0
<br />4
<br />0
<br />o
<br />Z21
<br />co
<br />N
<br />co _ _ _ 120 Vac
<br />Wht/Blk
<br />~� h 0-30 V do
<br />h
<br />Orange ICnmm
<br />--- Wh I
<br />0
<br />r- ----------------- 4
<br />1 24V
<br />I I
<br />1 I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I � I
<br />I I
<br />I I
<br />I I
<br />I L-t I
<br />O I
<br />I
<br />y jCONCEALED 3/8" FLEX W/3
<br />I 11 2 EMT W/3 #12 THHN CU
<br />l X�y #12 THHN CU
<br />r -t
<br />I I
<br />+ - - +
<br />FROM BRANCH CIRCUIT TO EXHAUST FAN
<br />SPEED CONTROL PROVIDED BY
<br />O MECHANICAL CONTRACTOR AND
<br />INSTALLED BY ELECTRICAL CONTRACTOR
<br />2 4" SQ BOX W/EXTENSION RING
<br />& 1 G SWITCH RS COVER
<br />O RIBUIS PILOT CONTROL RELAY PROVIDED BY
<br />MECHANICAL CONTRACTOR AND INSTALLED BY
<br />ELECTRICAL CONTRACTOR
<br />® THERMOTSAT CABLE P&I MECHANICAL CONTRACTOR
<br />EXHAUST FAN
<br />CONTROL DETAIL
<br />Tvrow
<br />EACH TV SYMBOL Q REPRESENTS PROVIDING AND INSTALLING A
<br />RECESSED TV BOX WITH A TERMINATED DATA AND/OR COAXIAL JACK AS
<br />PER RISER DIAGRAM.
<br />THE SYMBOL ALSO REPRESENTS PROVIDING AND INSTALLING A DUPLEX
<br />RECEPTACLE AS SCHEDULED THAT IS NOT SHOWN ON THE PLANS AND
<br />SHALL BE CIRCUITED AS SHOWN OR CONNECTED TO AN ADJACENT
<br />UN -SWITCHED RECEPTACLE CIRCUIT. THE RECEPTACLE SHALL BE
<br />TAMPER RESISTANT IF IN A RESIDENTIAL OR LODGING OCCUPANCY.
<br />THE BOX SHALL BE INSTALLED AT THE HEIGHT PER ARCHITECTURAL
<br />ELEVATIONS AND SHALL BE INSTALLED SO IT IS FULLY HIDDEN BEHIND
<br />THE FLUSH MOUNTED TV WHERE IT DOES NOT INTERFERE WITH THE
<br />MOUNTING SYSTEM.
<br />THIS RECEPTACLE SHALL BE LOCATED AT LEAST 6' FROM ANY WET
<br />AREA THAT WOULD REQUIRE A GFI RECEPTACLE AND IT IS NOT TO BE
<br />INCLUDED AS A CODE REQUIRED RECEPTACLE OR ACCESSIBLE.
<br />CONTRACTOR SHALL PROVIDE THE APPROPRIATE BOX AND/OR
<br />FIREPROOFING TO MAINTAIN FIRE RATING OF WALL IF APPLICABLE.
<br />TV CONFECTION
<br />TELEPHONE BOARD
<br />1 1/2" x 2' STRUT W/STRAPS
<br />2" EMT W/BUSHING BOTH ENDS
<br />ARLINGTON GBB50 GROUND BAR
<br />GROUNDING CONDUCTOR
<br />48' READYSPEC BACKBOARD —
<br />BRANCH CIRCUIT
<br />QUAD RECEPTACLE 0 48" TOE-
<br />CAP
<br />4" 2 HOLE STRAP
<br />4" x 25" PVC
<br />GLUE CAP TO PIPE & DRILL
<br />3-1/4" DRAIN HOLES
<br />AS BUILT
<br />HOLDER
<br />DRAWING SYMBOLS
<br />1 SECTION NUMBER
<br />2 3 DRAWING NUMBER DRAW
<br />DRAWING NUMBER CUT
<br />® NOTE
<br />NEC 70
<br />THE ENGINEER OF RECORD HAS DESIGNED THIS PROJECT
<br />TO MEET THE MINIMUM STANDARDS SET FORTH BY THE
<br />NATIONAL ELECTRICAL CODE, 2014.
<br />AS THE STATE OF FLORIDA HAS ADOPTED THE 2008 NEC,
<br />THE INSTALLATION SHALL MEET ANY 2008 CODE SECTION IF
<br />MORE STRINGENT.
