Laserfiche WebLink
A <br />A <br />GABLE -ENO <br />HPRCOF iI-�F <br />ROOF WIND DESIGN PRESSURES <br />N T ASCE 7-1 <br />ZONE 1 = 8.97 PSF (19.97) <br />ZONE 2 = 17.98 PSF (27.98) <br />ZONE 3 = 33.53 PSF (43.53) <br />"A"= 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE: "B" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT *-0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7116' <br />O.S.B. OR 1/2" CDX EXT, PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 5/8 COX EXT. PLYWOOD, WITH Sd RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS, SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />Bd GUN NAILS 0 4" O.C. EDGEWISE 20 <br />BLOCKING ALL PANEL JOINTS W/ IN W OF GABLE <br />FNn <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN.LENGTH <br />MIN.DIA <br />SHANK <br />TENSILESTR. <br />SHANK <br />8d <br />RING SHANK <br />2 1/2" <br />0.120" <br />170,000 <br />RING <br />(16-20 NGS <br />SCREW SHAM( <br />PER NCIH) <br />8d <br />SCREW SHANK <br />2 11T <br />0.1201 <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />o:TeRlo:t SH EOkTHINO <br />USE 1/2' COX OR 7116" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT W O.C. AT INTERMEDIATE SUPPORTS <br />OR 7116" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />TOP 8 BOTTOM EDGES <br />z <br />W <br />Z <br />= U <br />O <br />J <br />A <br />2 <br />AJ <br />y y <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />RAF ER OR TRUSS <br />---_� <br />I.___ -I' _1 <br />ROOF SHEATHING LAYOUT <br />ANO ENDWALL BRACING <br />FOR GABLE BND FRAMING <br />J <br />Z W <br />z8 l/ <br />� Ld C 8d RING SHANK GUN NAILS <br />Z LT 6" O.C. INFIELD' <br />0 J\ <br />a <br />GO <br />TYP. EXT. SHEATHING ATTACHMENT FOR ROOF SHEATHING(O.S.S. <br />? TO BE STRUCTURAL GRADE <br />LU <br />U¢ <br />L) 8d RING SHANK GUN NAILS 012" O.C. IN <br />Q U FIELD or 8d x 2 1/2" SCREW SHANK <br />wO PNEUMATIC SCREW -NAILS 0170.0.-1�1 <br />ro FIELD J\ <br />z <br />TYP. 3/4' T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ROOF SHEATHING LAYOUT <br />ANO ENDWALL BRACING <br />FOR GABLE BND FRAMING <br />J <br />Z W <br />z8 l/ <br />� Ld C 8d RING SHANK GUN NAILS <br />Z LT 6" O.C. INFIELD' <br />0 J\ <br />a <br />GO <br />TYP. EXT. SHEATHING ATTACHMENT FOR ROOF SHEATHING(O.S.S. <br />? TO BE STRUCTURAL GRADE <br />LU <br />U¢ <br />L) 8d RING SHANK GUN NAILS 012" O.C. IN <br />Q U FIELD or 8d x 2 1/2" SCREW SHANK <br />wO PNEUMATIC SCREW -NAILS 0170.0.-1�1 <br />ro FIELD J\ <br />z <br />TYP. 3/4' T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33 MAXIMUM AGGREGATE SIZE SHALL BE 3W. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSUL? <br />pROVDE 876 AIR ENTRAINED CONCRETE BP0.9BO TO EARTH OR WFATHt9t <br />WOOD. <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVE S,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBCR 2017. Stn EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CFNMFBT®3/d'. <br />ALL WOOD FOR SEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 31844, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER Fb - 1100 PSI ANDA MODULUS OF <br />FOR STRUCTURAL CONCRETE, ACI 530-131ASCE 5.13 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SA IADWFBEIMICAT®ON <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />DRAWINGS. SEAMS LAPPED 61NCHES MID SEALED WiTHAOFE5IVETAPE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTIRAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE TNTBE TYPICAL A ND <br />FORMWORK: <br />SHALL BE RATEDTO RETENTION <br />CORROBORATETETTRAHEDRAL (DOT). MOD FOR STRUCTURAL USE LS OF 0.25 PCF OF A BORATE THATHIAPRESERVATIVE S SHALL BE TREATED FORANY <br />E ON THE PROJECT, <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMY4S, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 POP FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWM. