q <br />s A <br />o.BLE-Ero <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-10 <br />ZONE 1 = 8.97 PSF (19.97) <br />ZONE 2 = 17.98 PSF (27.98) <br />ZONE 3 = 33.53 PSF (43.53) <br />"A"= 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE: "B" <br />RISK CATAGORY:II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT w 0.18 <br />ROOF DW+HRAGMI <br />FOR ASPHALT SHINGLE ROOF USE MIN 7/16" <br />O.S.B. OR 1/2" COX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 5/8 CDX EXT- PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />8d GUN NAILS @ 4" O.C. EDGEWISE 20 <br />BLOCKING ALL PANEL JOINTS W/ IN N OF GABLE <br />END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA <br />SHANK <br />TENSILE STIR. <br />SHANK <br />8d <br />RINGSHANK <br />21/2' <br />0,1201 <br />170,000 <br />RING <br />SCREW SHANK <br />(16-20 RINGS <br />PER INCH) <br />8d <br />SCREW SHANK <br />2 12" <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1, NAIL SIZE PER ASTM F1684 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTERIOR SHEATHNO <br />USE 1/2" CDX OR 7116" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT 8" O.C_ AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />TOP & BOTTOM EDGES <br />Lo <br />Z9 <br />LL . <br />Y Z <br />Z <br />y O <br />J <br />- <br />O- <br />Z <br />z . <br />z <br />(7 <br />\JJ <br />_ . <br />N <br />Z W <br />z8 <br />� W <br />z¢ <br />S U <br />NO <br />zFx <br />"a <br />TOP CORD BLOCKINGAT4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />RAFTER OR TRUSS <br />ROOF SHEATHING �\ <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />8d RING SHANK GUN NAILS <br />6" O.C. IN FIELD'\ <br />Bd RING SHANK GUN NAILS @ 12" O.C. IN <br />FIELD or 8d x 2 1)2' SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 17 O.D."N01 <br />FIELD J\ <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WTH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAMA NGS. APPLICABLE BUILDING CODE STANDARDS: FBCR 2017. 6R1 EDITION <br />ACI 318-14. BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, ACI 530-131ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF <br />COLO-FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMUM AGGREGATE SIZE SHALL BE 314'. <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3W. <br />PROVIDE 648L CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE LIVER ALL SIABSONG ROOD WHERE INDICATED ON <br />DRAWINGS. SEAMS LAPPED 61NCHES AND SEALED WITH ADFESVETAPE <br />FORM-W'ORK <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WTH ACI 347, <br />'RECOMMENDED PRACTICE FOR CONCRETE FORMWORK. <br />WOOD: <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PIPE NO. OR BETTER FD = 1100 PSI AND MODULUS OF <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />SHALL BE RATEDTO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). MOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />WI DDT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />CONTAINS MORE THIAN h' OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW VMBTTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, Bth EDITION. SEE NAILING SCHEDULE ON PLANS, <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP#2. <br />THE STRLICTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />Wa0® WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE AG <br />WOOD TRUSSES: <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2' CHAIRS SPACED 3'-O' OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE °NATIONAL DESIGN SPECIFICATIONS FOR <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOLI NDATION AND SITE PREPARATION <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NEPA. TRUSS DESIGNS SHALL BE SIGNEDAND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTEREDIN FLORIDA. SEE NOTED FOR SHOP DRAWANGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO MRK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: UVE LOAD FLOOR: LIVE LOAD 40 psf <br />20 psf TOP CHORD ­ncono Tt <br />10 P tloncBnnsf BTM CHORD -t <br />DEAD LOAD DEAD LOAD <br />15 psf TOP CHORD 20 psf TOP CHORD <br />17 psf W/ ASPHALT SHINGLES) (10 psf W/ No GYPCRETE) <br />10 psf BTM CHORD 5 prof BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT: 10psf <br />BALCONY LIVE LOAD 60 Psf <br />STAIRS LIVE LOAD 40 Psf <br />WIND DEAD LOAD SPEED=IE0 MPH 3-SECOND GUST <br />(ASCE 7-10 (FBC R2017) EXPOSURE 8, RISK CATEGORY II) <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 1 Opsf, UNINHABITABLE ATTIC WITH LIMITED <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />4Opsf <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WALL BE REVIEN.ED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES THE CONTRACT <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />WRITING BY THE ARCHITECT. <br />FOUNDATIOW SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2000 PST, FOOTING <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREATALL <br />SOIL FOR TERMITE PROTECTION. <br />REINFORCING STEEL <br />REBAR SHALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS ANDSPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 38" <br />#5 BAR - 30" #7 BAR - 42" <br />PROVIDE 36"x 36"CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALLAT THE TOP AND BOTTOM WTH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />WALL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />WITHOUT THE APPROVAL OF THE ENGINEER <br />MASONRY: <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />"SPECIFICATION MASONRY STRUCTURES" (ACI 5301 ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />ALL BLOCK WALLS SHALL