sd RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Bd RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />'v <br />a <br />Z W <br />Z C7 <br />5 W <br />Y 0 <br />QU <br />�O <br />C7 <br />K <br />GO <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />TOP & BOTTOM EDGES <br />J <br />JQ <br />2 . <br />Q <br />Z J <br />� w <br />� LL <br />Y Z <br />O <br />U) <br />QJQ <br />Y <br /><Z <br />z <br />2 <br />ZLU <br />z0 <br />U W <br />Y (ED <br />< d <br />y0 <br />O :r <br />z <br />zp <br />W <br />J <br />N <br />W <br />NU W <br />In <br />�p <br />LU p <br />W <br />a <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />RAFTER OR TRUSS--� <br />ROOF SHEATHING <br />■111■111■111,mill <br />�E��m11 <br />I,■����►11 <br />SEENNEENME 1 <br />L, BUILDING LENGTH <br />.. <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />Bd RING SHANK GUN NAILS <br />6" O.C. IN FIELD ` <br />C8d RING SHANK GUN NAILS @ 12" O.C. IN <br />FIELD or 8d x 2 12" SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 12" 0.G,(N <br />FIELD J\ <br />TYP. 314" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMUM AGGREGATE SIZE SHALL BE 3/4", <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD. <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />pROVIDE B%AIR ENTRAINED CONCRETE EXPOSED TO EARTH ORWEATHBi <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWIS FOR SLEEVES. DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ALL EXPOSED EDGES TO 3/4'. <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 6th EDITION <br />OF CONCRETE ARE BE CHAMFERED <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES. BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />PROVIDES-MILCONTINUO 8 POLYETHYLENE VAPOR HARMER MEMBRANE UNDERALL SLABS -ON -GROUND WHERE INDICATED ON <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb =1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, ACI 630.13IASCE 51 3011, AISI SPECIFICATION FOR THE DESIGN OF <br />DRAWINGS. SEAMS IAPPEDBINCIfSAM81 SEALED WITH ADFIESIVE TAPE. <br />ELASTICITY = PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COL0.FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />A <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />TREATED. <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS. SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN'/.' OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017. 6th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALAEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SVP 02' <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH' <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM Al85. GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />WOOD TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENt THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />TYPICAL DETAILS, MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS, <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />20 psf TOP CHORD -non-mnwrtent <br />10 psf BTM CHORD nolHmn Tent <br />DEAD LOAD DEAD LOAD <br />15 psf TOP CHORD 20 PSf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) (10 psf W/ No GYPCRETE) <br />10 psf BTM CHORD 5 psf BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT: 1Opsf <br />BALCONY LIVE LOAD 60 psf <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD SPEED =150 MPH 3- SECOND GUST <br />(ASCE 7-10 (FBC R2017) EXPOSURE 8, RISK CATEGORY IO <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WITH LIMITED <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30PSf, BALCONIES (EXTERIOR) <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50paf, PASSENGER <br />VEHICLE GARAGES: SOW, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />40 f <br />Ps <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />WRITING BY THE ARCHITECT. <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95'% OF THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557, TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER, <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2.500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR WU SUBMT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MX PRIOR TO <br />CONCRETE PLACEL934T. CONCRETE SLUMP SHALL NOT EXCEED 6 N-PRKMRTO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C44 OR MEASURING, MXING, TRANSPORTING, ETC. <br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS <br />ADDED TO THE MIX UNRL IT IS DEPOSITED