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH AG 347, <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FORCONCRETE PORM-VARK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD, DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER PBR 2017, 6th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2. STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH' <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />WELDED WIRE MESH, SHALL BE ASTM A186, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS, <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />WOOD �S' <br />SUPPORTED WITH 2' CHAIRS SPACED T-O' OC, EACH WAY. <br />TOE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE "NATIONAL DESIGN FOR <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />BE SATEEN A <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' SHALL SIGNED AND <br />NFPA. TRUSS DESIGNS SHALL <br />REQUIREMENTS AND SLABOWGRADE THICKNESS TO HANDLE CONSTRUCTDN LOADS. <br />E ED I O <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA, SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SMALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS REBAR SHALL BE ASTM A618 <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATIOK HORIZONTAL <br />STANDARDS FOR METAL-PLATEOONNECTED-WOOD TRUSS CONSTRUCTION:, AND 'TPI/WTCA BCS1 V <br />ROOF: LIVE LOAD FLOOR LIVE LOAD 40 <br />ANDVERTCAL BARS SHALL LAP 6 x SAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />pst <br />20 per TOP CHORD -noncondmanl <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />WOOD TRUSSES. <br />10 pot BTM CHORD a orconw nt <br />#5 BAR - 30" #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36"x 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982. <br />16 psf TOP CHORD 20 psf TOP CHORD <br />(7 psf W/ ASPHALT SHINGLES) (10 psf vs' No GYPRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS. <br />10 psf BTM CHORD 5 psf STM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: IOps1 <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 pef <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD SPEED MPH GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />01B6 <br />SURE END <br />(MICE (FBCATTIC EXPOSURE B. RISK CATEGORY IU <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY 8 ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />BIT LIMBED <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: ATTIC <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />WITHIOPBtFIXED 3 ALCWIT <br />STORAGE: 20pei, HABRABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30pe1, BALCONIES (EXTERIOR) <br />HABITABLE STAIRS: <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIEDTO THE <br />AND DECKS: dOpsi, GUARDS AND HIANCRAILS: 200ps1, GUARD IN•FILL COMPONENTS: 50pef, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE R TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psL ROOMS OTHER THAN SLEEPING ROOM: 40pef, SLEEPING ROOMS: 30pef, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40pef <br />MASONRY" <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAIAIING M)EW: <br />"SPECIFICATION MASONRY STRUCTURES" (ACI 530/ ASCE SRMS 402. BUILDING CODE REQUIREMENTS FOR <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIESM AS <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC' <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEOR THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C410, GRADE t1n = 1500 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES, THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS, <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />ID WITH <br />PLACING CONCRETE FOR tN-WALL COLUMNS. ROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER, IN ALL INSTANCES, THE CONTRACT <br />MI STRENGTH <br />ASTM C-478, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, <br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USA STRUCTURAL <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />FOUNDATION PLAN. THE OUT MIX SHALL HAVE A MAXIMUM 3S" <br />SPECIFICALLY NOTED OTHERWISE E <br />CONNECTORS" BY USP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS <br />WRITING BY THE ARCHITECT <br />COURSE AGGREGATE, AND SWILL BE PLACED VV/ A SLUMP OF TO 10'. USE ONLY MECHANICAL VIBRATION <br />WITH THE SIZE AND NUMBER OF BOLTS/NAILS AS RECOMMENDED BY THE MANUFACTURER IN THE <br />TO CONSOLIDATE GROUT. <br />LATEST CATALOG. <br />FOUNDATIOW SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D1557. TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RECOMPACTED AND RETESTEDAT THE <br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GE04ECH. ENGINEER <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLABONORADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB <br />CONTRACTOR SHALL SUBMIT PROPOSED TAX DESIGNS WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRORTO <br />CONCRETE PLACEMENT CONCRETE BLIMP SHALL NOT EXCEED 5' N-PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C84 OR MEASURING, MIXING, TRANSPORTING, ETC <br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCH®. THE MAXIMUM TIME ALLOWED FROM W1SN WATER IS <br />ADDED TO THE MX UNTIL IT IS DEPOSTED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES IF FOR ANY REASON THEE IS <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE <br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLIANCE WITH THEAB0IE <br />REQUIRED CONCRETE COVERAGE OVER R MAR SAL BE AS FOLLOWS <br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY SPOSEDTO EARTH (FOUNDATIONS) <br />B FOR CONCRETE EXPOSED TO FAITH AMDRWEATHER <br />14ri-FOR #5 AND SMMISR <br />2*FOR A AND LARCEt <br />C. FOR CONCRETE NOT DPOSED TO WEATHER <br />314. FOR STABS WALLS AND JOISTS <br />1.1R' FR BEAM AND COLUMN PRIMARY REINFORLEMIENT, TIES, STIRRUPS <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C470. HORIZONTAL AND VERTICAL MORTARJOINTS <br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS ANDIOR VERTICAL <br />REINFORCING, <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS}, U.N.O <br />STRUCTURAL STEEL <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL SE ASTM <br />ASS, Fy = 36 ksl FORANGLES, PLATES, AND WSHAPES, STRUCTURAL TUBING SWILL BE ASTMA500, GRADE S. <br />Fy = 46 ksl. STRUCTURAL PIPE SHALL BE ASTM 83, GRADE B, TYPE E OR S. Py = 35 kel. TUBE AND PIPE <br />COLUMNS SHALL BE 00 NCRETE-FILLE D IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL 8E ASTM A307 BOLTS WITH DOUBLE-NLJT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS' WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE T1JRN-0FF-THE-NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JAOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />APPLIGRON <br />I Siff <br />TYPE <br />BPAdNG <br />RENNPlO <br />AR•UGTION <br />.1ff <br />1 TYPE <br />SPACING <br />REAUwCi <br />1 TR)RRNGTO <br />-CON. <br />CASE IMROENED COL <br />WALL 11?LONG. <br />a Q'L <br />GMAGEDOORB'JCx <br />T01M90N2Y/ANC. <br />1"" <br />NO.GN. <br />TAPCON IAO90lAY <br />FASTENER <br />8 0p <br />11?EMBED.,PEW DUST., <br />11R"EDGE GIST. <br />B., A. FXT DOORS <br />CASE HARDENED COL <br />S"dC <br />WNDOWIDOQRIPASTENEO <br />GRADE DOIX2 EUCK <br />IT DW WI <br />1WA9HEA <br />E%PANSICNBOLT <br />3YOC <br />VE19ED., 3• EIDOIBT, <br />1x PT.SEENOTE. <br />NAL 11?LONG. <br />STAGGERED <br />IRO AWx)NRYICONC. <br />TOAwYJMwWNC. <br />3"EDGE DW <br />wN00w BUm <br />roc <br />wNODWDCOR/FA31H1EO <br />NETAL STwwTO <br />CONTACT THIS ENGINEER <br />FOR SPACING <br />tx PT, SEE NOTE. <br />CASE HARDENED GOL <br />NNLI I. -LONG. <br />STAGGERED <br />IN�MAsoNRYIcoNC <br />MASONRY ICorIC. <br />REQUIREMENTS <br />EXT. SANG DOOR <br />(2)3MBTJw. <br />RAPCO' <br />180.0 <br />11?EMBEO,rENT. <br />W -B-NG WOOD <br />1? EJPAN3KKJ R1" <br />K'EMBED.A•EN) <br />BUCK 2x M, BEE NOTES <br />NO-ER <br />F.TNER <br />DISi., 1EOGEDWT. <br />NIW CONC.9LAB <br />WIWABNm BOLT <br />DUST., 3'EDGED6T. <br />2x Pr WINDOWBUCK 0.130°PAF x21Ri" .'QY: A"ENO. DISi.if? <br />PT TO BN EL OG_,8EE WI WASHER STAGGERED EOOE OMIT <br />GTE. <br />I"S..!!d <br />i. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / R NCA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILT] X-ZF HEAVY DUTY PINS R EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR ORWINDOW FRAME EXPECT FORAN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NMLEDAND <br />2. MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-7744078 <br />FAX: 407-7744078 <br />www.abdesigngroup.com <br />AA 6: 000332E <br />8 <br />all <br />t <br />• <br />5811 <br />L <br />O <br />S <br />1 <br />sV3DIV. A6 LOT? <br />SILVERADO <br />LOT #4 <br />BLK. #18 <br />PROSWT <br />04128.001-04181 <br />MODEEA <br />4EBB <br />"1828-CAU" <br />GARAOR OWUM: <br />RIGHT <br />PAOr. <br />DETAILS <br />150 MPH EXP. B <br />STATE OF FLOF DA <br />DC 0 <br />J <br />AR AABE000 CR <br />aA Ek 12/03/19 <br />IICAL .1/4"=1'.-0" <br />S N1 <br />