Laserfiche WebLink
I . i i 'I !I!! I-' I- I I I L <br />1! - - I i - -1 IN11 1 1 1 Il <br />GENERAL DEMOLITION NOTES <br />1. IT IS THE INTENT OF THE CONTRACT DOCUMENTS TO PROVIDE FOR FIRE RETARDANT WOOD NAILER <br />ALL REQUIRED DEMOLITION TO BE PERFORMED, WITHOUT SPECIFICALLY I>< <br />ADDRESSING EACH AND EVERY ITEM. CONTRACTOR TO PROVIDE FOR ALL CLOSE CEILING SPACE WITH 6 <br />INCIDENTAL AND ASSOCIATED DEMOLITION REQUIRED FOR RENOVATED OR CLOSE OPEN DUCTS W/25 MIL FIRE -RETARDANT POLY. <br />NEW WORK TO BE CONSIDERED COMPLETE. GA. GALV. SHEET METAL SEAL ALL JOINT PENETRATIONS <br />2. DEMOLITION KEYNOTES: REFER TO KEYNOTE LEGEND FOR EXPLANATION 7 AND PERIMETER WITH DUCT <br />OF EACH NUMBERED ITEM ON THE DEMOLITION PLAN. SPECIFIC DEMOLITION SEAL AROUND ALL PIPE TAPE <br />ITEMS ARE NOT TO BE CONSIDERED ALL INCLUSIVE OR COMPLETE IN AND DUCT PENETRATIONS <br />THEMSELVES. ADDITIONAL DEMOLITION NOT DIRECTLY INDICATED MAY BE IN THE PARTITION AND <br />REQUIRED TO ACHIEVE THE DESIRED RESULT. POLY BARRIER WITH DUCT <br />3. SITE VISIT: PRIOR TO BIDDING, THE CONTRACTOR SHALL VISIT THE TAPE <br />FACILITY AND THOROUGHLY FAMILIARIZE HIMSELF WITH EXISTING EXIST GWB OR ACT CEILING <br />CONDITIONS. NO CLAIMS FOR ADDITIONAL WORK DUE TO UNFORESEEN <br />PLASTER TAPE ALL JOINTS; <br />CONDITIONS WILL BE CONSIDERED <br />4. ADDITIONAL ITEMS: FOR DEMOLITION AND PHASING, WHERE INDICATED, <br />ACCEPTABLE SUBSTITUTION: <br />REFER TO STRUCTURAL, MECHANICAL, ELECTRICAL OR PLUMBING DRAWINGS <br />MOBILE DUST CONTAINMENT AND <br />AND SPECIFICATIONS FOR ADDITIONAL INFORMATION SPECIFIC TO EACH <br />FIRE RATED, SMOKE TIGHT <br />?%OLTTION WORK: CARRY OUT DEMOLITION WORK TO CAUSE AS LITTLE <br />CONSTRUCTION ISOLATION <br />BARRIER UNITS BY 'KONTROL <br />COMPRESSIBLE INSULATION <br />INCONVENIENCE TO ADJACENT OCCUPIED BUILDING AREAS AS POSSIBLE. <br />KUBE" (OR EQUAL).CONTAINMENT <br />DEMOLISH IN AN ORDERLY AND CAREFUL MANNER AS REQUIRED TO <br />UNIT TO HAVE <br />ACCOMMODATE NEW WORK. PROTECT EXISTING SUPPORTING STRUCTURAL <br />JOINT COMMISSION COMPLIANCE <br />CONTINUOUS SEALANT BEAD <br />MEMBERS. PERFORM DEMOLITION IN ACCORDANCE WITH APPLICABLE <br />DOCUMENTATION <br />AUTHORITIES HAVING JURISDICTION. SCHEDULE ALL DEMOLITION WORK WITH <br />FINISH OCCUPIED SIDE WITH <br />OWNER PRIOR TO START OF THE WORK. GENERAL CONTRACTOR SHALL <br />GLOSS PAINT <br />COORDINATE ALL TRADES TO ENSURE THE WORK IS PERFORMED IN A <br />TIMELY MANNER AS SCHEDULED. <br />RENOVATION SIDE <br />OCCUPIED SIDE <br />6. EXISTING SYSTEMS: ALL EXISTING SYSTEMS SUCH AS ALARMS, <br />ELECTRICITY, WATER SPRINKLERS, ETC. SHALL REMAIN ACTIVE AT ALL <br />NOTE <br />TIMES DURING DEMOLITION AND CONSTRUCTION, ANY EXCEPTION TO THIS <br />.