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />I I
<br />1
<br />I I
<br />I I
<br />I I
<br />I O I
<br />y i CONCEALED3/8" FLEX W/3
<br />1�2W/3
<br />I I #12 THHN CU
<br />l X,y #12 THHN CU
<br />I I
<br />+
<br />FROM BRANCH CIRCUIT TO EXHAUST FAN
<br />SPEED CONTROL PROVIDED BY
<br />O MECHANICAL CONTRACTOR AND
<br />INSTALLED BY ELECTRICAL CONTRACTOR
<br />2 4" SQ BOX W/EXTENSION RING
<br />& 2G SWITCH IRS COVER
<br />30 MOTOR STARTING SWITCH, Sm
<br />EXHAUST FAN
<br />DISCONNECT DETAIL
<br />WORKING SPACE
<br />ELIECMICAL
<br />ROOM
<br />NO STORAGE PERMMED
<br />L 'ii":'- i`" - INSTALL THIS SIGN
<br />INSTALL THIS SIGN ON ON THE EXTERIOR
<br />A PANEL IN EACH OF EACH
<br />ELECTRICAL ROOM ELECTRICAL ROOM
<br />6' ABOVE EQUIPMENT OR STRUCTURAL
<br />CEILING
<br />INSTALL 2' RED AND WHITE FLOOR
<br />TAPE, BRADY TOUGHSTRIP #104318,
<br />36"/42" DEEP AND WIDTH OF
<br />ELECTRICAL EQUIPMENT
<br />30" MINIMUM OR WIDTH OF EQUIPMENT
<br />36" FOR VOLTAGE LESS THAN 300V
<br />42" FOR VOLTAGE MORE THAN 300V
<br />NEC 110.26(E)- THE SPACE EQUAL TO THE WIDTH AND
<br />DEPTH OF THE EQUIPMENT AND EXTENDING TO A HEIGHT OF
<br />6' ABOVE THE EQUIPMENT SHALL BE DEDICATED TO THE
<br />ELECTRICAL INSTALLATION.
<br />DATACOM LEGEND
<br />D11 DEVICE DATA, 3/4" EMT & 4"SQ W/SG PLASTER RING
<br />D2 2 DEVICE DATA, 3/4" EMT & 4-SQ W/2G PLASTER RING
<br />D4 4 DEVICE DATA, 1" EMT & 4"SQ W/2G PLASTER RING
<br />0 2 DEVICE VOICE/DATA, 3/4" EMT & 4"SQ W/SG PLASTER
<br />RING
<br />CONDUIT OR CHASE INSTALLATION
<br />P&I EMT FROM DEVICE ® 16" BOB TO ACCESSIBLE
<br />® CEILING SPACE, W/90 AT EXTERIOR WALLS ONLY &
<br />INSTALL ARLINGTON EMT INSULATING BUSHING
<br />P&I HUBBELL LOW VOLTAGE MOUNTING PLATE #8017 AT
<br />16" BOB W/PULL STRING TO ACCESSIBLE CEILING SPACE
<br />CONDUCTOR AND DEVICE INSTALLATION
<br />® CONDUCTORS AND DEVICE TERMINATIONS ARE BY OTHERS
<br />P&I ONE CAT6 CONDUCTOR FROM EACH DEVICE TO DATA
<br />❑ BOARD. PULL CABLE TO FLOOR AT BOTH ENDS AND
<br />CUT. TERMINATE DEVICE W/ CAT6A RJ45 DEVICE AND
<br />IDENTIFY EACH CONDUCTOR AT BOTH ENDS
<br />LINETYPE LEGEND
<br />HOMERUN - LION, I" CONDUIT W/3 #12 THHN
<br />LP CU CONCEALED IN WALL OR ABOVE CEILING
<br />WITH PANEL AND CIRCUIT NUMBER SHOWN
<br />EXISTING CONDUIT
<br />FLEXIBLE CONDUIT
<br />LUMINAIRE SWITCHLEG
<br />CAT 6A CABLING
<br />FIRE ALARM LEGEND
<br />© PULL STATION
<br />❑Q HORN
<br />® STROBE
<br />HORN/STROBE
<br />CHIME STROBE
<br />VOICE EVACUATION SPEAKER/STROBE
<br />QQ VOICE EVACUATION SPEAKER
<br />OO HEAT DETECTOR
<br />�z SMOKE DETECTOR
<br />co CARBON MONOXIDE DETECTOR
<br />® SMOKE ALARM
<br />® SMOKE ALARM W/CARBON MONOXIDE BASE
<br />DUCT SMOKE DETECTOR
<br />FLOW SWITCH
<br />TAMPER SWITCH
<br />FCP FIRE ALARM CONTROL PANEL
<br />EEI FIRE SYSTEM REMOTE ANNUCIATOR
<br />Erc FIRE ALARM TERMINATION CABINET
<br />FN—Acfl NOTIFICATION APPLIANCES POWER SUPPLY
<br />® SHUT DOWN RELAY
<br />Q DOOR HOLDER
<br />IR ISOLATION RELAY
<br />® REMOTE ALARM INDICATOR WITH TEST SWITCH
<br />IAM INDIVIDUAL ADDRESSABLE RELAY MODULE
<br />FIRE DAMPER, FURNISHED BY DIVISION 15
<br />SMOKE DAMPER, FURNISHED BY DIVISION 15
<br />Off— FIRE/SMOKE DAMPER, FURNISHED BY DIVISION 15
<br />FIRE SERVICE COMM. JACK. mi
<br />©FIRE SERVICE COMM. HANDSET.
