MECHANICAL SPECIFICATIONS <br />SCOPE: THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE THE DRAWINGS AND SPECIFICATIONS BEFORE SUBMITTING A PROPOSAL. <br />ALL WORK SHALL BE IN ACCORDANCE WITH THE 2014 FLORIDA BUILDING CODES, WITH ALL AMENDMENTS, AND LOCAL CODES AND ORDINANCES. <br />INSTALLATION SHALL COMPLY WITH THE STANDARDS SET BY NFPA, ASHRAE, ASPE, SMACNA, NEC AND UL THE SYSTEMS, EQUIPMENT, DEVICES AND <br />ACCESSORIES SHALL BE INSTALLED, FINISHED, TESTED AND ADJUSTED FOR CONTINUOUS AND PROPER OPERATION. THE CONTRACTOR SHALL BE <br />RESPONSIBLE FOR HIS WORK FITTING IN PLACE AND SHALL COORDINATE WITH OTHER TRADES TO AVOID INTERFERENCE WITH THEIR WORK. THE <br />INFORMATION GIVEN HEREIN AND ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED, BUT ITS EXTREME ACCURACY IS NOT GUARANTEED. THE <br />DRAWINGS ARE DIAGRAMMATIC, INTENDED TO SHOW GENERAL ARRANGEMENT, CAPACITY AND LOCATION OF VARIOUS COMPONENTS, EQUIPMENTS, AND <br />DEVICES. IF WORK IS REQUIRED IN A MANNER TO MAKE IT IMPOSSIBLE TO PRODUCE FIRST CLASS WORK, OR SHOULD DISCREPANCIES APPEAR AMOUNG <br />THE CONTRACT DOCUMENTS, OR BETWEEN THE CONTRACT DOCUMENTS AND THE MANUFACTURER'S RECOMMENDATIONS,THE CONTRACTOR SHALL REQUEST <br />INTERPRETATION BEFORE PROCEDING WITH WORK. CONTRACTOR SHALL FURNISH AND INSTALL ALL MINOR ITEMS WHICH ARE OBVIOUSLY AND <br />REASONABLY NECESSARY TO COMPLETE THE INSTALLATION WHETHER OR NOT SPECIFIED IN THE DOCUMENTS. <br />REQUIRED COORDINATION: ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS AND PIPING (INCLUDING DIVIDED <br />DUCTS) AND TRANSITIONS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER. <br />CONSTRUCTION PLANS: IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED. <br />REQUIRED ACCESS: CONTRACTOR SHALL ENSURE THAT ALL EQUIPMENT AND DEVICES THAT REQUIRE REPLACEMENT, SERVICING, ADJUSTING OR <br />MAINTENANCE SHALL BE LOCATED TO ALLOW EASY ACCESS AND SPACE FOR REMOVAL OF INTERNAL ASSMBLIES, IF REQUIRED. CONTRACTOR SHALL <br />PROVIDE ACCESS PANELS WHERE REQUIRED TO ALLOW ACCESS, EVEN IF NOT INDICATED ON THE DRAWINGS AT NO ADDITIONAL COST TO OWNER. <br />WIND RESISTANCE: ALL EQUIPMENT, APPLIANCE AND SUPPORTS LOCATED EXTERIOR OF THE FACILITY SHALL BE INSTALLED TO RESIST WIND LOADS AS <br />DETAILED IN THE BUILDING CODE. <br />CUTTING AND PATCHING: ALL OPENINGS AROUND DUCT OR PIPE PENETRATIONS THROUGH SMOKE OR FIRE RATED FLOORS, CEILINGS OR WALLS SHALL <br />BE SEALED AIRTIGHT WITH MATERIALS HAVING A RATING EQUAL TO THE MATERIAL OF THE WALL, CEILING OR FLOOR PENETRATED. <br />EQUIPMENT TAGS: ALL EQUIPMENT WILL HAVE A PERMANENTLY FIXED ENGRAVE PHENOLIC LABEL CORRESPONDING TO THE EQUIPMENT TAG ON THE <br />ENGINEER'S DRAWINGS. <br />FIRESTOPPING: UL APPROVED MATERIALS AND METHODS SHALL PROTECT THE PENETRATIONS OF FIRE AND/OR SMOKE RATED WALLS, CEILINGS OR <br />FLOORS. THE RATING OF THE FIRESTOPPING SHALL EQUAL THE RATING