FOR ASPHALT SHINGLE ROOF, USE MIN 7116" STRUCTURAL
<br />SHEATHING EXP 1(24/16) or 15132" STRUCTURAL SHEATHING EXP 1
<br />(32116). FOR CEMENTITIOUS TILE AND METAL ROOFING, USE 15/32"
<br />STRUCTURAL SHEATHING EXP 1 (32/16) .(SEE TABLE FOR FIELD AND
<br />EDGE SPACING) SEE DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE 8d RING SHANK GUN
<br />NAILS@4"O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/IN 4'
<br />OF GABLE END.
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL REQUIREMENTS
<br />SIZE
<br />HEAD
<br />LENGTH
<br />DIA.
<br />TENSILE STR.
<br />SHANK
<br />ASTM
<br />8d
<br />RING SHANK,
<br />2 318"
<br />0.113
<br />170,000
<br />ING
<br />16-20 RINGS
<br />F1667
<br />RSRS-01
<br />SCREW SHANK
<br />ER INCH)
<br />8d
<br />RING SHANK,
<br />PNEUMATIC
<br />23/8"
<br />0,113
<br />F1667
<br />SCREW -NAILS
<br />RSRS-01
<br />EXTERIOR SHEATHING
<br />USE 1/2" CDX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT
<br />4" O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND Bd RING SHANK GUN NAILS AT 6" O.C. AT
<br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM
<br />(INSTALLED PER MANUF. SPECS.) SEE DETAIL.
<br />ROOF SHEATHING ATTACHEMFM SPACING
<br />ZONE 1: 8d NAILS @ 4" O.C. ON EDGE AND 6" O.C. IN FIELD
<br />ZONE 2B, 2n, 2r: Bd NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />ZONE 3,3e, 3r: Sd NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />8d RING SHANK GUN NAILS Q 4" O.C.
<br />TOP & BOTTOM EDGES ,.
<br />�1
<br />Qom_Q
<br />ZN
<br />w
<br />�w
<br />z
<br />$O
<br />z
<br />K
<br />N
<br />v
<br />ULL
<br />N �
<br />Y
<br />wC
<br />❑ C
<br />ti
<br />1 N
<br />TYP. EXT. SHEATHING ATTACHMENT
<br />..
<br />GABLE -END
<br />HIP ROOF
<br />RAFTER OR TRUSS
<br />ROOF SHEATHING
<br />2 ti
<br />0 0
<br />3
<br />m
<br />BUILDING LENGTH
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />NOTE: GABLES -DROP GABLE END & (1) ADO'L DROPPED
<br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING
<br />1611O.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP
<br />BLOCKING Q 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA.
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/
<br />BLOCKING PER NAILING SCHEDULE
<br />8d RING SHANK GUN NAILS
<br />SEE "ROOF SHEATHING ATTACHMENT"
<br />TABLE FOR FIELD SPACING `
<br />C#8 2" DECK SCREWS @ 6%8" O.C. MAX Q
<br />EDGES & 12" O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />IGTKN
<br />S.
<br />TYPE
<br />SPACING
<br />REMAAIS
<br />APIKATION
<br />SIZE
<br />I TYPE
<br />I
<br />IRENMiM3
<br />t#PTFUPFNtlGTO
<br />DASENARDENEDCOIL
<br />9O�
<br />GAPAGEDOORBUCK
<br />1I4•DW.
<br />TAPCONMA90NRY
<br />G"aC
<br />Il-EMBED., 4' END DIST.,
<br />MA90NRYIGONG.
<br />NAIL IO"LONG.
<br />TO MASONRYICONC.
<br />NO WASHER
<br />FASTENER
<br />1-EDGEDIST.
<br />9G0, Al. EXT, DOOPS
<br />CASE HARDENED COl
<br />a C,O
<br />WINOOIlNOO1L FASTENED
<br />GARAGE GOORB
<br />1Yf ON.WI
<br />EXPANSION BOLT
<br />G4.O/C
<br />4• EM9E0., 4• END MT.,
<br />PT,9EENOTE3
<br />11?LONG.
<br />9T AGGERED
<br />AIASON-CONC.
<br />90NRYICONC.
<br />WASHER
<br />SEDGE DST.
<br />wMDOW&IDK
<br />CASE HARDENED COIL
<br />a'OIC
<br />WNDOWIDOON FASTENED
<br />METAL BTHAP To
<br />CONTACT THIS ENGINEER FOR SPACING
<br />1N PT, SEE NOTES
<br />NAILF IR'LONG.
<br />STAGGERED
<br />INTO MAAONtY-0
<br />MASONRY I CONC.
<br />REQUIREMENTS
<br />EXT. SWING DOOR
<br />SVCX 3a FT, SEE NOTES
<br />11L199'A
<br />WASHER
<br />TAPCON
<br />FASTNER
<br />18 Orc
<br />t— EA@ED. WEND.
<br />DST., I -EDGE DIET.
<br />NON BEARING WOOD
<br />WKLTO CONC.SVB
<br />tM FJIPANSgN 24,E 4"EMBED.I•EtW
<br />WI WASHER BOLT DST.,S EDGE DST.