<br />H
<br />RRR RESPONDER RADIO REPEATER
<br />sA� SURGE ARRESTOR, COMM., DITEK MRJ31 XSCPWP
<br />® SURGE ARRESTOR, DEVICES, DITEK 2MHLP36B
<br />® SURGE ARRESTOR, POWER, DITEK 120HW
<br />❑s PULL STATION INSIDE SIGN
<br />IVIC CABLE
<br />MC CABLE IS ALLOWED ON THIS PROJECT SUBJECT TO THE
<br />LIMITATIONS SET FORTH BELOW AND ACCORDING TO PARAMETERS
<br />SET FORTH IN NEC 70 ARTICLE 330.
<br />1 MC CABLE CAN BE USED TO CONNECT LUMINAIRES
<br />INSTALLED WITHIN AN ACCESSIBLE CEILING TO A JUNCTION BOX
<br />WHEN THE LENGTH DOES NOT EXCEED SIX FEET. IN SUCH
<br />INSTALLATIONS, THE MC CABLE FITTINGS SHALL BE PERMITTED
<br />AS MEANS OF CABLE SUPPORT.
<br />2 MC CABLE CAN BE USED TO CONNECT DEVICES
<br />INSTALLED CONCEALED INSIDE A WALL CAVITY.
<br />3 MC CABLE CAN BE USED TO CONNECT THE LAST DEVICE
<br />IN A CIRCUIT TO A HOMERUN JUNCTION BOX MOUNTED ON OR
<br />ADJACENT TO THE FRAMING TOP PLATE.
<br />4 MC CABLE USE SHALL BE LIMITED TO #12 AND #10
<br />COPPER CONDUCTORS.
<br />5 MC CABLE SHALL BE INSTALLED PARALLEL OR
<br />PERPENDICULAR TO BUILDING LINES AND FRAMING MEMBERS.
<br />6 MC CABLE SHALL BE USED FOR BRANCH CIRCUITS ONLY.
<br />HOMERUNS SHALL BE IN CONDUIT.
<br />7 MC CABLE SHALL BE PROTECTED WHEN INSTALLED
<br />THROUGH OR RUN PARALLEL TO FRAMING MEMBERS SO THAT
<br />THE NEAREST OUTSIDE SURFACE IS AT LEAST 1 1/4" FROM
<br />THE NEAREST EDGE OF THE FRAMING MEMBER. WHEN THIS
<br />DISTANCE CAN NOT BE MAINTAINED, THE CABLE SHALL BE
<br />PROTECTED FROM SCREW OR NAIL PENETRATION BY A STEEL
<br />PLATE, SLEEVE OR EQUIVALENT OF AT LEAST 1/16" THICK.
<br />8 THE RADIUS OF INNER BEND IN CORRUGATED SHEATH MC
<br />CABLE SHALL BE GREATER THAN 4" FOR MC CABLE CONTAINING
<br />#12 CONDUCTORS AND 4.5" FOR MC CABLE CONTAINING #10
<br />CONDUCTORS.
<br />9 MC CABLES SHALL BE SUPPORTED AT LEAST EVERY 6' &
<br />WITHIN 12" OF EVERY BOX, FITTING OR OTHER TERMINATION.
<br />10 MC CABLE SHALL BE REPLACED WHEN THE CORRUGATED
<br />SHEATH HAS SEPARATED AND IS NO LONGER INTERLOCKED.
<br />11 MEDICAL GRADE MC CABLE SHALL BE USED IN PATIENT
<br />CARE SPACES BUT NOT IN BUSINESS OFFICES, CORRIDORS,
<br />LOUNGES, WAITING ROOMS AND SIMILAR AREAS PER 517.10(B).
<br />LEGEND
<br />q �°
<br />2'x4' CEILING MOUNT
<br />A[
<br />2'X2' CEILING MOUNT
<br />A 0
<br />1'X4' CEILING MOUNT
<br />A��° -
<br />4' WALL MOUNT
<br />AO
<br />CEILING MOUNT
<br />A Q
<br />WALL MOUNT
<br />A ❑
<br />CEILING MOUNT
<br />A Csl
<br />WALL MOUNT
<br />A I--�-I
<br />SURFACE MOUNT STRIP
<br />X ® t X
<br />EXIT SIGN, SINGLE OR DOUBLE FACE
<br />WALL MOUNT BATTERY EGRESS
<br />q v v v
<br />TRACK LIGHTING
<br />LIGHTING CONTROLS
<br />INSTALL FULL NEUTRAL TO ALL SWITCHING DEVICES.
<br />INSTALL ALL AT 48" AFF TOB.
