A
<br />AABLE-END
<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASIDE 7-10
<br />ZONE 1 = 20.97 PSF (30.97)
<br />ZONE 2 = 36.87 PSF (45.87)
<br />ZONE 3 = 61.06 PSF (71.06)
<br />"A•= 4"0' END ZONE DISTANCE
<br />BASIC WIND SPEED: 150 MPH
<br />WIND EXPOSURE: -B'
<br />RISK CATAGORY: 11
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT +- 0.18
<br />ROOF DIAPFRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/18'
<br />O.S.B. OR 1/2' CDX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 518 COX EXT. PLYWOOD, WITH 8d RING
<br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED
<br />PANEL EDGES AND 8d RING SHANK GUN NAILS
<br />AT W O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />RCOF SHEATHING TO GABLE END FRAME USE
<br />Bd GUN NAILS 0 4' O.C. EDGEWISE 20
<br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE
<br />END.
<br />ROOF/ WALU FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN. DIA,
<br />SHANK
<br />TENSILE STIR.
<br />SHANK
<br />Bd
<br />RING SHANK
<br />21/2•
<br />0.120'
<br />170000
<br />LNG
<br />(1ER
<br />SCREW SHANK
<br />PER CH)
<br />INCH)
<br />8d
<br />SCREW SHANK
<br />2 1/2,
<br />0.120"
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION (ISANTA) ESR-1539
<br />EXTERIOR SHEATHING
<br />USE 1/2' CDX OR 7/16' O.S.B. PLY WITH 8d RING
<br />SHANK GUN NAILS AT 4. O.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4.O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN
<br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS
<br />OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />ZW
<br />Z s
<br />:) W
<br />Y
<br />U
<br />=G
<br />co
<br />Q
<br />Do
<br />8d RING SHANK GUN NAILS G 4" O.C.
<br />.. TOP & BOTTOM EDGES .,
<br />Y .
<br />'
<br />TOP CORD BLOCKING AT 4'
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END.
<br />RAFTER OR TRUSS
<br />ROOF SHEATHING
<br />mmm
<br />I
<br />_ e
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE EtW FRAMING
<br />8d RING SHANK GUN NAILS
<br />III W O.C. IN FIELD `
<br />TYP. EXT. SHE*IING ATTACHMEhT FOR R OF SHEATHING (O.. .
<br />TO BE STRUCTURAL GRADE
<br />Sd PING SHANK GUN NAILS 0 12' O.C. IN
<br />FIELD or 8d x 2 1/2' SCREW SHANK
<br />PNEUMATIC SCREW -NAILS 0 12' 0.Bw(N
<br />FIELD J\
<br />TYP. 3/4' T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPLICATKIN
<br />SIZE
<br />TYPE
<br />SPACPNO
<br />PEMAPo(S
<br />APPLICATx)N
<br />811E
<br />BPACWA
<br />iM:MAPoL9
<br />1RPTFumm TO
<br />CASE HAPDENEDCOL
<br />fNPAOE DOORBIICN
<br />1M'OU.
<br />TAPCON MASONRY
<br />112'EMBED., 4-END DIST.,
<br />MABONPYICONC.
<br />1M611rz'LONA.
<br />e,00
<br />TO MABONRYR.'IXC.
<br />ND WASHED
<br />FASTENER
<br />e,�
<br />ill 2'E.-
<br />A-
<br />CASE HARDENED LULL
<br />6'QC
<br />WINDOWIWOR/FASTENED
<br />OAMOE DOOP BUCK
<br />11 DIA W,
<br />EXPANSIQV BOLT
<br />21.OK:
<br />1EMBE0.,A'END DUST.,
<br />t"Pt, BEE N01Ee
<br />NAf 112'LONA.
<br />STAAAEREO
<br />WTO IMSONPY.CONC.
<br />TO MAeONRY,CONC.
<br />WASHER
<br />TEDGEDIST.