IN ITS FINAL POSITION SMALL NOT EXCEED 90 MNUTES. IF FOR ANY REASON THERE IS A <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SMALL NOT BE PLACED. IT SWILL BE THE <br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3'FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATIONS): <br />S. FOR CONCRETE EXPOSED TO EARTH ANWOR WEATHER <br />1.12' FOR #5AND SMALLER <br />2' FOR 116 AND URGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3fP FOR SUBS, WALLS AND JOISTS <br />1.12' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />GRADE 601N MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: 94 BAR - 25' #8 BAR - 36" <br />#5 BAR - 30" #7 BAR - 42" <br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, -DESIGN NATIONAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "TPIAVTCA SCSI V <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982, <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />WALL, <br />TRUSSESIGIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR 70 MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />MASONRY. <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />"SPECIFICATION MASONRY STRUCTURES" (ACI BUILDING CODE REQUIREMENTS FOR <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />FWl OR MASONRY TRU <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />MANUFACTURED #4 CONFORMANCE WITH ASTM C-90, GRADE Tm - 2000 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 740 COMPONENT <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />ASTM C476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM WS' <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8' TO 10'. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />TYPE "M" OR'S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270, HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 3/8- THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING, <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />STH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36, Fy = 36 ksl FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B, <br />Fy = 46 ksl. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE B, TYPE E OR S, Fy - 35 ksl. TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURWOFF-THE-NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JSOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLICATION <br />SfIE <br />TYPE <br />EPA— <br />REMARKS <br />APPLICATION <br />SIZE <br />TYPE <br />ACING <br />REMARKB <br />1n4 PTFURRWOTO <br />4IXYi1/GONG <br />CASEHMDENEDOOx <br />11?LONG. <br />B"O.0 <br />GARAGE DOORBIICK <br />TO IMSOM ,OGNC. <br />/PEW. <br />NO WASHER <br />TAPCON MABOIAY <br />FASTENER <br />e. <br />11R'EMBE0. P END DIST., <br />I-EDGEg3T. <br />SOD. AL. Exf. DO0R5 <br />CASE HARDE1ED Cql <br />P G <br />WINDOW,DOpV FASTENED <br />GARAGEDOORBUCK <br />1a DW. WI <br />x'EMBEDGE EW019i.. <br />Pf. SEE NOTES <br />NMLI—LONG. <br />STAGGERED <br />INTO MA90NRY G. <br />TO 1M90NRY/CONC, <br />WASHER <br />EKPANSKNI BOLT <br />28,E <br />S"EDE DIET. <br />WDOW EUCK <br />CA9EI—DE <br />r <br />W.—FASTENED <br />METAL STRAPTo <br />CONTACT THIS ENGINEER FOR SPACING <br />ix PT, WE <br />NAxi1lS LONG <br />STAGGERED <br />INTO— <br />MAAONRY,CONC. <br />REQUIREMENTS <br />fXT. SWING DOOR <br />RI #1COW. <br />RMCOIT <br />11G, K.,—ND. <br />N6EAR <br />NOINGWOW <br />M1.PEND 1F1� "I'91ON PEMEEO <br />WCK2 ,9EI W <br />—SHER <br />FASTNER <br />18'pC <br />D19T., I— EDGE DUST. <br />WALL TO DOW.SIAB <br />W/WASHER BOLT 24 WC DIST., YEDGEDIST. <br />GA PT WINDOW BUCK <br />0.1N°PMA]11H' S'OIC019T„it? <br />IT TO STEEL COL., SEE WI WAAHER STAOGEAEO EOOE ORT. <br />W ES <br />NOTEB <br />1LES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND/ OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE RAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAP TO THE SUBSTRATE. <br />1441 N. RONA GAN BLVD. <br />ORLAN FL 2780 <br />PH: TT 78 <br />FAX: 40-.. 078 <br />W W W.abdeslgn8roup.Gom <br />AAA: 0003325 <br />DRAFTING BY: <br />A.B. DESIGN GROUP <br />DRAFTING INC. <br />5439 BEAUMONT CENTER BLVD. <br />SUITE 1004 <br />TAMPA. FLORIDA 33634 <br />PH: 8134MS-2628 <br />FAX: 813886.2802 <br />SUHn:v & LOT <br />SILVERADO <br />LOT #13 <br />BLK #13 <br />PROJECT# <br />mopmu <br />2795—F <br />GARAGE 8 <br />LEFT <br />PAGE: <br />DETAILS <br />V. 150 MPH EXP. B <br />NOV <br />DA1W'E". 10/30/20 <br />SCALE: 1/4"=1'—O" <br />8HEET <br />SN1 <br />