OF THE RATED ASSEMBLY. ALL INSULATION SHALL HAVE COMPOSITE FIRE AND <br />SMOKE HAZARD RATINGS AS TESTED BY PROCEDURE ASTM E-84, NFPA-225, UL-723 NOT EXCEEDING: <br />FLAME SPREAD 25 SMOKE DEVELOPED 50 FUEL DISTRIBUTED 50 <br />ACCESSORIES SUCH AS ADHESIVE, MASTIC, CEMENTS AND TAPES SHALL HAVE THE SAME COMPONENT RATING AS LISTED ABOVE. <br />START-UP: CONTRACTOR SHALL STARTUP ALL EQUIPMENT AND FOLLOW THE MANUFACTURER'S START-UP PROCEDURES. <br />OPERATING AND MAINTENANCE DATA: SUBMIT THREE COPIES OF MANUFACTURER'S OPERATING AND MAINTENANCE INSTRUCTIONS AND SPARE PARTS LIST <br />FOR EACH PIECE OF EQUIPMENT. <br />CONDENSATE DRAIN PIPING: CONDENSATE DRAIN PIPING SHALL BE PVC TYPE DW `. DRAINS SHALL BE PITCHED NOT LESS THAN 1" IN 10'. RUNS <br />SHALL BE AS SHORT AS POSSIBLE WITHOUT ANY DIPS TO TRAP WATER AND INTERFERE WITH PROPER DRAINAGE. PROVIDE TRAPS AND CLEANOUTS AT <br />DRAIN PAN CONNECTIONS. RUN CONDENSATE DRAIN TO GRASSY AREA OR ROOF DRAIN <br />DIMENSIONAL DATA: ALL DUCTWORK DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. <br />SUPPLEMENTARY SUPPORTS: CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTARY STEEL REQUIRED TO SUSPEND MECHANICAL EQUIPMENT AND <br />MATERIALS, IN ORDER TO PROVIDE A 'VIBRATION -FREE" RIGID INSTALLATION. <br />JST DUCT <br />HVAC LEGEND <br />® SUPPLY AIR DIFFUSER OR GRILLE <br />RETURN/EXH. AIR REGISTER OR GRILLE <br />I NEW DUCTWORK, WITH SIZE LISTED <br />-� I FLEXIBLE DUCT <br />QT I THERMOSTAT BASE <br />0 ROUND, DIAMETER <br />AFF ABOVE FINISHED FLOOR <br />CFM I CUBIC FEET PER MINUTE <br />TYP TYPICAL - ITEM OR METHOD <br />Lyon I TAKEOFF WITH MANUAL VOLUME DAMPER <br />DIFFUSER TAG EQUIPMENT TAG <br />- AIRFLOW EQUIPMENT <br />450 CFM TYPE <br />RTU-1 <br />CD-12"� :EQUIPMENT <br />MARK_ NECK NUMBER <br />SIZE <br />DUCTWORK - GENERAL, FABRICATE AND INSTALL ALL DUCTWORK AND DUCT ACCESSORIES IN ACCORDANCE WITH THE LATEST EDITION OF SMACNA'S a ------- m----^ _ __T__ 100 CFM'' <br />WAC DUCT CONSTRUCTION STANDARDS -METAL AND FLEXIBLE, THE LATEST NFPA STANDARDS, AND THIS SPECIFICATION. THE MOST STRINGENT OF THESE CD=6nO <br />SHALL BE THE MINIMUM STANDARD. MINIMUM OF 1" PRESSURE CLASS RATING FOR ALL DUCTWORK. <br />ALL RESTROOM EXHAUST & FRESH AIR DUCTWORK SHALL BE GALVANIZED SNAPLOCK ROUND SHEET METAL <br />ALL SUPPLY & RETURN DUCTWORK SHALL BE R-6.0 RIGID FIBERGLASS DUCTBOARD (UL-181 AND 181A) WITH CLEANABLE AIRSIDE SURFACE AND _ r i150 CF ` ..! �� - I NOTE TO CONTRACTOR <br />EPA -APPROVED BIOCIDE (ANTI -MICROBIAL AGENT) IMPREGNATED IN MATTED AIR -SIDE SURFACE. o ICD-8" - - -- (( _— <br />I � IL i ON EXISTING CONDITIONS: <br />DUCTWORK INSTALLATION: ALL INTERIOR DUCTWORK SHALL BE SEALED TO SMACNA CLASS (A,B,C) REQUIREMENTS. PROVIDE DOUBLE THICKNESS TURNING <br />VANES IN ALL NINETY (90) DEGREE SQUARE ELBOWS. CONTRACTOR SHALL FURNISH AND INSTALL ALL DUCT OFFSETS AS REQUIRED TO CLEAR <br />INTERFERENCES