<br />WINDOW BACK
<br />CASE HAPDEIEO COK
<br />l'QC
<br />WNDOWNOONFASTENED
<br />METALS -TO
<br />CONTACT THIS ENGINEER FOR SPACING
<br />1x PT, SEE NDTEe
<br />NARttrz'LON3,
<br />STAODEPED
<br />m1D MA90NRYAONC.
<br />-CONC.
<br />REQUIREMENTS
<br />EXT.9WNA DOOR
<br />BUCKDi PT,SEE N01E9
<br />(Z)3I1e9W
<br />ND WASHED
<br />'TAPCpY
<br />FASTNEP
<br />1g QG
<br />t 1rz' EMBED.9'fNO.
<br />DIST.,11rz'EDDEGIST.
<br />NONBE,IPNO WOOD
<br />WALL TO CONC.9LAH
<br />12'° E%PANSKKY 4'EM3EA.4'END
<br />WI WASYEP BOLT NOC DST, 3-EDDE C13T.
<br />2P PT WINDOY/BUCK Ot3e°PAF"21,e' YOb 4'END. DIST.,11fY
<br />PT TO STLCOL., 9EE W/WASHED STAAAERED EDAE MST.
<br />Ee
<br />NOTBI
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />e. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. IX MEMBERS ARE NAILED AND
<br />2z MEMBERS ARE SECURED W/TAPOONS OR PAF TO THE SUBSTRATE.
<br />GENERAL NOTES:
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, Sth EDITION
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, ACI 6W13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS,
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />DESIGN LOADS:
<br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 pef
<br />20 pef TOP CHORD-TanooODu-t
<br />10 Del BTM CHORD mtHoo ffl
<br />DEAD LOAD DEAD LOAD
<br />16 pef TOP CHORD 20 pe1 TOP CHORD
<br />(7 pef W ASPHALT SHINGLES) (10 psf w/ No GYPCRETE)
<br />10 Dof BT M CHORD 5 P of BTM CHORD
<br />DEAD LOAD TO RESIST WIND UPLIFT: 10pef
<br />BALCONY LIVE LOAD 80 Per!
<br />STAIRS LIVE LOAD 40 Pef
<br />WIND: DEAD LOAD SPEED-150 MPH 3-SECOND GUST
<br />(ASCE 7-10 (FED R2017) EXPOSURE B, RISK CATEGORY 11)
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10pe1, UNINHABITABLE ATTIC WITH LIMITED
<br />STORAGE: 20pef, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30pa1, BALCONIES (EXTERIOR)
<br />AND DECKS: 40pef, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50pef, PASSENGER
<br />VEHICLE GARAGES: 60pef, ROOMS OTHER THAN SLEEPING ROOM: 40pef, SLEEPING ROOMS: 30PN, STAIRS:
<br />4W
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />OF THE
<br />H CONTRACT DOCUMENTS ONLY, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />E
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH ElEVA710NS, DIMENSIONS ETC
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />WRITING BY THE ARCHITECT.
<br />FOUNDATIOW SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2.000 pef. FOOTING
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 96% OF THE
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1667. TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER,
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2,600 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB-OWGRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 6" STRUCTURAL TERRACE SUB.
<br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP WALL NOT EXCEED S * PRIOR TO THE ADDITION OF PLASTICIZER
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC33. MAXIMUM AGGREGATE SIZE SHALL BE 3'1".
<br />WOOD:
<br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPR
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CIMAEERED 31C.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb =1100 PSI AND A MODULUS OF
<br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLASSONGROUND WHERE INDICATED ON
<br />ELASTICITY . 1.400.000PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />DRAWINGS. SEAMS UPPED B INCHES AND SEALED WITH ADHESIVETAPE.
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED, WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />FORM -WORK,
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />FORMWORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />"RECOMMENDED PRACTICE FOR CONCRETE FORMWORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2017, 6th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL. DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2z STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTRS.
<br />HE
<br />SYP I2.
