G/BlE - END <br />— <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-10 <br />ZONE 1 = 8.97 PSF (19.97) <br />ZONE 2 = 17.98 PSF (2798) <br />ZONE 3 = 33.53 PSF (41 3) <br />"A"=4'G" END ZONE DISTANCE <br />BASIC WIND SPEED: 15O MPH <br />WIND EXPOSURE: "B" <br />RISK CATAGORV: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT +-0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16' <br />O.S.B. OR 1/2" CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 5/8 CDX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />8d GUN NAIW LS 0 4" O.C. EDGESE 2x4 <br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE <br />END_ <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA. <br />SHANK <br />TENSILE STR. <br />SHANK <br />8d <br />RING SHANK <br />2 12" <br />0.120" <br />170,000 <br />RING <br />SCREW SHANK <br />(16-20 RINGS <br />PER INCH) <br />8d <br />SCREW SHANK <br />2 12" <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PERASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION ([SANTA) ESR-1539 <br />EXTERIOR SHEATHING <br />USE 1/2" COX OR 7116" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND 8d RING SHANK GUN NAILS4"O.C. TOP& <br />BOTTOM PANEL AND Sol RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />TOP & BOTTOM EDGES <br />J <br />zs: <br />Y Z <br />= U <br />y O <br />� <br />Q <br />Z= <br />z <br />= . <br />0 <br />m <br />Y <br />co <br />co <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />BUILDING LENGTH <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />Bd RING SHANK GUN NAILS <br />6" O.C. IN FIELD' \ <br />8d RING SHANK GUN NAILS @ 12" O.C. IN <br />FIELD or 8d x 2 12" SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 12" 0.C-1LJ <br />FIELD J\ <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TOALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMUM AGGREGATE SIZE SHALL BE 3W. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE fi%AIR ENTRAINED CONCRETE EXPOSEDTO EARTH OR WEATHER <br />NOWBEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF, <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOTSHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 6th EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3/4'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACT 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER Fb = 1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, ACT 53D-13/ASCE 5-13 AST SPECIFICATION FOR THE DESIGN OF <br />OR BARRIER MEMBRANE UNDER ALL SLABSONGROUND WHERE INDICATED ON E HYLENVAPOR <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENEVAPLED <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />DRAWINGSSEAMS LAPPED 6 INCHES WITH ADHESIVE TAPE <br />, <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 POE OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FORANV <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWIH. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACT 347, <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />"RECOMMENDED PRACTICE FOR CONCRETE FORMWORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAW NGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, 6th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUTARE BY OTHERS. <br />SYP 92. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TE-DOWMS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />20 psf TOP CHORD non -concurrent <br />10 psf BTM CHORD non -concurrent <br />DEAD LOAD <br />15 psf TOP CHORD <br />(7 psf 4 ASPHALT SHINGLES) <br />10 psf BTM CHORD <br />DEAD LOAD TO RESIST VIAND UPLIFT: 1 Opsf <br />DEAD LOAD <br />20 psf TOP CHORD <br />(10 psf w/ No GVPCRETE) <br />5 psf BTM CHORD <br />BALCONY LIVE LOAD 60 psf <br />STAIRS LIVE LOAD 40 psf <br />WELDED WIRE MESH: <br />WELDED W RE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACT <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. W RE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2" CHAIRS SPACED 3'-0" OC, EACH WAY. <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />GRADE 601N MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACT STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36' <br />#5 BAR - 30" #7 BAR - 42" <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTEN NGS° BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0. 036" AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL-PLATEGONNECTEO-WOOD TRUSS CONSTRUCTION: AND '7PI/ VTCA BCSI 1" <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METALFLATECONNECTEO <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR SEE DETAILS LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />FOR ADDITIONAL INFORMATION. INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WTH ANSI A58.1-1982. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTI NUOUS THROUGHOUT THE HEIGHT OF THE CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAW NGS FOR ALTERNATE CONNECTION DETAILS AT <br />WALL. TRUSSES/GIRDERS TO COLUMNS AND WALLS FORAPPROVAL. <br />WIND: DEAD LOAD SPEED =160 MPH 3- SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE 7-10 (FBC R2017) EXPOSURE B, RISK CATEGORY II) <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: tOpsf, UNINHABITABLE ATTIC WITHLIMITED <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 2DOpsf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: MOST,, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS' 3Gpsf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40psf <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BV A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WTI ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (ACT 530/ ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER <br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />ALL BLOCK WALLS SHALL R ACEWITH <br />MANUFACTURED IN CONFORMANCE WITH GRADE f m = 1500 PSI. BLOCK BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. W NO UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />ALL SHOP DRAWINGS SHALL U REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL G THE ARCHITECT. <br />DRAW NGS SUBMITTED WTHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAW NGS IN THE FORM <br />OF TIHALLE <br />RUNNING BOND UNLESS OhIERW SE NOTED. LAVLP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ED. LAY-UP <br />AND CLADDING W NO LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USP STRUCTURAL <br />DOCUMENTS WLL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERW SE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3I8" <br />CONNECTORS" BY USP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION <br />WITH THE SIZE AND NUMBER OF BOLTS/NAILS AS RECOMMENDED BY THE MANUFACTURER IN THE <br />TO CONSOLIDATE GROUT. <br />LATEST CATALOG. <br />FOUNDATION/ SITE PREPARATION' <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />FOOTINGS WERE DESIGNED FORAN ALLOWABLE SOIL BEARING PRESSURE OF ZOOO Psf, FOOTING <br />PROPORTIONED AND MIXED AS OUTU NED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WTH ASTM D-1557. TREATALL CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />THE OMER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANDIOR VERTICAL <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL RE13AR 6X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THATTHE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />CONCRETE: <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTON OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />A36, Fy = 36 ksi FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM A500, GRADE S, <br />Fy = 46 ksi. STRUCTURAL PIPE SHALL BE ASTM53, GRADE B, TYPE E OR S, Fy =35 W. TUBE AND PIPE <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ZODO PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB, <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5'+I- PRIORTO THE ADDITION OF PLASTICIZER <br />BE TIGHTENED IN ACCORDANCE WITH THE TURNOFF -THE -NUT METHOD. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACT 301 AND ASTM C 94 OR MEASURING, MIXING, TRANSPORTING, ETC. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />CONCRETE TICKETS SHALL BE TIME STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER 15 <br />ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES, IF FOR ANY REASONTHERE ISA <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE <br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER <br />1-112' FOR #5 AND SMALLER <br />2' FOR #6 AND URGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />314' FOR SLABS, WALLS AND JOISTS <br />1-112' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />—C-ON <br />SRE <br />TYPE <br />—NCI <br />.— <br />APPLICATION <br />S. <br />1 1. <br />SPACING <br />REMARKS <br />FT—IGTO <br />MASONRY, CONO <br />CASE NARDENEDCOIL <br />1 — LONG. <br />S.O� <br />G—EDOORSUCx <br />TO MAEONRY/CONC <br />SEE DETNL <br />GEE DETNL <br />SEE OETPoL <br />SEE DETPoL <br />x . <br />N°.. <br />9.O.G <br />STAGGERED <br />WINDow'DOOR/FASfENED <br />INTO MASONRYiCONC. <br />Y/CONC. <br />SEE DETNL <br />SEE OEraL <br />SEE DETNL <br />SEE DETNL <br />aLI11TLO <br />e•oc <br />vANDov4DooRrE Ewo <br />IwoMAsoMRncoNc. <br />—To <br />vI.— <br />CONTACT THIS ENGINEER FOR SPACING <br />REQUIREMENTS <br />PT NOTES <br />NDj3°�� <br />-SHERolsT.,, <br />to WC <br />t„2'EMBED BEND. <br />,nEocEOlsr. <br />FARING WOOD <br />rz' EXPM'90N <br />vuASRER oLr <br />2 BELGE. <br />°-O'C .. GEDGEwsr. <br />ol ENDDIST.,I t2• <br />PTT 'SEE TES .1—SHER TAGGERED EDGE pSl. <br />No <br />NOTES <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE FICA OR THE SPACING DETAILED ABOVE <br />6, W NDOW AND DOOR BUCKS SHALL BE AS WIDE OR W ERAS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SANG DOOR WITH A WOOD DOOR FRAME. IS MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/TAPCONS OR PAF TO THE SUBSTRATE. <br />11441.N . RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-7744078 <br />www abde sigrlgroup-dom <br />AA #: 0003325 <br />x <br />� <br />Cml <br />y <br />� <br />� <br />ti <br />SP <br />S <br />O <br />LL <br />Q <br />LL <br />d <br />9 <br />61 <br />d <br />aVHDIV. & LAT: <br />SILVERADO <br />LOT #22 <br />BLK. #7 <br />PROJECT* <br />04128.002-22071 <br />MODEL• <br />4EBB <br />"1828—CALI" <br />GAl2AOM 3Trng0: <br />RIGHT <br />PAGE: <br />DETAILS <br />150 MPH EXP. B <br />06/03/19 <br />/4"=1'-0 <br />SNI <br />