GABLE -END <br />i A <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-1 0 <br />ZONE 1 •8,97 PSF (19.97) <br />ZONE 2 • 17.98 PSF (27.98) <br />ZONE 3 •33.53 PSF (43.53) <br />"A"• 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE: "B" <br />RISK CATAGORY: It <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT -- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7116' <br />O.S.B. OR12" CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />" MIN. 5/8 COX EXT. PLYWOOD, WITH 8d RING <br />_ SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT S" O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />Sd GUN NAILS 0 4" O.C. EDGEWISE 2x4 <br />BLOCKING ALL PANEL JOINTS W/ IN W OF GABLE <br />END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA. <br />SHANK <br />TENSILE STR. <br />SHANK <br />Sd <br />RING SHANK, <br />21/2" <br />0.120" <br />170,000 <br />I G <br />SCREW SHANK <br />6-0 RINGS <br />PER2 <br />8d <br />SCREW SHANK <br />21/2" <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTERIOR SHEATHING <br />USE 1/Y' CDX OR 7/1&' O.S.B. PLY WITH Sd RING <br />SHANK GUN NAILS AT C O.C. AT PANEL SIDES <br />AND Bd RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Sd RING SHANK GUN <br />NAILS AT W O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />Sd RING SHANK GUN NAILS @ 4" O.C. <br />TOP & BOTTOM EDGES <br />.......... <br />a <br />� <br />z9 <br />-L L <br />M <br />Lu <br />n W <br />C7 u <br />ZZ <br />< O <br />Z <br />Lj <br />p <br />y <br />y d Z <br />I. <br />0 <br />Z <br />$ 0 <br />/1 Z <br />N <br />z <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />.� DER OR Tu ^SS—� <br />Emm <br />hl(,l I I <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />8d RING SHANK GUN NAILS . <br />6" O.C. IN FIELD <br />TYP. EXT. SHEATHING ATTACHMENT FOR ROOF SHEATHING ( .B. <br />TO BE STRUCTURAL GRADE <br />�-• Sd RING SHANK GUN NAILS ® 12' O.C. IN <br />FIELD or 8d x 212" SCREW SHANK <br />PNEUMATIC SCREW -NAILS 0 12' 0.E).jN <br />FIELD J\ <br />TYP..' T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, BIN EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, ACI 530-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL Be CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWM. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS, <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES RE ND. S A FOUND. EP NCE O <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />20 psf TOP CHORD --mirrent <br />10 paf BTM CHORD-nan-wnwrrent <br />DEAD LOAD DEAD LOAD <br />15 pat TOP CHORD 20 Pef TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) (10 psf w/ No GYPCRETE) <br />10 psf BTM CHORD 5 pef BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT: IDpsf <br />BALCONY LIVE LOAD 00 Pat <br />STAIRS LIVE LOAD 40 PSI <br />WIND: DEAD LOAD SPEED -160 MPH 3- SECOND GUST <br />(ASCE 7-10 (FBC R2017) EXPOSURE 8, RISK CATEGORY 10 <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO <br />THE ARCHITECT. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. <br />SHOP DRAWINGS IN THE FORM OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON- <br />TRACT DOCUMENTS) ARE PROHIBITED WITHOUT THE EXPRESS WAiI77EN PERMISSION FROM <br />THE ENGINEER. <br />IN ALL INSTANCES, THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS <br />CHECKED, UNLESS OTHERWISE SPECIFIED IN WRITING BY THE ARCHITECT. <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PSI, <br />FOOTING EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY <br />OF AT LEAST 95%OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN <br />ACCORDANCE WITH ASTM D-1557. TREAT ALL SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER <br />TO VERIFY SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS <br />FAILING TO MEET THE GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND <br />RETESTED AT THE CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN <br />CERTIFICATION THAT THE MINIMUM DESIGN BEARING CAPACITY, AND THAT RE COMPACTION <br />REQUIREMENTS HAVE BEEN MET SHALL BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED NIX DESIGNS, WITH HISTORICAL STRENGTH DATA <br />FOR EACH SEPARATE MIX PRIOR TO CONCRETE PLACEMENT. CONCRETE $LIIMP SHALL <br />NOT EXCEED S H- PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMEKS OF ACI 301 AND ASTMC44 OR <br />MFASMONG, MIXING, TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED <br />WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS ADDED <br />TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES. <br />IF FOR ANY REASON THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN <br />SO MNUTES, THE CONCRETE SHALL NOT BE PLACED. IT SWILL BE THE RESPONSIBILITY OF <br />THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON COMPLIANCE WITH THE <br />ABOVE. <br />REOUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATDNSr <br />S. FOR CONCRETE EXPOSED TO EARTH ANDOR WEATHER <br />"W FORMS AHD SMAL ER <br />, FOR MS AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3W FOR SLABS, WALLS AND JOISTS <br />I.1R" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMUM AGGREGATE SIZE SHALL BE 3/C. <br />WOOD: <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3/1'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />PROVIDE 64AL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDERAll BIABS-0N-GROUND WIVE INDICATED ON <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb - 1100 PSI AND A MODULUS OF <br />PROVIDES. SEAMS TAPPED S INCHES AND SEALED WITH ADHESIVE TAPE. <br />ELASTICITY = 1,400,0110 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED, WOOD FOR NONSTRUCTURAL USES <br />RATEDSHALL BE TO I <br />I(DOT�LAT UM <br />FORMWORK: <br />CORROBORATETETRAHEDRAL WOOD FORS STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN %' OF HEARTWOOD. <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBR 2017, SIN EDITION. SEE NAILING SCHEDULE ON PLANS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEYARE NOT CONSIDERED TO BE STRUCTURALDEPENDING PROVIVI DE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOF COLUMNS WITH h STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP <br />WELDED WIRE MESH: <br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 05 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2' CHAIRS SPACED TW OC, EACH WAY. <br />REINFORCING STEEL <br />REBAR SHALL BE ASTM .A615 GRADE 60 DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN <br />ACCORDANCE W THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE AG STANDARDS AND <br />SPECIFICATIONS. CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO <br />FABRICATION. HORIZONTAL AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE <br />SUBJECT TO ENGINEER'S REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: M4 BAR - 25" NB BAR - W' <br />p5 BAR - 30' 87 BAR - 4Z' <br />PROVIDE 38' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A448, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION: AND 'TPIAWTOA SCSI 1" <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS, <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />WALL. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />MASONRY! <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED 8, A FLORIDA <br />"SPECIFICATION MASONRY STRUCTURES" (ACI 530/ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />LICENSED PROFESSIONAL ENGINEER. <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />PROVIDED BY THE TRUSS ENGINEER. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE Pm = 1500 PSI. BLOCK SHALL BE PLACED USING <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />OF THE DELEGATED TRUSS ENGINEER. VIAND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />PLACING CONCRETE FOR IN -WALL COLUMNS, GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />ALL TRUSS 70 TRUSS CONNECTIONS. <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318" <br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USP STRUCTURAL <br />COURSE AGGREGATE, AND SHALL BE PLACED W/A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION <br />CONNECTORS" BY USP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS <br />TO CONSOLIDATE GROUT. <br />WITH THE SIZE AND NUMBER OF BOLTSMAILS AS RECOMMENDED BY THE MANUFACTURER IN THE <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />LATEST CATALOG. <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />STRUCTURALSTEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A38, Fy = 36 W FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B, <br />Fy = 48 ksl. STRUCTURAL PIPE SHALL BE ASTM-53, GRADE B, TYPE E OR S, Fy = 35 W. TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING, ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APP 1-04 <br />8DE <br />rvPE <br />ePAdnc <br />RDAN&9 <br />APPU ON <br />SIZE <br />HYPE <br />ISPAGNO <br />REMaxrcs <br />1r2PTFlIRPoNOTO <br />GeE HARDENED WIL <br />S'QC <br />GAMETE ODOR BIICI( <br />SEE.— <br />BEE DETNL <br />SEE pETNL <br />SEE DETNL <br />MASONRY ICCN'C. <br />NNL I ITT LONG. <br />TO MASONRY,x%lNC <br />SOD,AL. EKT.DDORS <br />I. PT, SEE NOTES <br />CASEHARDENED- <br />NNL 11?LONG. <br />IIIWINDOw000Rl <br />STAOOERED <br />FASTENED <br />I—MA90NRYAxk10. <br />GAR AGE DOOR&1CK <br />To MASONRYKONC. <br />SEE OETNL <br />SEE DETNL <br />SEE DETNL <br />I SEE DETNI <br />wiNDnveucx <br />cASE HARDENED-- <br />e•oc <br />`MNDOWaJ00Rl FASTENED <br />METU STRAP To <br />CONTACT THIS ENGINEER FOR SPACING <br />tr PT, SEE NOTES <br />NNL 11?LONG. <br />STAGGERED <br />HMO MA90NRY.CUNC. <br />MPaONRYI CCNC <br />REQUIREMENTS <br />FM.SMNO DOOR <br />Ib 3'1B91A <br />TAPUXT <br />11/Y EAIBEO,SEID. <br />NOIYaEM1R1NO_ <br />tr EKPPNSION 22.00 A'EMSEO. <'END <br />Bl1CK ]r PT. BEE NOTED <br />NO WASHER <br />FASTNER <br />iCOF <br />GIST.. 1112' EDGE dST. <br />WALLTO CDIF. SIAa <br />WI WASHER BOLT .]•EDGE paT. <br />L PT WINDOW SIGN 0.1]8°PAFa21/d' 4"OIC A'FND pST.,11YY <br />PT To STEEL COL., SEE 4VI WASHER STAGGERED EOOE dST. <br />NOTES <br />NOTEO <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3, ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAP SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR W DER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. lx MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W TAPCONS OR PAF TO THE SUBSTRATE. <br />i44i N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774.6078 <br />FAX: 407-7744078 <br />wwwAbdesigngfoup.00m <br />AA E: 0003325 _ <br />n: <br />p�p <br />C <br />p <br />a <br />s�ss� <br />40 <br />10 <br />x <br />SILVERADO <br />LOT 63 <br />BLK 6 <br />PROJECT <br />04128.00 -63061 <br />MODETZ <br />4EBB <br />°1828-CALM' <br />GARAGE at/IIITG: <br />RIGHT <br />PAGE: <br />DETAILS <br />V.150 MPH EXP. <br />