<br />WELDED WIRE MESH:
<br />WELDED WIRE MESH, SHALL BE ASTM A186, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES, WIRE MESH FOR SUBS SHALL BE
<br />SUPPORTED WITH 2' CHAIRS SPACED 3'-0" DC, EACH WAY.
<br />REINFORCING STEEL
<br />REBAR SHALL BE ASTM A616 GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />REVIEW.
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: 44 BAR - 25' e6 BAR - 36'
<br />e6 BAR - 30" N7 BAR - 42'
<br />PROVIDE 36" x 38" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />MINIMUM 101N CH HOO
<br />KS KS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />O
<br />WALL,
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />MASONRY:
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />'SPECIFICATION MASONRY STRUCTURES' (ACI 630/ASCE 6/TMS 402. BUILDING CODE REQUIREMENTS FOR
<br />ANSPECIFICATIONS P R MASONRY STRUCTURES AND COMMENTARIES AS
<br />MASONRY STRUCTURES D 0 ),
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />MANUFACTURED IN CONFORMANCE WITH ASTM G90, GRADE ft0. 2000 PSI. BLOCK SHALL BE PLACED USING
<br />RUNNING BOND UNLESS OTHERWISE NOTED, LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />ASTM C-478, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8'
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF e' TO 10'. USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />TYPE'M' OR W MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C470. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL BE 31W THICK UNLESS OTHERWISE NOTED, REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />STRUCTURAL STEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />BTH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36, Fy . 36 kei FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A,600, GRADE B
<br />Fy .46 k9i. STRUCTURAL PIPE SHALL BE ASTM63, GRADE B, TYPE E OR S. Fy .35 W. TUBE AND PIPE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM A326-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />CONCRETE SWILL COMPLY WITH ALL THE REQUIREMENTS OF ACI 3DI AND ASTM C.940R MEASURING, MANG, TRANSPORTING, ETC . ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL.J-BOLTS ARE TO BE STEEL.
<br />CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS
<br />ADDED TO THE MX UNTIL IT IS DEPOSITED IN ITS RNA POSITION SHALL NOT EXCEED 9D MINUTES, IF FOR ANY REASON THERE IS A
<br />DRAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT $WALL BE THE
<br />RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON
<br />COMPLIANCE WTH THE ABOVE.
<br />REQUIRED CONCRETE COVERAGE OVER REBAR WALL BE AS FOLLOWS:
<br />A. 3• FOR CONCRETE CAST AGAINST AND PERMA MY EXPOSED TO EARTH(FOUNDATIONSI
<br />B. FOR CONCRETE EXPOSED TO EARTH ANDIORWEATHER:
<br />I Ur FORTS AND SMALLER
<br />Z: FOR BB AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />31Y FOR SLABS, WALLS AND JOISTS
<br />1.12' FOR BEAM AND COLUIM PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />WOOD TRUSSES:
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE 'NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.038" AND BE MANUFACTURED FROM STEEL
<br />MEETING THE REQUIREMENTS OF ASTM A46S, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED,
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14,'DESIGN NATIONAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND 'TPUWTCA BCSI V
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />WOOD TRUSSES.
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982.
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS,
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE, TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING, ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />LICENSED PROFESSIONAL ENGINEER.
<br />THEHURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />R AP L TE
<br />CONSTRUCTION SCHEDULE AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />PROVIDED BY THE TRUSS ENGINEER,
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL THOSE
<br />SUPERCED E E
<br />S
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7.10 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />A N 0 N I T E C T•
<br />F
<br />GWDe
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL 32750
<br />PH: 407-7748078
<br />FAX: 407-774.4078
<br />www.abdesigngroup.com
<br />AA N: 0003325
<br />DRAFTING BY:
<br />A.B. DESIGN GROUP
<br />DRAFTING INC.
<br />5439 BEAUMONT CENTER BLVD.
<br />SUITE 1004
<br />TAMPA, FLORIDA 33634
<br />PH: 813-SM2628
<br />FAX: 81"862802
<br />
|