<br />$ SINGLE POLE, 20A, 120/277V, LEVITON CS1202
<br />$3 THREE WAY, 20A, 120/277V, LEVITON CS3202
<br />$4 FOUR WAY, 20A, 120/277V, LEVITON CS4202
<br />$D 0 - 10V DIMMER
<br />$T TWIST TIMER, 5 MINUTE, NO HOLD, INTERMATIC FF5M
<br />Pc PHOTOCELL, TORK K2101
<br />Ej TIME SWITCH, TORK DZS200BP
<br />$p SWITCH WITH PILOT LIGHT. LEVITON 1221-PLR
<br />$m MOTOR STARTING SWITCH. LEVITON MS302/3
<br />os CEILING MOUNT LINE VOLTAGE OCCUPANCY SENSOR
<br />WATTSTOPPER DT-355
<br />os WALL MOUNT LINE VOLTAGE OCCUPANCY SENSOR
<br />WATTSTOPPER WS-250
<br />ED WALL MOUNT LINE VOLTAGE FAN/LIGHT OCCUPANCY
<br />SENSOR SENSORSWITCH WSD PDT 2P FAN
<br />os CEILING MOUNT LOW VOLTAGE OCCUPANCY SENSOR
<br />WATTSTOPPER DT-300
<br />os WALL MOUNT LOW VOLTAGE OCCUPANCY SENSOR
<br />WATTSTOPPER DW-100
<br />pp LOW VOLTAGE OCCUPANCY SENSOR POWER PACK
<br />WATTSTOPPER BZ-50
<br />4> CEILING MOUNT LOW VOLTAGE DAYLIGHTING SENSOR
<br />WATTSTOPPER LS-301
<br />DAYLIGHTING REMOTE CONTROLLER
<br />WATTSTOPPER LRS-301S
<br />1
<br />SHADED SYMBOLS INDICATE LUMINAIRES PROVIDED WITH
<br />EMERGENCY BACKUP POWER AND ARE SHOWN AS
<br />LIFE SAFETY BRANCH CIRCUIT
<br />CRITICAL BRANCH CIRCUIT
<br />BATTERY BACK UPEM
<br />SYMBOLS SHOWN WITH DASHED LINES INDICATE EXISTING
<br />WHERE THE SUBSCRIPTS INDICATE THE FOLLOWING:
<br />ER - Existing to Remain
<br />XD - eXisting to be Demolished
<br />EL - Existing to be reLocated
<br />EP - Existing to be rePlaced
<br />Mc
<br />N_
<br />� J �
<br />kh ME 6' TOTAL LENGTH
<br />NE 3'
<br />M
<br />TT
<br />UQUIDTIGHT w/o 11ERL
<br />I PC to EVERY 10' ILIC
<br />�- we
<br />e e e�—
<br />, , 2 1/2'-3' 6' ,
<br />T 3 1/2'-5' 7' I
<br />STRAPPING
<br />ABBREVIATIONS
<br />A
<br />AMPERE
<br />AC
<br />ABOVE COUNTER
<br />AF
<br />AMPERE FRAME
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />AFCI
<br />ARC -FAULT CIRCUIT INTERRUPTER
<br />AFG
<br />ABOVE FINISHED GRADE
<br />AHU
<br />AIR HANDLING UNIT
<br />AIC
<br />AMPS INTERRUPTING CAPACITY
<br />AL
<br />ALUMINUM
<br />ATS
<br />AUTOMATIC TRANSFER SWITCH
<br />A/V
<br />AUDIO/VISUAL
<br />AWG
<br />AMERICAN WIRE GAUGE
<br />BOB
<br />BOTTOM OF BOX
<br />C
<br />CONDUIT
<br />CAT
<br />CATEGORY
<br />CB
<br />CIRCUIT BREAKER
<br />CH
<br />CHILLER
<br />CKT
<br />CIRCUIT
<br />CL
<br />CENTER LINE
<br />CLG
<br />CEILING
<br />CU
<br />COPPER
<br />DWG
<br />DRAWING
<br />EG, EGG
<br />EQUIPMENT GROUND BAR
<br />EC
<br />ELECTRICAL CONTRACTOR
<br />EF
<br />EXHAUST FAN
<br />EM
<br />EMERGENCY
<br />EMT
<br />ELECTRICAL METALLIC TUBING
<br />ENCL
<br />ENCLOSURE
<br />EWH
<br />ELECTRIC WATER HEATER
<br />EXIST, EX
<br />EXISTING
<br />FA
<br />FIRE ALARM
<br />FBO
<br />FURNISHED BY OWNER
<br />FCP
<br />FIRE ALARM CONTROL PANEL
<br />FACC
<br />FIRE ALARM COMMAND CENTER
<br />FATC
<br />FIRE ALARM TERMINAL CABINET
<br />FO
<br />FIBER OPTIC
<br />GFI, GFCI
<br />GROUND FAULT CIRCUIT INTERRUPTER
<br />GND,G
<br />GROUND
<br />HOA
<br />HAND -OFF -AUTO
<br />HACR
<br />HEATING/AIR CONDITIONING -RATED
<br />HID
<br />HIGH INTENSITY DISCHARGE
<br />HPF
<br />HIGH POWER FACTOR
<br />HIPS
<br />HIGH PRESSURE SODIUM
<br />HP
<br />HORSEPOWER
<br />IG
<br />ISOLATED GROUND
<br />IPTV
<br />INTERNET PROTOCOL TELEVISION
<br />J, JB
<br />JUNCTION BOX
