HVAC NOTES <br />A 0 p u I v a p 7 a <br />L ALL MECHANICAL EQUIPMENT SWAILL. BE PROVIDED WT14 PROPER CLEARANCE, FOR SERVICING, PER <br />MFG.REQUIREMENTS. <br />2. ALL DUCT SYSTEMS INSTALLED IN NON -CONDITIONED AREAS SHALL, BE CONSTRUCTED OF A VALUE <br />OF NO LESS THEN R-6 RATING. ALL SEAMS SHALL BE SEALED WITH GLASS FAD 4 MASTIC. AND <br />INSTALLED AS PER FBC 6TH EDITION (2011) MECHANICAL BLOC. CODE SECTION 603. <br />3. ALL FLEX DUCTS SHALL BE APPROVED UL 181 CLASS I AIR DUCT AS PER NFPA WA 2-31 <br />4. FRESH AIR INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FT. FROM ANY CHIMNEY OR VENT <br />OUTLET, OR SANITARY SEWER VENT OUTLET <br />5. ALL EXHAUST AND OUTSIDE AIR INLET DUCTS, SHALL BE CONSTRUCTED OF SMOOTH GALV. METAL. <br />OR OTHER MATERIALS AS PER FBC 6TH EDITION (2011) MECHANICAL GORE SECTION 603 <br />6. ENCLOSED SUPPORT PLATFORMS SHALL BE CONSTRUCTED IN ACCORDANCE TO FDC (PTH EDITION <br />120PT) MECHANICAL CODE 6031 <br />1. BATHROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR BATHING FIXTURES SHALL BE <br />MECHANICALLY VENTED IN ACCORDANCE WITH FBC 6TH EDITION (20I1) MECHANICAL CODE SECTION <br />403. <br />S. ALL EXHAUSTED BATH ROOMS, SHALL HAVE UNDER -CUT DOORS FOR MAKE-UP AIR TO BE <br />RETURNED, TO EQUAL AIR EXHAUSTED. <br />9. ALL FIRE RATED CEILINGS AND WALLS SHA"L. HAVE AN APPROVED FIRE OR FIRE/SMOKE <br />DAMPER'S LOCATED AT CEILING OR WALL PENETRATION AND BE SLEEVED WITH ACCESS DOORS TO <br />RESET DAMPER ALL DAMPERS SHALL BE INSTALLED TO MFG. RECOMMENDATIONS AND FBC 6TH <br />EDITION (2011) MECHANICAL CODE SECTION 601. <br />10. GRILLES AND DFFUSERS SHALL BE PROVIDED WITH BALANCING DAMPERS. <br />II. DRYER BOOSTER TO BE A FANTECH DBF BOOSTER FAN OR EQUAL. <br />PANTEC 4 DBF 110 DRYER BOOSTER CAPACITY 60 LINEAR FEET WITH MAX. SIX ELBOWS. <br />NOTE <br />ALL HVAC TO HAVE PROPER <br />PANS W/ DRAINS <br />ATTIC <br />GEILMCs <br />O O <br />EXTERIOR WALL <br />PLENUMX <br />AIR RETURN <br />ON AND LIQUID <br />AIR SUPPLYGERANT <br />LINES <br />AIR HANDLERIOR <br />WALL <br />VC CONDENSATE DRAIN LINE <br />EVAP. TRAYLEEVE <br />TO LINES BELOW SLAB <br />REFRIGERANT LINES TO <br />ILATFOIaI'1CONDENSING <br />UNIT <br />TRAP DRAIN LINE AND TERMINATE <br />IN AN APROVED DRAIN, AS PER <br />FSCR 6TH EDITION (2011) <br />MECHANICAL BLDG. CODE <br />SECTION 3013A <br />HVAC <br />DRAINS <br />SCORIATED NICKEL FIN, FLOOR <br />BRONZE FL. PL OR WALL <br />FITTING OR EXTENSION TO <br />SOIL OR WASTE AS <br />REQUIRED <br />WADE 8240-K "AM 560M <br />INSIDE SERIES NICKEL BRASS TOP <br />CAULK P.V.0 OPTI/SPEC <br />LEGEND <br />® <br />SUPPLY AIR DIFFUSER <br />RETURN AIR GRILL <br />® <br />SIDE -WALL OR 1 WAY DPUSER <br />— <br />SOLID LINE- SUPPLY TRLNK <br />BROKEN LINE- RETURN TRIA K <br />1 <br />BALANCING DAMPER OR OBD <br />O <br />CEILING EXHAUST FAN <br />CEILING EXHAUST FAN 4 LIGHT <br />O/A <br />OUTSIDE AIR <br />® <br />THERMOSTAT <br />N9 <br />PASS-TWMJ AIR GRILL <br />SECURE STRAP TO CONG.CIONDENWR <br />W/ (2)-3/16'X2' TAPCONS UNIT SIMPSON LLB ROLL STRAP <br />OR EQUAL <br />4 <br />4' CONCRETE SLAB SECURE STRAP TO UNIT W/ (2) <br />'SXI V4' SHT. N1TL.. SCREWS <br />CONDENSER UNIT <br />CONNECTION TO PAD <br />NOTE: MAIN COND. DRAIN 3/4' DIA. <br />OVER HEAD • 12' FROM STRUCTURE <br />COUNTERSUNK <br />CA. PLUG <br />FIN. GRADE <br />OR PAVING <br />SEE SPEC. <br />1'-8'XS' CONIC. <br />FITTING OR <br />EXTENSION TO SOIL <br />OR WASTE AS <br />REQUIRED <br />nEXT. GROUND CLEAN -OUT (TYP. <br />vFLOOR SLAB CLEAN -OUT (T� ti N <br />MECHANICAL PLAN <br />SCALE, 1/4 " 1'-0' <br />rou"O G <br />L441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-7748078 <br />FAX: 407-7744078 <br />wwwabdesigngroupcom <br />AA A: 0003325 <br />R <br />M <br />q <br />t <br />a <br />0 <br />a <br />O <br />V <br />sysDiv ae roT <br />SILVERADO <br />LOT #2 <br />BLK #18 <br />PROJECT# <br />03719.000-02182 <br />acGnEL <br />"2045-LANTANA" <br />GARAGE 81WI dG: <br />LEFT <br />PAGE: <br />MECHANICAL <br />PLAN <br />150 MPH EXP. B <br />11 <br />[a*=] <br />RINT 8/03/20 <br />DATE: <br />CALF. 1/4"=1'-0" <br />CT <br />M1 <br />