Laserfiche WebLink
FOR ASPHALT SHINGLE ROOF, USE MIN 7/16" STRUCTURAL <br />SHEATHING EXP 1(24116) or 1N32" STRUCTURAL SHEATHING EXP 1 <br />(32/16). FOR CEMENTITIOUS TILE AND METAL ROOFING, USE 15/32" <br />STRUCTURAL SHEATHING EXP 1 (32/16) .(SEE TABLE FOR FIELD AND <br />EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 8d RING SHANK GUN <br />NAILS 0 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' <br />OF GABLE END. <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL REQURrMENTS <br />SIZE <br />HEAD <br />LENGTH <br />DIA. <br />TENSILE STR. <br />SHANK <br />ASTM <br />Sd <br />RING SHANK, <br />2 318" <br />0113 <br />170,000 <br />RING RINGS <br />F1667 <br />SCREW SHANK <br />PER INCH) <br />RSRS-01 <br />Bd <br />RING SHANK, <br />PNEUMATIC <br />2 3/8" <br />0.113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 1/2" COX OR 7116" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT <br />4" O.C. AT PANEL SIDES AND Bd RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6" O.C. AT <br />INTERMEDIATE SUPPORTS OR 7116" ZIP SHEATHING SYSTEM <br />(INSTALLED PER MANUR SPECS.) SEE DETAIL. <br />ZONE 1: 8d NAILS @ 4" O.C. ON EDGE AND 6" O.C. IN FIELD <br />ZONE 2e, 2n, 2r: 8d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3C Sd NAILS Q 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />z <br />z pV <br />awl <br />z� <br />aaU <br />N0 <br />Z <br />A <br />Bd RING SHANK GUN NAILS @ 4" O.C. <br />TOP & BOTTOM EDGES <br />Ij <br />TYP. EXT. SHEATHING ATTACHMENT <br />a <br />vJ <br />z <br />z <br />y0 <br />904 <br />K <br />UN LNT99 <br />NW <br />Y <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />2 <br />os <br />m <br />BUILDING LENGTH <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2X4 #2 SYP OUTLOOKER RAFTER WI BLOCKING <br />16"O.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP <br />BLOCKING 0 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />C8d RING SHANK GUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT" <br />TABLE FOR FIELD SPACING ` <br />#8 2" DECK SCREWS 0 6"-B" O.C. MAX � <br />EQGES & 12" O.C. MM IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBEF <br />• • <br />• <br />�© <br />.1--L 7 <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APFLICATxN1 <br />SfE <br />TYPE <br />9PACNG <br />REMMKB <br />gPPLIGTIgJ <br />SITE <br />TTPE <br />BPACMG <br />REMAPKS <br />1. PF FURiWD iO <br />CASE NARDENEO OOX <br />GARAGE DOONBUCK <br />1IP DIA <br />TAPWNMASONRr <br />11?EMN:D., 4'EID DIBT., <br />MA901RYl CONC. <br />rUXtt?LOlq. <br />POC <br />TO MASONRYIpANC. <br />NG WASHER <br />FASTENER <br />B" <br />11?EDGE DIET. <br />SOD, AL. EXi.D0OR3 <br />1�Ri, WEE NOlEB <br />CASE XARDEAED COX <br />NAxtt?LONG. <br />POIC <br />STAGGERED <br />WINDOWB1001UFASTENEO <br />WTO MABOMYA'XNIC. <br />GARAGE DOORBUO( <br />TO MA9pNRYlCONC. <br />uY Ow. WI <br />AeHER <br />E%PANSKIN BOLT <br />31.0/O <br />4"EMBED.,YEM DIST., <br />SEDGE DLBT. <br />wlm wwm <br />CABEHARDENEDC08 <br />POIC <br />WINDOWNWWFA9TENED <br />METusTRAPro <br />CONTACT THIS ENGINEER FOR SPACING <br />ll PT, eEE NOTES <br />NAIL 11!l LONG. <br />STAGGERED <br />Nro MABornnmNc. <br />MA80NRY ICONL. <br />REQUIREMENTS <br />Exi.9WNG DOOR <br />(2)611B94A <br />TIPCON' <br />16.OK <br />11?EMBEDPEND. <br />NCNBEAWNG WOOD <br />1?' EXPAN810N 4°EMBED ♦END <br />b•OIC <br />BUCKh Pi, 9FF NOTES <br />NO-E. <br />FABR <br />DE{T.,11?EDGE 018T <br />WPLL TO CONC. BLAB. <br />WI WABNER BOLT DRT.,TEDGE OLtt. <br />h PTWSIDOINw O.1SB'PAFa]1R PYfND.OLtt.,11? <br />PT TO STEEL COL. SFE wIWASHER STAGD EDGE D•T. <br />NDTee GEOLORE <br />NoTo <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL 8E AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. Ix MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPOONS OR PAF TO THE SUBSTRATE. <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C3303M. MAXIMUMAGGREGATE SIZE SHALL BE 314'. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE B%NR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBCR 2020, 7th EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 314'. <br />ALLWOOD OR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />F <br />ACI 318-14. BUILDING CODE REQUIREMENTS <br />CRIPPLERS. SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. Fb= 11DO PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, TMS 402/602.16 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE B-MIL CONrINUWS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS -ON -GROUND WHERE INDICATED ON <br />ELASTICITY - 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016. ASCE 7-16 AND AISC SPECIFICATIONS <br />DRAWINGS. SEAMS LAPPED B INCHES AND SEALED #ITN ADHESIVE TAPE. <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN, <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />Wl DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD, <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />S. FOLLOW Y. A DISCREPANCIES SHAM B <br />DRAWING LL W WRITTEN DIMENSIONS ONLY. ANYL E BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020 781 