BE TVWOCELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm = 1500 PSI. BLOCK SHALL BE PLACED USING <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY_Up MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />ASTM C-476 AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS UNLESS <br />SPECIFICALLY NOTED OTHERNSE ON FOUNDATION PLAN, THE GROUT MIX SHALL HAVE A MAXIMUM 318" <br />COURSE AGGREGATE, AND SHALL BE PLACED WI A SLUMP OF 6" TO 10", USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />TYPE "W OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 3/8' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />THEOAMNERSHALL RETAIN THE SERVICES OFAN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEC -TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)„ U.KO. <br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />CONCREM <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BLALOINGS, <br />9TH EDITION, BV THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />A36, Fy = 36 la FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM AS00, GRADE B, <br />Fy = 46 ksi. STRIX;TURAL PIPE SHALL BE ASTMS3, GRADE B, TYPE E OR S, Fy = 35 16i. TUBE AND PIPE <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB-014GRADE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />3,ODO PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, NTH HSiOfiICM STRENGTH DATA FOR EACH SEPARATE MIX PRKIRTO <br />TS WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BERDANCE <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED5'4-PRIORTO THE ADDITION OF PLASTICIZER <br />IN ACCOUL <br />DANCESTM <br />TENEDOLTS <br />BE TIGHTENED <br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />WEIGT THE <br />CONCRETE SHALL COMPLY WITH ALL THE REOUIREIENTS OF ACI 301 AND ASTM C-94 OR MEASURING, MANG, TRANSPORTING, ETC ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL JSOLTS ARE TO BE STEEL. <br />CONCRETE TICKETS SHALL BE TIMESTAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS <br />ADDED TO THE MX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 UNITES IF FOR ANY REASON THERE SA <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER TFAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BETHE <br />RESPONSIBILITY OF AND THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE ATIE CONTRACTOR OF ANY NON <br />COMPLIANCE MATH TIE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REST EHIRL BE AS FOLLOWS <br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONSt <br />a FOR CONCRETE EXPOSED TO EARTH ARDOR WEATHER <br />1-Art FGR 05 MND SWWLIER <br />2' FOR#5 ONO LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4' FOR SLABS, WALLS AND JOISTS <br />1412-FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT-0IPPEDGALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WTH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL-PLATECONNECTEDWOOD TRUSS CONSTRUCTION:, AND 'TPIMVTCA SCSI 1" <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WALL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-198Z <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIEDTO THE <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />PROW DE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />PLAN SHOW NG COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />LICENSED PROFESSIONAL ENGINEER <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PROVIDED BY THE TRUSS ENGINEER. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />OF THE DELEGATED TRUSS ENGINEER. WAND UPLIFT VALUES HAVE BEEN BASED ONASCE 7-10 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />A S T FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE"USP STRUCTURAL <br />ALL SHEET METAL <br />CONNECTORS" BY USP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS <br />WITH THE SIZE AND NUMBER OF BOLTS/NAILS AS RECOMMENDED BY THE MANUFACTURER IN THE <br />LATEST CATALOG. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />PPLICNTION <br />512E <br />TYPE <br />SPRClAD <br />BIg <br />TYPE <br />REM <br />N TTO <br />CAISEHINFIDENEC04 <br />S O,C <br />SEE DETNL <br />SEE DETNL <br />SEE DETNL <br />BEE DETNL <br />.. IAL. EXT DOORS <br />9EENOTE6 <br />CASEFNRDENEDLONG. COIL <br />NNL I TIT <br />90� <br />DOW/MORY/CONC. IFABTENW <br />Ni <br />GASOGE DDOB BUCK <br />TOMNgOMiVICONC <br />glE.ET <br />SEE DETNL <br />BEE DETo4 <br />9EE DETNL <br />wx4JOW- <br />I. IT, SEENETE. <br />CASEwVroENEDCOL <br />L„IZ LONG. <br />sTAoow® <br />NDow000RlEABrENED <br />METH STRAP TO <br />MrsoNRrlcoNc <br />CONTACT THIS ENGINEER FOR SPACING <br />REQUIREMENTS <br />GOOK <br />NOTES <br />(�L.1- <br />ER <br />TAPCp." <br />FASTr9i <br />1 B•OC <br />EMBEDBDB.D. <br />2<•OC MBED.r@D <br />. 3'EOGE01S1. <br />ITT :r- sT:oG�ED <br />MOM <br />1LES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND I OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILT X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. III, MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />L0 GWOOD, FL 32750 <br />PH: 407-774.6078 <br />FAX: 407-7744078 <br />W ww.abdeslgngroup.com <br />AA #: 0003325 A <br />h <br />b <br />lu <br />F <br />0 <br />N <br />0 <br />Q <br />� <br />J <br />2 <br />b <br />W <br />L <br />W <br />® <br />V <br />V <br />LL <br />IL <br />LL' <br />UDDIV. aC LNOT: <br />SILVERDADO <br />LOT #65 <br />BLK #6 <br />PRZOdF=T#II <br />04128.002-65061 <br />MODEL: <br />4EAB <br />1672- ARIA" <br />GARAGE SWING: <br />RIGHT <br />PAGE: <br />DETAILS <br />50 MPH EXP. <br />DAN M 08/04/19 <br />SC :1/4"=1'-0" <br />ammOr <br />SN1 <br />