�Jp <br />ADEQUATE BRACING <br />5/8" GWB ON 3 5/8" MTL <br />SHALL BE COORDINATED WITH OWNER AND ARCHITECT PRIOR TO THE <br />FOR POLY BARRIER TO <br />STUDS 1 HR) - U.L. DESIGN <br />IEE&NFLICTS: ANY CONFLICTS FOUND WITH EXISTING CONDITIONS AND <br />ENSURE A CONTINUOUS <br />96D INSULATION BAITS <br />REQUIREMENTS FOR NEW CONSTRUCTION SHALL BE IMMEDIATELY BROUGHT <br />SEAL WHILE MAINTAINING <br />TO THE ATTENTION OF THE ACHITECT. IF THE CONFLICT AFFECTS THE <br />REQUIRED NEGATIVE AIR <br />SEAL PERIMETER OF WALL WITH <br />PROGRESS OF THE WORK, VERIFY WITH ARCHITECT SOLUTION NECESSARY <br />PRESSURE <br />DUCT TAPE <br />PRIOR TO PROCEEDING WITH THAT PORTION OF THE WORK. COORDINATE <br />. SECURE ALL TAPE W/E& CONTINUOUS SEALANT BEAD <br />ALL TRADES TO ASCERTAIN NO FURTHER WORK WILL BE IMPACTED BY THE <br />HIGH TACK SPRAY OR COMPRESSIBLE INSULATION <br />CONFLICT OR ITS SOLUTION. <br />EQUAL <br />EQU <br />8. REMOVE AND REPLACE EXISTING CONSTRUCTION AS NECESSARY TO <br />COMPLETE THE MECHANICAL, ELECTRICAL AND PLUMBING DEMOLITION WORK <br />AT THIS FLOOR LEVEL, ABOVE AND BELOW. EXAMPLE: PENETRATE AND <br />CONSTRUCTION BARRIER D ETAI L <br />PATCH STRUCTURAL FLOOR, PARTITIONS, CEILINGS AND FIRE PENETRATIONS <br />FOR MECHANICAL, ELECTRICAL AND PLUMBING PENETRATIONS. <br />S(ALE: 3" = 1'-0" <br />9. COORDINATE AND SCHEDULE ACCESS TO ALL DEPARTMENTS OUTSIDE OF <br />THIS SCOPE OF WORK WITH THE OWNER PRIOR TO ANY WORK. <br />10. PROVIDE NEGATIVE AIR PRESSURE FROM ALL AREAS UNDER <br />RENOVATION FOR THE DURATION OF DEMOLITION AND CONSTRUCTION. <br />f CEILING AS SCHEDULED <br />11. STRUCTURE: PREVENT MOVEMENT OR SETTLEMENT OF STRUCTURE. <br />- - <br />PROVIDE AND PLACE BRACING OR SHORING AND BE RESPONSIBLE FOR <br />ONE LAYER 5/8" <br />SAFETY AND SUPPORT OF STRUCTURE. ASSUME LIABILITY FOR SUCH <br />GWB TOP OF <br />MOVEMENT, SETTLEMENT, DAMAGE OR INJURY. CEASE OPERATIONS AND <br />PARTITION <br />NOTIFY THE ARCHITECT IMMEDIATELY IF SAFETY OF THE STRUCTURE <br />APPEARS TO BE ENDANGERED. TAKE PRECAUTIONS TO PROPERLY <br />CONT. TRACK <br />SUPPORT THE STRUCTURE. DO NOT RESUME OPERATIONS UNTIL SAFETY IS <br />ffS CTION: EXERCISE CARE DURING WORK TO PROTECT EXISTING <br />CONSTRUCTION TO REMAIN. REPAIR TO EXISTING CONSTRUCTION DUE TO <br />DAMAGE SHALL BE DONE AT NO COST TO THE OWNER. <br />13. CONSTRUCTION SEPARATION PARTITIONS: ERECT AND MAINTAIN DUST <br />3 5/8" METAL STUDS ® 16" O.C. <br />PROOF PARTITIONS AS REQUIRED TO PREVENT SPREAD OF DUST, FUMES <br />AND SMOKE TO OTHER PARTS OF THE BUILDING. PARTITIONS SHALL BE <br />MINIMUM 1-HOUR RATED CONSTRUCTION WHEN SEPARATING WORK FROM <br />ONE LAYER LEAD -LINED 5/8" GWB ON <br />OCCUPIED AREAS, ALONG EXIT ACCESS CORRIDORS AND BUILDING EXITS <br />PROCEDURE SIDE OF PARTITION <br />OR WHERE REQUIRED BY CODE OR GOVERNING AUTHORITY. ON <br />COMPLETION, REMOVE PARTITIONS AND REPAIR DAMAGED SURFACES TO <br />PROCEDURE ROOM SIDE <br />MATCH ADJACENT SURFACES AND FINISHES. (SEE <br />7 <br />WA60WMWIMATERIALS: EXCEPT WHERE NOTED OTHERWISE, MAINTAIN <br />ONE LAYER 5/8" GWB ON NON - <br />POSSESSION OF ALL MATERIALS BEING DEMOLISHED. EQUIPMENT AND <br />PROCEDURE SIDE OF PARTITION <br />ARTICLES OF VALUE REMAIN THE PROPERTY OF THE OWNER. NOTIFY THE <br />ARCHITECT PRIOR TO REMOVAL AND OBTAIN ACCEPTANCE REGARDING <br />METHOD OF REMOVAL REMOVE ALL MISCELLANEOUS MATERIALS, <br />SOUND ATTENUATION INSULATION <br />LINE OF STRUCTURE <br />CONNECTORS, FASTENERS, FLOORING, CEILING TILE AND GRID, ETC., NOT <br />REQUIRED FOR NEW CONSTRUCTION. ARTICLES OF NO VALUE, INCLUDING <br />CONT. RUNNER <br />TRASH, DEBRIS, WASTE MATERIALS, ETC., SHALL BE IMMEDIATELY REMOVED <br />FROM THE SITE AND DISPOSED OF IN A LEGAL, APPROVED MANNER. <br />1 <br />15. REPAIR: REPAIR ALL DEMOLITION PERFORMED IN EXCESS OF THAT <br />CONT. SEALANT <br />BOTH SIDES OF <br />REQUIRED AT NO ADDITIONAL COST TO THE OWNER. <br />PARTITION <br />16. DISPOSAL- REMOVE FROM SITE ALL CONTAMINATED, VERMIN INFESTED <br />OR DANGEROUS MATERIALS ENCOUNTERED AND DISPOSE OF BY SAFE, <br />��11/2- GAP AT BOTTOM GWB TYP. <br />APPROVED MEANS SO AS NOT TO ENDANGER THE HEALTH OF WORKERS <br />AND PUBLIC. BURNING OF MATERIALS ON SITE IS NOT PERMITTED. <br />17. COMPLETION OF CONSTRUCTION PHASES: REMOVE ALL DEMOLISHED <br />MATERIALS, TOOLS, EQUIPMENT, ETC., FROM THE SITE UPON COMPLETION <br />NON RATED <br />OF THE WORK. LEAVE SITE IN CONDITION ACCEPTABLE TO THE ARCHITECT, <br />AND READY FOR THE NEXT PHASE OF WORK. <br />LEAD -LINED LOW -WALL, <br />18. REFER TO HOSPITAL'S PROTOCOLS FOR INFORMATION REGARDING <br />INFECTION CONTROL AND DEMOLITION AND CONSTRUCTION. THESE <br />PROTOCOLS ADDRESS BUT ARE NOT LIMITED TO THE FOLLOWING: <br />PARTITION <br />A. REMOVAL OF DEBRIS FROM THE PROJECT. <br />B. DELIVERY OF NEW MATERIALS INTO THE BUILDING. <br />A.) 3-5/8" METAL STUDS ® 16" O.C., TYP. <br />C. STORAGE OF CONSTRUCTION MATERIALS. <br />B.) 5/8" LEAD -LINED GWB AT PROCEDURE SIDE OF WALL. <br />D. CLEANING OF DUST AND DEBRIS FROM BOTH CONSTRUCTION AND <br />C.) 5/8" GWB AT NON -PROCEDURE SIDE AND TOP OF WALL. <br />OCCUPIED AREAS. <br />D.) USE LOW -WALL PARTITION BRACE WHERE INDICATED - <br />19. MAINTAIN AT ALL TIMES THE FIRE RATED INTEGRITY OF ALL VERTICAL <br />SEE FLOOR PLANS AND DETAIL C2/A001. <br />SHAFTS. <br />20. CONTRACTOR SHALL