<br />KCMIL
<br />THOUSAND CIRCULAR MILS
<br />KVA
<br />KILOVOLT AMPERE
<br />KW
<br />KILOWATT
<br />MCB
<br />MAIN CIRCUIT BREAKER
<br />MCC
<br />MOTOR CONTROL CENTER
<br />MDP
<br />MAIN DISTRIBUTION PANEL
<br />MH
<br />METAL HALIDE
<br />MLO
<br />MAIN LUGS ONLY
<br />MTD
<br />MOUNTED
<br />NC
<br />NORMALLY CLOSED
<br />NEC
<br />NATIONAL ELECTRICAL CODE
<br />NEMA
<br />NATIONAL ELECTRICAL MANUF. ASSOCIATION
<br />NF
<br />NON -FUSED
<br />NFPA
<br />NATIONAL FIRE PROTECTION ASSOCIATION
<br />NIC
<br />NOT IN CONTRACT
<br />NL
<br />NIGHT LIGHT
<br />NO
<br />NORMALLY OPEN
<br />NTE
<br />NOT TO EXCEED
<br />0
<br />PHASE
<br />POE
<br />POWER OVER ETHERNET
<br />P&I
<br />PROVIDE AND INSTALL
<br />PB
<br />PUSHBUTTON
<br />PC
<br />PHOTOCELL
<br />PNL
<br />PANEL
<br />POTS
<br />PLAIN OLE TELEPHONE SYSTEM
<br />PVC
<br />POLYVINYL CHLORIDE CONDUIT
<br />RGS
<br />RIGID GALVANIZED STEEL CONDUIT
<br />SCA
<br />SHORT CIRCUIT AVAILABLE AMPS
<br />SG
<br />SINGLE GANG
<br />SPD
<br />SURGE PROTECTIVE DEVICE AS INDICATED
<br />STP
<br />SHIELDED TWISTED PAIR CABLE
<br />STR
<br />STRANDED WIRE
<br />SW
<br />SWITCH
<br />SWBD
<br />SWITCHBOARD
<br />TIC
<br />TIME CLOCK
<br />TOB
<br />TOP OF BOX
<br />TP
<br />TWISTED PAIR CABLE
<br />TR
<br />TAMPER RESITANT
<br />TS
<br />TIME SWITCH
<br />TYP
<br />TYPICAL
<br />UG
<br />UNDERGROUND
<br />UH
<br />UNIT HEATER
<br />UPS
<br />UNINTERRUPTIBLE POWER SUPPLY
<br />LION
<br />UNLESS OTHERWISE NOTED
<br />VAV
<br />VARIABLE AIR VOLUME
<br />VFD
<br />VARIABLE FREQUENCY DRIVE
<br />V
<br />VOLT
<br />WP
<br />WEATHER PROOF
<br />WR
<br />WEATHER RESISTANT
<br />XFMR
<br />TRANSFORMER
<br />2G
<br />TWO GANG
<br />DEVICE COLOR
<br />ALL DEVICES INCLUDING SWITCHES & RECEPTACLES ARE
<br />WHITE IN COLOR.
<br />ALL DEVICE PLATES ARE STAINLESS STEEL AND SHALL BE
<br />LABELED WITH PANEL AND CIRCUIT DESIGNATIONS.
<br />ALL DATACOM AND TV OUTLETS ARE WHITE.
<br />ELECTRIC NOTES
<br />1 CONTRACTOR SHALL BE LICENSED BY THE STATE OF FLORIDA ACCORDING TO CHAPTER
<br />489, FLORIDA STATUTES AND SHALL PROVIDE FOR AND ACQUIRE ALL NECESSARY
<br />PERMIT(S) AND INSPECTIONS AS MAY BE REQUIRED BY THE AUTHORITY(IES) HAVING
<br />JURISDICTION.
<br />2 INSTALLATION SHALL MEET OR EXCEED THE MINIMUM REQUIREMENTS OF THE FLORIDA
<br />BUILDING CODE, 2010 AND NFPA 70, NATIONAL ELECTRICAL CODE, 2014 UNLESS THE
<br />AN APPLICABLE SECTION OF THE ADOPTED NEC IS MORE STRINGENT.
<br />3 THE CONTRACTOR SHALL FURNISH ALL MATERIALS AND LABOR NECESSARY TO PROVIDE
<br />FOR THE INSTALLATION OF A COMPLETE ELECTRICAL DISTRIBUTION SYSTEM.
<br />4 THE CONTRACTOR SHALL MAKE A THOROUGH EXAMINATION OF THE SITE CONDITIONS
<br />AND CONTRACT DOCUMENTS.
<br />5 PRIOR TO COMMENCING WORK, THE CONTRACTOR SHALL COORDINATE WITH THE
<br />APPROPRIATE UTILITIES FOR METERING, TRANSFORMER AND SERVICE CONNECTION
<br />REQUIREMENTS.
<br />6 PROVIDE ANY AND ALL NECESSARY TEMPORARY CONNECTIONS OF EQUIPMENT,
<br />DEVICES OR LUMINAIRES AS MAY BE REQUIRED FOR CONSTRUCTION.
<br />7 CONDUIT SHALL BE INSTALLED CONCEALED, RECESSED AND IN A NEAT AND
<br />WORKMANLIKE MANNER. ALL CONDUIT SHALL BE INSTALLED PARALLEL OR
<br />PERPENDICULAR TO BUILDING LINES. EXPOSED CONDUIT ON EXTERIOR WALLS ON
<br />FINISHED WALLS IS PROHIBITED.
