q <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN V16" <br />O.S.B. OR 1/2"CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 5/8 COX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. <br />S SEE <br />DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE <br />Ed GUN NAILS @ 4- O.C. EDGEWISE 2X4 <br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE <br />END. <br />GAEIE-END ��� <br />xv BaoF il`—>t' <br />ROOF WIND DESIGN PRESSURES <br />1 <br />ZONE 1 = 20.97 PSF (30.97) <br />ZONE 2 = 35.67 PSF (45.67) <br />ZONE 3 = 61 DS PSF (71.06) <br />"A'= 4'-0' END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE:'Bl <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT+- 0.18 <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 6th EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, ACI 530-13IASCE 5-13 Ai91 SPECIFICATION FOR THE DESIGN OF <br />COLD.FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />TO ASTMC33. MAXIMANAGGiEG1TE SIZE SHALL BE 3W". <br />EXPOSED TO EARTH OR WEATHER <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3W . <br />PROVIDE 64AIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALI NABS*NGROUMD WHERE INDICATED ON <br />DRAWINGS. SEAMS LAPPED 6 INCHES AND SEALED WITH ADHESIVE TAPE <br />FORMWORK <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />WOOD: <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. FO = 1100 PSI AND A MODULUS OF <br />ELASTICITY - 1,400.000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED, WOOD FOR NON-STRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 025 POF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />EXCLUSIONS FRAM THESE PLANS- MINIMUM NAILING PER FBCR 2017, 69T EDITION. SEE NAILING SCHEDULE ON PLANS. <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DPROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2, STRUCTURAL LUMBER <br />EPENDING SYPVI <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />-WALL GROUT USED TO FILL MASONRY E <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />WELDED �� <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />TEMPORARY BRACING, GUYS OR TIE-DOWMS. <br />WELDED WIRE MESH, SMALL HE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />WOW TRUSSES' <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />SUPPORTED WITH 2' CHAIRS SPACED TO- OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE WATIONAL DESIGN SPECIFICATIONS FOR <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL- <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A615 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SWILL BE ASTM A615 <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED. <br />GRADE 60IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, -DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION% AND 'TPUWTCA BCSI 1' <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 { <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL-PLATE-CONNECTEDPs <br />20 ps{ TOP CHORD �IDOmnaureM <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25' aN BAR. - 38' <br />WOOD TRUSSES. <br />10 pot BTM CHORD -rarvcona rg <br />95 BAR - 30" #7 BAR - 42" <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36" x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS. CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982. <br />15 psf TOP CHORD 20 psf TOP CHORD <br />17 ASPHALT SHINGLES) psf wl No GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL HE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 PSTSTM CHORD 5 5 paf BTM CHORD <br />PP <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opsf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 Ps1 <br />WALL' <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />WIND! DEAD LOAD SPEED MPH GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE (FBC 017) SUE B. RI <br />EXPOSURE B. RISK CATEGORY ILA <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: tO <br />BIT ATTIC UNINHABITABLE ATTIC WITH LIMBED <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING, ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />IT <br />STORAGE: 20paf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED i0 THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200ps/, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf. SLEEPING ROOMS: 30W. STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40ps{ <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHGP DRAWING RENEW: <br />'SPECIFICATION MASONRY STRUCTURES- (ACI S30/ ASCE 5ZTMS 402, BUILDING CODE REQUIREMENTS FOR <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PROVIDED BY THE TRUSS ENGINEER, <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC, <br />ALL BLOCK WALLS SHALL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED THE CONTRACTORS PRIOR SUP TO THE ARCHITECT. <br />R ONCE WITH GRADE Dn = 1500 PSI. BLOCK SHALL PLACED USING <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90LAY-UP <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT <br />WILL . S <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />DRAWL <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />B <br />PLACING CONCRETE FOR IN COLUMNS <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED C LLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES. THE CONTRACT ASTM G476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL RAVE A MAXIMUM 31W <br />ROOF/ WALL/ FLOOR WRITING BY THE ARCHITECT. COURSE AGGREGATE. AND SHALL BE PLACED W/ A SLUMP OF 8' TO 10". USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />SHEATHING FOUNDATIOW SITE PREPARATION: TYPE 'M'OR'S"MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />FASTENER SCHEDULE EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA. <br />SHANK <br />TENSILE STR. <br />SHANK <br />8d <br />RING SHANK, <br />2 12" <br />0.120" <br />170,000 <br />RING <br />SCREW SHANK <br />1B RINGS <br />ER INCH) <br />Ed <br />SCREW SHANK <br />21/2" <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 TOP CORD BLOCKING AT 4' <br />2. INTERNATIONAL STAPE, NAIL &TOOL O.C. MAX: IN FIRST 2 FRAMING <br />ASSOCIATION (ISANTA) ESR-1539 SPACES AT EACH END. <br />RAFTER OR TRUSS—` <br />ROOF SHEATHING — <br />EXTERIOR SHEATHING <br />USE 12" CDX OR 7/16" O.S.B. PLY WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND Ed RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />., TOP & BOTTOM EDGES .. <br />J <br />J <br />Q <br />Q <br />Z W <br />Z Q . <br />Z <br />O <br />O W <br />O C, <br />Z ? <br />Z <br />Q0 <br />O <br />mO Z <br />cO <br />z o <br />m :D <br />Z <br />� <br />E <br />m <br />Z <br />= <br />O <br />0 <br />- m <br />Tfm <br />Z <br />9� <br />m <br />p BUILDING LENGTH <br />x <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />C8d RING SHANK GUN NAILS . <br />R 6" O.C. IN FIELD <br />TYP. EXT. S I ATTA H E F R OOF gHirTHING (O. .B. <br />TO BE STRUCTURAL GRADE <br />CSd RING SHANK GUN NAILS R IT O.C. IN <br />FIELD or 8d x 2 12" SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 12-0.6.)N <br />FIELD J\ <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIORTO <br />CONCRETE PLACEMIENT. CONCRETE SLUMP SHALL NOT EXCEED Y N- PRIOR TO THEADDRION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTMC 940R MEASURING, MXINQ TRANSPORDNG, ETC <br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS <br />ADDED TO THE MIX UNTIL IT IS DEPOSITED N ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES. IF FOR ANY REASON THERE IS A <br />DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE <br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON <br />COMPLWNCE WITH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A TFOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER <br />1.12' FOR 05 AND SMALLER <br />P FOR #B AND URGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />314' FOR SLABS, WALLS AND JGSTS <br />1-irr FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FILL CMU CELLS SOLID WITH GROUT AT AL CELLS TO RECEIVE N L CE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, STRUCTURAL STEEL SHALL BE ASTM <br />A36, Fy = 36 ksl FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B <br />Fy = 46 ksl. STRUCTURAL PIPE SHALL BE ASTMb3, GRADE B, TYPE E OR S, Fy = 35 ksi. TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURNOFF-THE-NUF METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JSOLTS ARE TO BE STEEL, <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APRIGTION <br />5� <br />1YPE <br />SPACING <br />REAIARtS <br />A➢R1CATgN <br />SP£ <br />twE <br />PACING <br />gFMAPo(3 <br />MM1BONRYICONG. <br />C 9E NANDENFD C04 <br />NAK 11?LONG. <br />S• <br />GNtAGE DODRBUCI( <br />TO MABONRYICOND. <br />N'DM <br />NDWASHE0. <br />?EMBED.. r EN0 DI3T., <br />11?EDGE DBT. <br />GD AL. EXi. DOOR4 <br />+. ar. sEE NDTEs <br />CA9E HARDENED COx <br />NAA>>?LONG. <br />YaG <br />sTAGGFIe:D <br />wNWW/DOOM FASlENE9 <br />wro MAsoNwnxwc. <br />GARAGE UOdi BU41( <br />roMA30NRrIDGNG. <br />IA w� <br />DEB <br />EWM19aNBOLT <br />]r ac <br />rEMBED •06T. <br />.6T <br />wwDow suDx <br />CASE HARDENED COL <br />rac <br />wwoowrooa+i rASTENEo <br />Tu smAP To <br />CONTACT THIS ENGINEER FOR SPACING <br />. Pr, SEE NOTES <br />NMLt uz care. <br />sTaasERED <br />e.TO MA90N2rIWHG. <br />MAsaHRricaNc. <br />REQUIREMENTS <br />Exr.swsuG DooRl <br />aisvu. <br />�e ac <br />?EMBEorsro. <br />sx;waaD <br />ExPANsx»r zrac ,rEorE oaT. <br />v PTwwoowsuac iE Axe? A oc rENo o�sT.l �? <br />m ro STEELGa.,3EE BIW/WASHER ST GGER® EDGE DIET. <br />NDTE6 <br />I STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4, PAF SHALL BE NLTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EJECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />A R C N I T R C T S <br />6 <br />Grou►n <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL32750 <br />PH: 407-774-WIS <br />FAX: 407-774-4078 <br />wwwmbdesigngroup.com <br />L AA 4: 0003325 A <br />4 6 <br />V <br />y <br />Y <br />O <br />N-. <br />M <br />�e <br />C <br />Stmmv. ac LOT: <br />SILVERADO <br />LOT #1 <br />BLK #18 <br />PROTECT# <br />03719.000-01182 <br />MODEL: <br />°2045-LANTANA" <br />GARAGE 931r1TG: <br />LEFT <br />PAGE: <br />DETAILS <br />150 MPH EXP. B <br />