BE RESPONSIBLE FOR ADHERING TO ALL <br />HOSPITAL PROTOCOLS AS THEY RELATE TO CONSTRUCTION NOISE, <br />LINE OF STRUCTURE <br />VIBRATION, INFECTION CONTROL AND ANY OTHER THAT MAY AFFECT THE <br />ONGOING SAFE OPERATION OF THE FACILITY DURING CONSTRUCTION. <br />21. CONTRACTOR SHALL ROUTE/SCHEDULE DELIVERY OF CONSTRUCTION <br />MATERIALS AS WELL AS THE REMOVAL OF CONSTRUCTION DEBRIS TO <br />MINIMIZE ITS IMPACT TO HOSPITAL OCCUPIED AREAS. <br />EXTEND GWB TO 6" ABOVE CLG. <br />22. NO CONSTRUCTION MATERIALS SHALL BE STORED IN OCCUPIED <br />PATIENT AREAS. <br />23. CONTRACTOR SHALL SWEEP AND DAMP MOP FLOORS ALONG THE <br />AREAS OF MATERIAL MOVEMENT TO LIMIT THE SPREAD OF DUST AND <br />DEBRIS THROUGHOUT THE OCCUPIED AREAS. <br />CEILING AS SCHEDULED <br />24. THE INTEGRITY OF THE FIRE/SMOKE COMPARTMENTS SHALL BE <br />MAINTAINED AT ALL TIMES DURING THE CONSTRUCTION PROCESS, <br />ONE LAYER 5/8" LEAD -LINED GWB <br />DURING PHASED CONSTRUCTION, SHOULD A FIRE/SMOKE BARRIER BE <br />REMOVED, EITHER A PERMANENT NEW BARRIER OR TEMPORARY BARRIER <br />MEETING THE REQUIREMENTS OF THAT BARRIER WHICH IS BEING REMOVED <br />FURRING TO MATCH EXISTING ADJACENT <br />SHOULD BE CONSTRUCTED BEFORE THE EXISTING BARRIER IS REMOVED. <br />(DEPTH, SPACING, ETC.) CONSTRUCTION <br />25. IF DURING THE DEMOLITION PROCESS, THE CONTRACTOR ENCOUNTERS <br />DAMAGE AFFECTING THE INTEGRITY OF ANY EXISTING RATED <br />EXISTING WALL <br />WALL/MEMBRANE, HE SHALL REPAIR SUCH DAMAGE IN ORDER TO RETURN <br />WALL/MEMBRANE TO ITS INTENDED FIRE/SMOKE RATING. <br />26. FIRE ALARM AND SMOKE DETECTION SYSTEMS SHALL REMAIN ACTIVE <br />DURING THE ENTIRE CONSTRUCTION PROCESS, SPRINKLER HEADS MAY BE <br />COVERED DURING HOURS OF CONSTRUCTION, BUT MUST BE REMOVED <br />DURING IDLE HOURS. SHOULD THE ABOVE BE IMPOSSIBLE, A FIRE WATCH <br />CONT. SEALANT <br />SHALL BE ESTABLISHED UNTIL SUCH TIME AS THE AUTOMATIC SYSTEMS <br />CAN BE PLACED BACK INTO OPERATION. <br />27. IF THE FIRE PROTECTION SPRINKLER SYSTEM AND/OR THE REQUIRED <br />FIRE ALARM SYSTEM IS SHUT DOWN GREATER THAN 4 HOURS IN A <br />24-HOUR PERIOD, THE AUTHORITY HAVING JURISDICTION SHALL BE <br />1 2" GAP AT BOTTOM GWB TYP. <br />/ <br />NOTIFIED AND AN APPROVED FIRE WATCH SHALL BE PROVIDED FOR ALL <br />PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE SPRINKLER <br />2 <br />SYSTEM AND/OR FIRE ALARM SYSTEM HAS BEEN RETURNED TO SERVICE. <br />28. CONSTRUCTION BARRIERS MUST BE COMPLETED BEFORE DEMOLITION <br />N 0 N RATED <br />BEGINS. POST SIGNAGE AS REQUIRED AT DOORS TO THE WORK AREA: <br />"CONSTRUCTION AREA - DO NOT ENTER" <br />LEAD -LINED, SINGLE <br />29. CONSTRUCTION BARRIERS ARE TO MAINTAIN ACCESS TO ALL ACTIVE <br />MEDICAL GAS ISOLATION, CONTROL VALVES AND ALARM PANELS. <br />SIDED, FURRED PARTITION. <br />30. PROVIDE TEMPORARY EMERGENCY EGRESS LIGHTING, SIGNAGE, FIRE <br />ALARM DEVICES AND EXTINGUISHERS AS REQUIRED. <br />A.) FURRING TO MATCH ADJACENT EXISTING (DEPTH, SPACING, ETC.) <br />31. NOTIFY OWNER 48 HOURS PRIOR TO OBSTRUCTION OF DOORWAYS FOR <br />CONSTRUCTION <br />RECONSTRUCTION OF PARTITIONS. COORDINATE WORK WITH OWNER TO <br />B.) 5/8" LEAD -LINED GWB AT PROCEDURE SIDE OF WALL. <br />OCCUR AT TIME OF MINIMAL USAGE, SUCH AS WEEKENDS OR AFTER <br />C.) EXTEND GWB TO 6" MIN. ABOVE CEILING <br />REGULAR HOURS. <br />32. AT NO TIME SHALL ANY EGRESS DOOR OR PASSAGE BE OBSTRUCTED <br />PROVIDING AN ALTERNATE, CODE COMPLIANT MEANS OF EGRESS, <br />PARTITION TYPES <br />WITHOUT <br />B3 <br />REFER TO N.F.PA. 101 SECTION 18.7.9 <br />SCALE: NTS <br />33. CONTRACTOR SHALL REMOVE DEBRIS FROM CONSTRUCTION AREA IN <br />AIR TIGHT CONTAINER. <br />EILING AS SCHEDULED <br />LEAD LINING SHALL CONFORM TO LEAD LINING PLAN AS PROVIDED. <br />IT SHALL BE CONTINUOUS THROUGHOUT. <br />MAINTAIN INTEGRITY OF RADIATION SHIELDING, <br />EAD LINING SHALL CONFORM TO PHYSICIST'S REPORT AS PROVIDED BY OWNER. <br />IT SHALL BE CONTINUOUS THROUGHOUT. <br />MAINTAIN INTEGRITY OF RADIATION SHIELDING. <br />3 5/8" METAL STUDS ® 16" O.C. <br />DNE LAYER 5/8" GWB EACH SIDE <br />SOUND ATTENUATION INSULATION <br />CONT. RUNNER <br />CONT. SEALANT <br />BOTH SIDES OF <br />P RTITION <br />1 /2" GAP AT BOTTOM GWB TYP. <br />3 <br />NON RATED PARTITION <br />A.) 3 5/8" STUDS AT 16" O.C. <br />B.) 5/8" GWB BOTH SIDES OF STUDS TO <br />BOTTOM OF STRUCTURE ABOVE <br />'irt , JAMB OR SILL CONDITION <br />.EAD LINED HOLLOW METAL FRAME <br />FAQ IINFI> =A <br />PROCEDURE ROOM SIDE <br />LEAD SHIELDING TO TIE-IN TO NEW LEAD LINED PARTITION FOR CONTINUOUS RADIATION BARRIER <br />HEAD/JAM B/SILL <br />LEAD -LINED VIEW WINDOW <br />C) SCALE: 3r - 1'-0r <br />3" x 1 /4" STL CHANNEL <br />ATTACHED TO DBL. BOXED <br />MTL STUDS AT END OF <br />Cn <br />j <br />LOW PARTITION AND STL <br />o <br />E a I <br />BASE PLATE <br />I <br />a I <br />CONTINUOUS WELD AT <br />ao <br />STEEL BASE PLATE AND <br />STEEL CHANNEL <br />_ I <br />3/8" STEEL GUSSETT <br />o <br />WELDED TO VERT. STL. <br />CHANNEL AND STL. BASE <br />o W j I <br />PLATE <br />III <br />I III <br />3" x 1 /4" STEEL PLATE <br />o Q <br />W/ 9/16" DIA. HOLES FOR <br />0 <br />1 /2"DIA. ANCHOR BOLTS <br />Co <br />TO CONC. FLOOR. <br />8• <br />ANCHORS SHALL BE <br />INSTALLED IN PAIRS ALONG <br />THE LENGTH OF THE BASE <br />PLATE. PROVIDE FLAT H.D. <br />BOLTS FOR FLAT <br />INSTALLATION OF METAL <br />SILL PLATE. RUNNER