<br />8 CONDUIT SHALL BE EMT AND FITTINGS SHALL BE STEEL. FOR UNDERGROUND AND
<br />UNDER SLAB INSTALLATIONS, CONDUIT SHALL BE PVC OR IMC W/AN ASPHALTIC
<br />COATING. ENT OR "SMURF" TUBING IS NOT APPROVED.
<br />9 ALL CONDUIT CUT ENDS SHALL BE REAMED PER NEC 358.28.
<br />10 SEAL ALL CONDUITS WHERE THE CONDUIT CONNECTS AN INTERIOR CONDUIT BODY TO
<br />AN EXTERIOR CONDUIT BODY OR LUMINAIRE.
<br />11 PVC CONDUIT INSTALLED UNDERGROUND SHALL BE A LEAST 12" UNDER SIDEWALKS,
<br />24" UNDER PARKING LOTS AND DRIVEWAYS AND 18" IN ALL OTHER LOCATIONS PER
<br />NEC TABLE 300.5.
<br />12 ALL UNDERGROUND CONDUITS AND CONDUCTORS SHALL BE MARKED WITH A WARNING
<br />RIBBON AT LEAST 12" ABOVE THE CONDUIT OR CONDUCTOR PER NEC 300.5(3).
<br />13 CONDUCTORS IN CONDUIT INSTALLED EXPOSED TO DIRECT SUNLIGHT SHOULD BE
<br />DE -RATED DEPENDING ON THE DISTANCE BETWEEN THE ROOF AND BOTTOM OF
<br />CONDUIT PER NEC 310.15(B)3(C) AND SHOULD BE INSTALLED USING THE
<br />APPROPRIATE SPACER.
<br />14 PROVIDE AN INDEPENDENT MEANS OF SUPPORT FOR CONDUIT INSTALLED ABOVE A
<br />CEILING WHERE THEY ARE DISTINGUISHABLE BY COLOR, TAGGING OR OTHER EFFECTIVE
<br />MEANS. THE CEILING SUPPORT SYSTEM SHALL BE PERMITTED TO SUPPORT BRANCH
<br />CIRCUIT WIRING WHERE INSTALLED IN ACCORDANCE WITH THE CEILING
<br />MANUFACTURER'S INSTRUCTIONS.
<br />15 PROVIDE A MINIMUM 1 1/2" SPACE BETWEEN METAL CORRUGATED SHEET ROOF
<br />DECKING AND ANY CABLE, CONDUCT OR BOX PER NEC 300.4(E).
<br />16 PROVIDE AN INSULATED THROAT FITTING OR PLASTIC BUSHING FOR ALL 1" AND
<br />LARGER CONDUIT TERMINATIONS IN PANEL BOARDS, LOAD CENTERS, WIREWAYS AND
<br />DISCONNECT SWITCHES.
<br />17 PROVIDE GROUNDING BUSHINGS FOR ANY CONDUIT TERMINATIONS AT CONCENTRIC
<br />KNOCKOUTS OR WHEN REDUCING WASHERS ARE USED. BOND ALL JUNCTION AND
<br />PULL BOXES TO GROUND.
<br />18 ALL WIRE SHALL BE COPPER, THHN, THWN OR XHHW. MINIMUM WIRE SIZE IS #12.
<br />AMPACITIES ARE CALCULATED USING THE 75'C COLUMN.
<br />19 ALL 20 AMP BRANCH CIRCUIT HOMERUNS OVER 100 FEET SHALL BE #10. SEE
<br />SCHEDULE THIS SHEET FOR LENGTH LIMITATIONS.
<br />20 ALL WIRING DEVICES SHALL BE TERMINATED AT THE SCREW IN A CLOCKWISE
<br />DIRECTION. THE PUSH -IN TERMINATIONS SHALL NOT BE USED.
<br />21 VOLTAGE DROP SHALL NOT EXCEED 2% FOR BRANCH AND 2% FOR FEEDER CIRCUITS.
<br />22 ALL CONDUCTORS SHALL BE COLOR CODED AS PER THE INDUSTRY STANDARD.
<br />120/208V 277/480V
<br />PHASE A BLACK BROWN
<br />PHASE B RED ORANGE
<br />PHASE C BLUE YELLOW
<br />23 INSTALL A FULL SIZE NEUTRAL TO ALL DEVICES INCLUDING SWITCHES.
<br />24 TERMINATE NO MORE THAN ONE WIRE PER TERMINAL PER NEC 110.14A.
<br />25 CONDUCTORS SHALL BE TWISTED TOGETHER PRIOR TO INSTALLATION OF TWIST ON
<br />CONNECTORS.
<br />26 REFER TO DATA/COMM DETAIL FOR EXTENT OF INSTALLATION REQUIRED.
<br />27 ALL BOXES SHALL BE A 4" SQUARE METAL BOX WITH THE APPROPRIATE RING. THE
<br />MAXIMUM GAP AROUND ANY RECESSED BOX SHALL NOT EXCEED 1/8" AND THE
<br />MAXIMUM SETBACK SHALL NOT EXCEED 1/4" PER NEC 314.20 & 314.21.