EDITION, SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALOEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2' <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTORS RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE-DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A1064/A1084M, GRADE 85 AND BE PLACED IN ACCORDANCE WITH THE <br />WOOD TRUSSES' <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WITH Y CHAIRS SPACED 3'G' OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED 13Y A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS, THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A615AS15M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />MEETING THE REQUIREMENTS OF ASTM A446/A448M, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL SENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-ib, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION, HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND 'SCSI LATEST EDITION' <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 pat TOP CHORD-nortconwrr•14 <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - " #6 BAR - <br />WOOD TRUSSES. <br />10 psf BTM CHORD -n wnarteM <br />3042" <br />Ki BAR - Bn BAR - 4Y <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 38' x 38' CORNER BARS, BOND BEAM ONLY, LAPPED AND <br />ND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSUASCE 7 88: 1990. <br />15 pal TOP CHORD p. TOP CHORD <br />(7 PSTWI ASPHALT SHINGLES) (1 No GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS. <br />6 P t Sw/ <br />10 f BTM CHORD 6 BTM CHORD <br />Ps Mf <br />THICKENED SLAB BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: tOpst <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 PV <br />WALL, <br />TRUSSES/GADERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 PIT <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />WIND: DEAD LOAD FBCSPER20150 MPH 3-SECOND GUST <br />EXPOSURE B, RISK CATEGORY II) <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LIVE(NICE BIT BLE ATTIC UNINHABITABLE ATTIC WITH LIMITED <br />LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />WITH <br />STORAGE: 20p3T, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30ps1. BALCONIES (EXTERIOR) <br />STORAGE: <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40pnf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30pBf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40pef <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402. BUILDING CODE REQUIREMENTS FOR MASONRY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED By <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT, <br />MANUFACTURED IN CONFORMANCE WITH ASTM G90, GRADE ftn = 2000 PSI. BLOCK SMALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER, WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />pLAACING CONCRETE FOR IN -WALL COLUMNS. GROUT UeED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM 0476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS. UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318" <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8-TO 10". USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 Pef, FOOTING <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE <br />SHALL BE 3/8' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557, TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />CELLS TO BE FILLED. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEERS REQUIREMENTS SMALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE UX PRIOR TO <br />CONCRETE RACEME#. CONCRETE SLUMP SMALL NOT EXCEED V 4. PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SMALL COMPLY WITH ALL THE REQUIRBMENTS OF ACI 318 AND ASTM CS4C94M ORMEASUWNG, MIXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SWILL BE AS FOLLOWS: <br />A 3- FOR DONCREM CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATIM): <br />B. FOR CONCRETE EXPOSED TO EARTH ANDIORWEATHER: <br />14f' FOR O AND SMALLHL <br />Y FOR #8 AND URGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />31C FOR BUGS, WALLS AND JOISTS <br />1-III FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TES, STIRRUPS <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR B X BAR NO. (48 BAR DIAMETERS)., U.N.O <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />BTH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36IA36M, Fy = 36 ksl FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A6D0/ASOOM, GRADE 8, Fy = 46 ksl. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S. Fy = <br />35 ksl. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING, ALL <br />OTHER BOLTS SHALL BE ASTM F3126IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SMALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />A R c II I T I C T i <br />GroupI�. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-7744078 <br />www.abdeWgngroup.eom <br />AA #: 0003325 <br />DRAFTING BY: <br />A.B. DESIGN GROUP <br />DRAFTING INC. <br />5439 BEAUMONT CENTER BLVD. <br />SUITE 1004 <br />TAMPA, FLORIDA 33634 <br />PH: 813888-2828 010 <br />FAX: 813888-2802 <br />