TRACK <br />IS TO BE INSTALLED <br />BENEATH STEEL BASE <br />LOW -WALL PARTITION <br />PLATE. <br />SUPPORT BRACKET DETAIL <br />SCALE: N.T.S. <br />LAMINATE BACK PIECE TO GWB FACE LAYER <br />5/8" LEAD LINED GWB AT ALL SIDES <br />(5 SIDES) OF RECESSED OPENING <br />SHALLOW FIVE SIDED BOX 5/8" LEAD LINED GWB AT PROCEDU E <br />ROOM SIDE OF PARTITION (TYP) <br />JUNCTION BOX (TYP) <br />JUNCTION BOX AT GWB LEAD LINED PARTITION <br />SCALE: 1 1/2" = 1'-0" <br />►' STEEL STUDS - CHANNEL <br />f 1 5/8" 25 MSG, GALV <br />EXISTING/NEW - 5/8" LEAD LINED <br />GWB AT PROCEDURE ROOM SIDE OF <br />PARTITION (TYP) <br />5/8" LEAD LINED GWB AT ALL SIDES <br />r (5 SIDES) OF RECESSED OPENING <br />t II <br />CABLE DUCT/UTILITY BOX <br />I I -CONTRACTOR TO VERIFY DIMENSIONS <br />I I AND MOUNTING HEIGHT W/ APPROPRIATE <br />I I CONSTRUCTION DOCUMENTS AND/OR <br />I I EQUIPMENT VENDOR DOCUMENTS, OR AS <br />I I INDICATED ON THE INTERIOR ELEVATIONS <br />c STEEL STUDS <br />REFER TO RADIATION PHYSICIST'S <br />REPORT, TO DETERMINE REQUIRED <br />L,+-' L THICKNESS AND LOCATION OF LEAD <br />LINED GWB - RADIATION SHIELDING. <br />EQUIPMENT AT GWB LEAD LINED PARTITION <br />SCALE: 1 1/2" = 1'-0" <br />PLEAD -LINED PARTITION DETAILS <br />SCALE: AS NOTED <br />NTERIOR FINISH NOTES <br />GENERAL FINISH NOTES: <br />• CONTRACTOR SHALL CLEAN AND REMOVE OLD PAINT, STAIN, ETC. FROM ALL WALL MOUNTED ACCESSORIES BEING <br />REMOVED AND REINSTALLED. <br />• CONTRACTOR SHALL REPAIR ALL VOIDS AND PENETRATIONS AT LEAD -LINED PARTITIONS - INSTALL LEAD -LINED GWB AS <br />REQUIRED. <br />• CONTRACTOR SHALL REPAIR ALL VOIDS AND PENETRATIONS AT FIRE AND SMOKE RATED PARTITIONS - INSTALL FIRESAFING <br />AS REQUIRED FOR COMPLIANCE. <br />• FINAL INTERIOR FINISH, COLOR, PATTERN AND MANUFACTURER SELECTION BY OWNER. COLORS & PATTERNS MAY VARY. <br />• NEW DOORS FINISH TO MATCH EXISTING. <br />• EXISTING FURNISHINGS AND MOVABLE EQUIPMENT TO BE RELOCATED BY OWNER. <br />• ALL FLOORING SEAMS TO BE WELDED PER MANUFACTURER'S INSTRUCTIONS. <br />PAINT: <br />• ALL WALL COLORS TO BE PAINTED IN EGG SHELL FINISH. <br />• ALL MOLDING TRIM TO BE PAINTED IN SEMI -GLOSS FINISH. <br />• ALL DOOR TRIM TO BE PAINTED TO MATCH ADJACENT WALL COLOR; SEMI -GLOSS FINISH. <br />• ALL WALLS TO BE PAINTED 'PT1', UNLESS NOTED OTHERWISE. <br />• ALL METAL PAINTED DOORS, DOOR FRAMES, ACCESS DOORS, ELECTRIC PANEL COVERS, <br />RECESSED CABINET DOORS, HVAC REGISTERS, GRILLES, ETC. (EXCEPT THOSE WHICH ARE <br />PRE -FINISHED, STAINLESS STEEL, OR ANODIZED ALUMINUM) SHALL BE PAINTED TO <br />MATCH ADJACENT WALL COLOR. <br />• FIRE EXTINGUISHER & FIRE HOSE CABINETS SHALL BE PAINTED TO MATCH ADJACENT <br />WALL COLOR. <br />• INTERIOR WINDOW AND VIEW WINDOW FRAMES TO BE PAINTED TO MATCH ADJACENT WALL <br />COLOR. <br />• WHERE DOOR FRAMES ARE NOTED OR SCHEDULED TO RECEIVE DIFFERENT PAINT <br />COLORS ON EACH SIDE OF PARTITION - COLOR CHANGE SHALL OCCUR AT INSIDE <br />CORNER OF DOOR JAMB STOP. <br />• EXISTING WALL COVERING AND WALL COVERING BORDERS TO BE REMOVED, WITH WALL <br />SURFACES PATCHED AND PREPARED TO RECEIVE NEW PAINT FINISH. <br />• ADDITIONAL WALL PREP MAY BE REQUIRED WHERE NEW WALL BASE IS ONLY 4" HIGH IN <br />LIEU OF EXISTING 6" HIGH WALL BASE. <br />• PROVIDE BENJAMIN MOORE PAINT (IF REQUIRED BY COLOR SCHEDULE BELOW - MIX <br />BENJAMIN MOORE TO MATCH OTHER MANUFACTURER'S COLORS LISTED) <br />PLASTIC LAMINATE: <br />• IN VERTICAL APPLICATIONS, ALL GRAIN TO RUN VERTICALLY, TYPICAL. <br />SCOPE OF WORK APPLICATION NOTES <br />A. CONTRACTOR SHALL REMOVE ALL WALLPAPER IN PREPARATION TO RECEIVE NEW FINISH. CONTRACTOR SHALL <br />MAKE ALL NECESSARY REPAIRS TO WALLS. <br />B. CONTRACTOR SHALL REMOVE ALL FLOORING AND WALL BASE IN ALL ROOMS IN PREPARATION TO RECEIVE NEW <br />FINISH. CONTRACTOR SHALL MAKE ALL NECESSARY REPAIRS TO FLOORS. <br />C. CONTRACTOR SHALL PROTECT ALL EXISTING CEILING ASSEMBLY IN ROOMS, UNLESS NOTED OTHERWISE. <br />PATCH/REPAIR/PAINT ANY CEILING GRID THAT IS SCRATCHED OR CHIPPED WITH PAINT 'PT3'. CONTRACTOR <br />SHALL REPLACE ANY DEFECTIVE CEILING TILE WITH 'LIKE' TILE TO EXISTING - CONSULT WITH OWNER. <br />INTERIOR FINISH MATERIAL SPECIFICATIONS <br />PLASTIC LAMINATE [CASEWORK] <br />PLM-1 /ALL CASEWORK U.N.O - MATCH BLDG. CASEWORK STANDARD (TO BE SELECTED BY OWNER) <br />PLM-2 /ALL COUNTERTOPS U.N.O - MATCH BLDG. CASEWORK STANDARD (TO BE SELECTED BY OWNER) <br />(NOTE: All adjacent backsplash and sidesplash to match countertop laminate, unless noted otherwise) <br />SHEET FLOOR <br />FL1 = WOOD GRAIN SHEET VINYL FLOORING TO MATCH BLDG. STANDARD (TO BE SELECTED BY OWNER), <br />• WITH MATCHING WELD ROD <br />WALL BASE <br />BSE-1 INTEGRAL - SEE 'FL1' ABOVE <br />PAINT <br />CEILING / SOFFIT PAINT <br />PT-3 /ALL - UNDERSIDE OF SOFFITS AND CLG. GRID - "Super White" (in semi -gloss finish) <br />(MFR. TO BE SELECTED BY OWNER) <br />WALL PAINT <br />PT-1 / GENERAL WALLS - TO BE SELECTED BY OWNER <br />PT-2 / ACCENT WALLS - TO BE SELECTED BY OWNER <br />ACOUSTICAL CEILING <br />ACT1 / MATCH EXISTING BLDG. TILE AND GRID STANDARD <br />r\i\L-r1 U1 vvvi\r\ <br />WORK LOCATION PLAN <br />SCALE: 3/32" = 1'-0" <br />NORTH <br />C) <br />SaltCo, LLC <br />AA 26001479 <br />General Notes: <br />A. DO NOT SCALE DRAWINGS. <br />B. VENDOR PROVIDED EQUIPMENT SHOWN FOR REFERENCE ONLY - <br />REFER TO OWNER PROVIDED VENDOR DOCUMENTS FOR <br />ADDITIONAL INFORMATION. CONTACT EQUIPMENT MANUFACTURER <br />FOR EQUIPMENT RELATED QUESTIONS OR CONCERNS. <br />C. CONTRACTOR SHALL CAREFULLY STUDY AND COMPARE THE <br />DRAWINGS AND SPECIFICATIONS AND NOTIFY THE ARCHITECT OF ANY <br />ERRORS OR INCONSISTENCIES PRIOR TO BEGINNING WORK. <br />D. CONTRACTOR SHALL VERIFY AND COORDINATE CLEAR DIMENSIONS <br />REQUIRED FOR OWNER/VENDOR FURNISHED EQUIPMENT AND <br />NOTIFY THE ARCHITECT IMMEDIATELY OF ANY CONFLICTS AND <br />PROCEED ONLY UPON RESOLUTION. <br />E. COLOR, STYLE, PATTERN AND MANUFACTURER OF INTERIOR <br />FINISHES MAY VARY. SELECTIONS BY OWNER. VERIFY PRIOR TO <br />INSTALLATION. <br />F. MAINTAIN COMPLIANCE WITH OWNER -FURNISHED RADIATION SHIELDING <br />REQUIREMENTS - IN ANY RENOVATED, AND NEW CONSTRUCTION. <br />G. EXISTING EQUIPMENT REFERENCED AND/OR NOT SHOWN, IS REMOVED <br />BY OTHERS - UNDER SEPARATE AGREEMENT WITH OWNER. <br />H. REPAIR ANY PENETRATIONS/HOLES ON EXISTING FIRE OR SMOKE RATED, <br />AND LEAD -LINED WALLS WITHIN THE SCOPE OF THE WORK, IN ORDER <br />TO MAINTAIN THE INTEGRITY OF ALL REQUIRED FIRE / SMOKE RATINGS <br />- INSTALL FIRESAFING AS REQUIRED FOR COMPLIANCE (SEE SHEET <br />A600 FOR FURTHER CLARIFICATION), AND LEAD LINING <br />REQUIREMENTS. <br />I. MAKE NECESSARY ADJUSTMENTS TO GWB PARTITIONS, IN ORDER TO <br />ACCOMMODATE NEW RECESSED CABLE DUCTS/CONDUITS. PATCH AND <br />MATCH REMAINING ADJACENT SURFACES - RADIATION SHIELDING SHALL <br />COMPLY WITH SHIELDING PLAN. SEE DETAIL C2/A201 E FOR FURTHER <br />INFORMATION. <br />J. WALLS SHOWN IN ALIGNMENT ARE TO ALIGN WITH FINISHED SURFACE. <br />K. PROVIDE AND INSTALL FLORIDA BUILDING CODE APPROVED <br />SUBTERRAINIAN TERMITICIDE AT ALL COMPACTED SOIL TO BE COVERED <br />WITH CONCRETE FLOOR SLAB. RETREAT ALL AREAS DISTURBED BY PIPE <br />AND CONDUIT INSTALLATION, OR OTHER CONSTRUCTION WORK, PRIOR TO <br />NEW SLAB INSTALLATION. CONTRACTOR TO VERIFY TERMITICIDE <br />INSTALLATION IS IN COMPLIANCE WITH FLORIDA BUILDING CODE SECTION <br />1816, AND THAT WORK IS PERFORMED BY CERTIFIED PERSONNEL ONLY. <br />?0 <br />)(FIA0.) A IN (C"'ER <br />SPEC 1 A L I T. <br />Research InsUtute <br />Key Plan <br />MARK ISSUE DATE DESCRIPTION <br />Issue Log <br />JOHN P. SAL`f - AR 92309 <br />FLORIDA CANCER SPECIALISTS <br />EQUIPMENT REPLACEMENT <br />38010 MEDICAL CENTER AVE. <br />ZEPHYRHILLS, FL 33540 <br />Drawing Title <br />GENERAL DEMOLITION NOTES, <br />PARTITION TYPES, DETAILS, <br />AND FINISH SCHEDULE <br />Commission No. <br />71604 <br />Date Issued 07/01/16 <br />Scale <br />AS NOTED <br />Sheet Number <br />A001 <br />Drawn By C2 <br />Approved By J� <br />Filename 71604 - A001 <br />SolWo, LLC 2007 <br />