<br />28 TO MEET ADA GUIDELINES AND MAINTAIN COURSE SPACING, ELECTRICAL OUTLET BOXES
<br />SHALL BE INSTALLED 48" TO TOP OF BOX OR 16" TO BOTTOM OF BOX. OUTLET
<br />BOXES INSTALLED OVER COUNTERS SHALL BE INSTALLED AT 42" TO BOTTOM OF BOX.
<br />29 VERIFY DOOR SWINGS AND BACKSPLASH HEIGHTS AT ROUGH IN.
<br />30 STAGGER BACK TO BACK WALL BOXES IN ALL WALLS BY AT LEAST ONE STUD.
<br />31 PROVIDE TAMPER RESISTANT AND WEATHER RESISTANT RECEPTACLES WHERE REQUIRED
<br />BY NEC 406.4.
<br />32 PROVIDE IN USE COVERS FOR ELECTRICAL DEVICES INSTALLED IN DAMP AND WET
<br />AREAS WITH THE APPROPRIATE DUTY PER NEC 406.9.
<br />33 ALL PANEL BOARD BUS SHALL BE COPPER.
<br />34 EACH LOAD CENTER AND DISCONNECTING MEANS SHALL BE MARKED TO INDICATE ITS
<br />PURPOSE, FEED, AND OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
<br />INVOLVED PER NEC 110.22.
<br />35 PROVIDE A TYPED PANEL SCHEDULE REFLECTING INSTALLED CONDITIONS FOR ALL
<br />PANEL BOARDS WITH "SPACE" OR "SPARE" WRITTEN IN PENCIL.
<br />36 INSTALL LOAD CENTERS AND DISCONNECTS SO THAT AT LEAST 3% FEET OF WORKING
<br />SPACE CAN BE MAINTAINED PER NEC 110.26 AND DETAIL THIS SHEET.
<br />37 EQUIPMENT SHALL NOT PROTRUDE MORE THAN 6" INTO THE REQUIRED WORKING
<br />SPACE AROUND ELECTRICAL EQUIPMENT.
<br />38 "TYPICAL" NOTES APPLY TO ALL SIMILAR SITUATIONS.
<br />39 PROVIDE A DISCONNECTING MEANS FOR EACH WATER HEATER PER FPC 504.3.
<br />40 LABEL WITH A SHARPIE ALL JUNCTION BOX COVERS WITH CIRCUITS DESIGNATION
<br />CONTAINED WITHIN.
<br />41 PROVIDE OPERATING AND INSTALLATION INSTRUCTIONS TO THE OWNER FOR ALL
<br />INSTALLED EQUIPMENT.
<br />42 DEVICES IN VICINITY OF GAS CYLINDERS SHALL BE AT INSTALLED 60" TO BOTTOM OF
<br />BOX PER NFPA 99.
<br />43 AN FS BOX IS NOT APPROVED AS A SUPPORT FOR A LUMINAIRE.
<br />44 PROVIDE A DISCONNECTING MEANS IN ALL FLUORESCENT LUMINAIRES THAT ARE
<br />INSTALLED NEW OR REPAIRED.
<br />45 LUMINAIRES INSTALLED IN SUSPENDED CEILINGS SHALL BE FASTENED TO THE
<br />CEILING FRAMING MEMBERS IN ACCORDANCE WITH NEC 410.36.
<br />46 PROVIDE DOCUMENTATION WITH CLOSE OUT DOCUMENT PROVING THAT ANY AND ALL
<br />BALLASTS AND LAMPS HAVE BEEN RECYCLED BY AN APPROVED RECYCLING VENDOR.
<br />47 PROVIDE THE APPROPRIATE FIRE STOP SYSTEM AND/OR FIRE CAULK AT ANY
<br />PENETRATION OF A RATED VERTICAL ASSEMBLY.
<br />48 PENETRATIONS OF A RATED HORIZONTAL ASSEMBLY WITH A METAL CONDUIT NOT
<br />EXCEEDING 6 INCH NOMINAL DIAMETER, INSTALL CONCRETE, GROUT, OR MORTAR THE
<br />FULL THICKNESS OF THE FLOOR AS REQUIRED BY FBC 713.4.1.1 SO TO MAINTAIN
<br />THE FIRE RESISTANCE RATING. FOR MULTIPLE PENETRATIONS, REFER TO THE
<br />FLORIDA BUILDING CODE.
<br />49 ALL JUNCTION BOXES ARE TO BE ACCESSIBLE PER NEC ARTICLE 100.
<br />50 NOT ALL ITEMS, NOTES, DETAILS, ABBREVIATIONS, SCHEDULES AND LEGENDS ON THE
<br />SHEET MAY BE APPLICABLE TO THIS PROJECT.
<br />51 CONDUIT TERMINATION AT NEMA3R ENCLOSURES SHALL BE WITH MYERS HUBS FOR
<br />TOP PENETRATIONS AND LIQUID TIGHT SEALING RINGS OR SEALING LOCKNUTS FOR
<br />BOTTOM AND SIDE PENETRATIONS.