<br />h PT WINDOW BUG% 0.1SS•PAFx]1B' SOIC 4" END, DIST., 1117'
<br />PT T09TEEL COL., SEE WI WASHER STAGGERED EDGE 0I..
<br />NOTE B
<br />NOTES
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILT] X-ZF HEAVYDUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS'MOE OR WIDER AS THE DOOR OR WfNOOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1A MEMBERS ARE NAILED AND
<br />2X MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />GENERAL NOTES:
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBGR 2020 781 EDITION
<br />ACI 318-14 BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE TMS 402/6 2-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />U 0
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2018, ASCE 7-18 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK,
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORMTOASTMC3113W MAXIMUM AGGREGATE SIZE SHALL BE 3I4•,
<br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 311
<br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS-0NGROUNO INDICATED
<br />YLE WHERE NDIC TIED ON
<br />DRAWINGS. SEAMS LAPPED 6INCHES AND SEALED WITH ADHESIVE TAPE.
<br />FORM -WORK -
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST
<br />EDITION,•RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />WOOD:
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF
<br />ALL WOOD FOR BEAMS BEARING WALLS SOLE PLATES TOP PLATES BRACING LEDGERS,
<br />. S EDG RS BLOCKING
<br />CRIPPLERS SILLS ETC. SHALL BE SOUTHERN PINE NO, 2 OR BETTER. Fb - - 1100 PSI AND A MODULUS OF
<br />ELASTICITY - 1 400 ODO PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL
<br />AL BE
<br />PRESSURE TREATED, PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />W/ DOT SHALL BE HOT DIPPED GALV, FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />CONTAINS MORE THANIA" OF HEARTWOOD.
<br />EXCLUSIONS FROM THESE PLANS: MINIMUM NAILING PER FBCR 2020, 71h EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />ARE NOT PART OF THE STRUCTURAL. PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALAEPENOING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. SYP #Z
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />WELDED WIRE MESH: AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />WELDED WIRE MESH SHALL BE ASTM Al 064/A1064M GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL
<br />BE SUPPORTED WITH 2• CHAIRS SPACED 3'-0. OC, EACH WAY.
<br />TODESIGNED
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR
<br />C
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF DOW AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE F OUND
<br />REBAR T 1 15 4 A REBAR
<br />SHALL BE AS M AB M GRADE O IN CONCRETE DEFORMED B SHALL BE ASTM A615
<br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED.
<br />RA
<br />GRADE 80 IN MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE
<br />OR STDPL
<br />DESIGN LOADS:
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND METAL LATEST EDITION"
<br />ROOF: LINE LOAD FLOOR: LIVE LOAD 40 psf
<br />AND VERTICAL BARS SHALL LAP 8 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />20 PST TOP CHORD-non-wnarrent
<br />REVIEW.
<br />TM. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25' #6 BAR - 36'
<br />WOOD TRUSSES.
<br />10 psf BTM CHORD -non<onc enl
<br />05 BAR - 30' #7 BAR - 42"
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 36' x 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990.
<br />15 psf TOP CHORD 20 psf TOP CHORD
<br />(7 Psf W/ ASPHALT SHINGLES) (10 Psf W/ No GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS,
<br />10 Psi BTM CHORD 5 psf BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opsf
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 psf
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 psf
<br />WINO: DEAD LOAD SPEED MPH 3- SECOND GUST
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />(ASCE 020) EXPOSURE B, RISK CATEGORY IU
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />BIT BLE(FBC ATTIC
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10p9/, UNINHABITABLE ATTIC WITH LIMITED
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: BALCONIES (EXTERIOR)
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />NTS:
<br />AND DECKS: 40pst, GUARDS AND HANDRAILS: 200ps1, GUARD IN -FILL COMPONENTS: 50pst, PASSENGER
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30Paf, STAIRS:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />40psf
<br />MASONRY:
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT.
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE Pm = 2000 PSI. BLOCK SHALL BE PLACED USING
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL RAVE A MAXIMUM 3/8"
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT,
<br />FOUNDATION/ SITE PREPARATION
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557, TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2.500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB.
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIORTO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5' 41. PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94C94M OR MEASURING, MIXING. TRANSPORTING,
<br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN
<br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL HOT EXCEED 90 M9NUTES. IF FOR ANY REASON
<br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL
<br />BE THE RESPONSIBIUTY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPLIANCE WITH THE ABOVE.
<br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A. Y FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER
<br />1-1/Z FOR AS AND SMALLER
<br />2" FOR MI AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />SIC FOR SLABS, WALLS AND JOISTS
<br />1-1/2" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />TYPE "M" OR W MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT, MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL BE 3/8' THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />STRUCTURAL STEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36/A36M, Fy = 36 ksl FOR ANGLES, PLATES, AND W-SHAPES, STRUCTURAL TUBING SHALL BE ASTM
<br />A500/A500M, GRADE B, Fy = 46 kSl. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy =
<br />35 IFIL TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS
<br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />PROVIDED BY THE TRUSS ENGINEER,
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7A6 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />101
<br />A R C N I T R C T R
<br />Grog Degin
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL 32750
<br />PH: 407-7748078
<br />FAX: 407-774-4078
<br />www,abdesigngroup.com