WITH EXISTING BUILDING STRUCTURE, PIPES AND ELECTRICAL CONDUITS. FURNISH AND INSTALL ALL MISCELLANEOUS STEEL SUPPORTS <br />REQUIRED FOR HANGING AND SUPPORTING DUCTWORK UNLESS OTHERWISE NOTED. <br />VOLUME DAMPERS: DAMPERS SHALL BE PROVIDED IN THE BRANCHES OF THE DUCT SYSTEMS WHERE SHOWN ON DRAWINGS AND AS REQUIRED TO <br />PROPERLY REGULATE THE VOLUME OF AIR DELIVERED TO OR WITHDRAWN FROM THE OUTLETS. <br />FLEXIBLE DUCTWORK: FLEXIBLE DUCTWORK MAY BE USED FOR THE FINAL RUNOUTS TO AIR OUTLETS, AND SHALL BE SIZED TO MATCH AIR OUTLET <br />NECK. FLEXIBLE DUCTS SHALL NOT EXCEED 8-FEET LENGTHS. NO FLEXIBLE DUCTS SHALL PENETRATE FIRE -RATED WALLS OR CEILINGS. FLEXIBLE <br />DUCTS SHALL COMPLY WITH THE PROVISIONS OF UL-181 CLASS 1 AIR DUCT MATERIAL DUCTS SHALL BE FACTORY MADE AND COMPOSED OF: AN <br />INNER FIBERGLASS WOVEN LINER, ENCAPSULATED HELIX COIL, A FIBERGLASS INSULATING BLANKET AND OUTER VAPOR BARRIER OF FIBERGLAS <br />REINFORCED METALIZED FILM LAMINATE. PROVIDE THERMAFLEX MK-C FLEXIBLE DUCT OR APPROVED EQUAL (MIN. OF R-6.0). CARE IS TO BE TAKEN <br />THAT ALL RUNOUTS OF FLEXIBLE DUCTS ARE INSTALLED AS STRAIGHT AS PRACTICAL AND FASTENED SO AS TO ELIMINATE AIR LEAKAGE. THE <br />INSTALLATION SHALL CONFORM TO THE TECHNIQUES SHOWN IN THE UL APPROVED AND FACTORY -SUPPLIED INSTRUCTIONS. <br />INSULATION: ASSURE ALL DUCTWORK IS SEALED PRIOR TO INSTALLING INSULATION. <br />ALL FRESH AIR & ROUND BRANCH SUPPLY DUCTWORK SHALL BE WRAPPED WITH 2" THICK FIBERGLASS BLANKET INSULATION WITH FSK (ASJ) FACING, <br />MINIMUM INSTALLED R VALUE OF 6.0. AND FLAME SPREAD/SMOKE DEVELOPED RATINGS OF 25/50 BY ASTM E-84. INSTALL INSULATION ON DUCTWORK <br />USING ADHESIVE AND/OR WELD PINS WITH WASHERS. SEAL ALL INSULATION JOINTS, SEAMS AND FASTENER PIN PENETRATIONS WITH VAPOR RETARDING <br />PRESSURE SENSITIVE TAPE OR WITH GLASS FABRIC AND MASTIC. INSTALL TAPERED INSULATION TO THE TOP OF ALL EXTERIOR HORIZONTAL <br />RECTANGULAR DUCTS WIDER THAN 24" BEFORE APPLYING THE FINISH INSULATION TO CAUSE A 1/2" PER FOOT SLOPE OF FINISH INSULATION TO SHED <br />WATER. <br />SUPLY BRANCH DUCT RUNOUTS: SHALL BE GALVANIZED ROUND (SNAPLOCK) SEAM LOCKED DUCTWORK WITH EXTERNAL FIBERGLASS WRAP INSULATION <br />(R-6.0). NOTE: BRANCH DUCT RUNOUTS & FLEXIBLE DUCTS SHALL BE THE SAME SIZE DUCT AS THE DIFFUSER NECK CONNECTED TO, AS LISTED ON <br />THE FLOOR PLAN. <br />GRILLES AND DIFFUSERS: ALL GRILLES AND DIFFUSERS SHALL BE INSTALLED WITH AN INSULATED BOOT OR BLANKET. PROVIDED A METHOD OF <br />VOLUME CONTROL BY DEVICE ADJUSTABLE AT DIFFUSER FACE OR MANUAL VOLUME DAMPERS AT TAKEOFF BRANCHES. COORDINATE DIFFUSER AND <br />GRILLE LOCATIONS WITH ELECTRICAL LIGHTING LAYOUT AND ARCHITECTURAL REFLECTED CEILING PLAN. <br />CONTROLS: PROVIDE CONTROLS COMPLETE TO SUIT THE EQUIPMENT PROVIDED AND TO ACCOMPLISH THE SEQUENCE OF OPERATION AS REQUIRED BY <br />PLANS AND SYSTEMS. LOCATE THERMOSTATS 48" ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED. <br />TESTING AND BALANCING: THE CONTRACTOR SHALL ENSURE THAT ALL DEVICES AND SYSTEMS ARE COMPLETE, TESTED AND BALANCED, AND READY FOR <br />OPERATION WHEN THE FACILITY IS HANDED OVER THE OWNER. THE AIR CONDITIONING SYSTEM SHALL BE TESTED IN ACCORDANCE WITH AABC OR NEBB. <br />WRITTEN REPORT SHALL BE SUBMITTED TO OWNER. <br />GUARANTEE: THE ONE-YEAR GUARANTEE PERIOD SHALL NOT START UNTIL THE PROJECT IS FULLY COMPLETED AND THE CONTRACTOR HAS RECEIVED <br />THE FINAL PAYMENT. ALL NEW EQUIPMENT AND ALL WORK SHALL BE FULLY GUARANTEED, PARTS AND LABOR, FROM DEFECTS IN MATERIAL AND <br />WORKMANSHIP FOR ONE YEAR FROM THE DATE OF THE FINAL PAYMENT, AT NO ADDITIONAL COST TO OWNER. REPAIRS MADE DURING THIS PERIOD <br />MUST BE FULLY GUARANTEED FROM DEFECTS IN MATERIAL AND WORKMANSHIP AT NO EXPENSE TO THE OWNER, FOR AN ADDITIONAL ONE YEAR PERIOD <br />FROM THE DATE OF REPAIRSAT NO ADDITIOAL COST TO OWNER. IN ADDITION, THE CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR ANY DAMAGE <br />TO THE BUILDING, AND ITS CONTENTS OR OTHER EQUIPMENT, CAUSED BY DEFECTS OR IMPROPER INSTALLATION OF EQUIPMENT OR MATERIAL INSTALLED. <br />ALL NEW HVAC UNITS SHALL INCLUDE 5-YEAR WARRANTY ON COMPRESSORS AND 1-YEAR WARRANTY ON ALL OTHER PARTS AND LABOR FOR UNIT. <br />PROPOSED <br />SCALE: 1 /4" = 1'-0" <br />PLAN <br />CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID <br />AND SURVEY ALL EXISTING CONDITIONS AND <br />EQUIPMENT PRIOR TO SUBMITTING BID FOR WORK <br />REQUIRED BY THESE DOCUMENTS. THIS <br />INCLUDES ABOVE THE CEILING AND ON TOP OF <br />THE ROOF. <br />2. CONTRACTOR SHALL REFER TO AND READ <br />THROUGH ALL OF THE "CONTRACTOR'S SCOPE OF <br />WORK" AS DEFINED IN THE BID SPECIFICATIONS <br />AND DOCUMENTS AS PART OF THE BID PROCESS. <br />3. IF AT ANY TIME, THERE IS DISCREPANCY BETWEEN <br />THE PLANS & SPECS, OR CONFUSION/CONCERN <br />OVER REQUIRED WORK, CONTRACTOR SHALL <br />IMMEDIATELY NOTIFY ARCHITECT, ENGINEER, &/OR <br />OWNER AND GET DIRECTION BEFORE PROCEEDING <br />WITH WORK IN QUESTION. <br />JJCAJ 26254 <br />STRUCTURAL DESIGN BY: <br />FERLITA ENGINEERING <br />CIVIL ENGINEERING <br />4221 N. Florida Av. <br />TAMPA, FLORIDA 33603 <br />PHONE (813) 234-5004 <br />as Z m <br />mm� Dz <br />a r N M <br />Cm p N <br />os <br />�O <br />to <br />a 0 r <br />D M <br />m� <br />w <br />O <br />CD <br />LLJ <br />�' <br />N <br />� O CD <br />L� <br />z cn o <br />00 <br />LLJ o <br />O <br />Lrn00- <br />ENGINEERS SEAL <br />t%J W D111'��. <br />GENS��GL�� <br />-No 56189 <br />* N •� <br />g1'ATE OF <br />�",';1'0 N A1- �?.N'• <br />SHEET <br />MECHANICAL <br />CEILING PLAN & <br />SPECIFICATIONS <br />DRAWING SETS <br />SHEET NUMBER <br />m I <br />ENGINEERING <br />Designer. <br />MATTHEW LEWIS, PE <br />Drawn By. <br />TJ <br />Checked By. <br />Project No. <br />ML <br />116-17 <br />