<br />52 FOR ALL LUMINAIRES INSTALLED IN A CEILING GRID SYSTEM, INSTALL LISTED CLIPS
<br />SECURELY FASTENING THE LUMINAIRE TO THE CEILING FRAMING MEMBERS PER NEC
<br />70-410.36(8).
<br />53 SET ED FOR FAN TO RUN 10 MINUTES AFTER LIGHTS ARE TURNED OFF.
<br />POWER LEGEND
<br />MH MANHOLE
<br />® HAND HOLE
<br />O JUNCTION BOX
<br />HP ELECTRIC MOTOR
<br />FS-P-D-1 SURGE PROTECTION DEVICE
<br />Q PUSHBUTTON 48" AFF TOB
<br />F551 ACCESSIBLE DOOR OPENER 48" AFF TOB
<br />996 480/277V PANEL BOARD
<br />G 208Y/120V THREE 0 PANEL BOARD
<br />61 120/240 SINGLE 0 LOAD CENTER
<br />120/240 THREE 0 HIGH LEG LOAD CENTER. TERMINATE
<br />G HIGH LEG ON "C" PHASE IN THE METER AND "B" PHASE
<br />IN THE PANEL BOARD
<br />6 MISCELLANEOUS PANEL BOARD
<br />TRANSFORMER & ENCLOSURE
<br />DISCONNECT, NON FUSIBLE.
<br />MOUNT 48" AFF CENTER
<br />DISCONNECT, FUSED,
<br />MOUNT 48" AFF CENTER
<br />FUSED COMBINATION STARTER/DISCONNECT
<br />MOUNT AT 48" AFF CENTER
<br />8 MOTOR STARTER MOUNT AT 48" AFF CENTER
<br />® VFD - VARIABLE FREQUENCY DRIVE
<br />MOUNT AT 48" AFF CENTER
<br />17W ENCLOSED CIRCUIT BREAKER
<br />DEVICE LEGEND
<br />ALL DEVICES ARE INSTALLED 16" AFF 808 UON.
<br />ABOVE COUNTER DEVICES ARE INDICATED BY INTERIOR SHADING AND ARE
<br />INSTALLED AT 42" AFF BOB UON.
<br />RECEPTACLE, 20A, LEVITON CR20
<br />RECEPTACLE, AC, 20A, LEVITON CR20
<br />RECEPTACLE, ISOLATED GROUND, 20A, LEVITON IG5362
<br />DECORA, TAMPER RESISTANT, 20A, LEVITON TBR20
<br />TR
<br />DECORA, TAMPER RESISTANT, USB, 20A, LEVITON T5832
<br />USB I I
<br />DECORA, GFCI, WEATHER RESISTANT, 20A, LEVITON WR899
<br />WPr' DECORA GFCI, TAMPER & WEATHER RESISTANT, 20A,
<br />LEVITON WT899
<br />GFI
<br />TT
<br />QUAD RECEPTACLE - DOUBLE DUPLEX, 20A, 120V
<br />QUAD RECEPTACLE, AC, W/1 USB RECEPTACLE
<br />UP
<br />® SPECIAL RECEPTACLE
<br />SWITCH CONTROLLED DUPLEX RECEPTACLE, 20A, 120V
<br />w/ CONTROLLED RECEPTACLE MARKING PER 406(E)
<br />® DUPLEX RECEPTACLE IN FLOOR BOX
<br />® QUAD RECEPTACLE IN FLOOR BOX
<br />---]DUPLEX RECEPTACLE AND DATA IN FLOOR BOX
<br />-T QUAD RECEPTACLE AND DATA IN FLOOR BOX
<br />DRP 30A, 240V, 4 WIRE DRYER RECEPTACLE, LEVITON 279
<br />RP 50A, 240V, 4 WIRE RANGE RECEPTACLE, LEVITON 278
<br />f' TWIST LOCK RECEPTACLE, NEMA LX-XXR
<br />Q CLOCK RECEPTACLE, LEVITON 5261-CH @ 96" BOB
<br />DRAWING INDEX
<br />E-1.0 LEGEND, ABBREVIATIONS AND GENERAL NOTES
<br />E-2.0 ELECTRICAL RISER DIAGRAM DEMOLITION
<br />E-3.0 LIGHTING PLAN
<br />E-4.0 POWER PLAN
<br />E-5.0 PANEL SCHEDULE AND ELECTRICAL RISER
<br />E-6.0 FIRE ALARM SYSTEM
<br />p\N AR 13
<br />3 ,
<br />_ � l
<br />N.`L
<br />G � • . C.
<br />0"""DOVE
<br />Project No.
<br />151010
<br />NOT FOR CONSTRUCTION
<br />E1*0
<br />■
<br />� 1
<br />Z:\BH_PK Architects\151010 — FH (Zephyrhills) — Wellness Center\Design\151010_E1.0.dwg Monday, February 14, 2011 3:34:45 PM Shawn Jeffrey
<br />02015 BH/PK Architects, Inc.
<br />
|