JOINT FIRESTOP DETAIL <br />DESIGN NO. HW-D-0181 <br />PENETRATION FIRESTOP DETAIL <br />DESIGN NO. W-L-5028 <br />SCAT F: NTS <br />SECTION A -A <br />1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be <br />constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall <br />and Partition Designs in the UL Fire Resistance Directory and shall include the following <br />construction features: <br />A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to <br />consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide and spaced <br />max 24 in. OC. <br />B. Gypsum Board, -%in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, <br />thickness, number of layers, fastener type and sheet orientation shall be as specified in the <br />individual Wall and Partition Design. Max dram of opening 1 <br />s 7-1/2 in. <br />The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly <br />in which it is installed. <br />2. Through Penetrants - One metallic pipe or tubing to be centered within the firestop system. Pipe <br />or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of <br />metallic pipes or tubing may be used: <br />A. Steel Pipe - Nom 4 in. dram (or smaller) Schedule 40 (or heavier) steel pipe. <br />B. Copper Tubing - Nom 2 in. dram (or smaller) Type L (or heavier) copper tubing. <br />C. Copper Pipe - Nom 2 in. dram (or smaller) Regular (or heavier) copper pipe. <br />3. Tube Insulation - Plastics+ - Nom3yin. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) <br />flexible foam furnished in the form of tubing. An annular space of min 0 in. (point contact)to max <br />1-1/2 in. is required within the firestop system. <br />See Plastics+ (OMFZ2)category in the Recognized Component Directory for names of manufacturers. <br />Any Recognized Component tube insulation material meeting the above specifications and having a UL <br />94 Flammability Classification of 94-5VA may be used. <br />The hour T Rating of the firestop system is dependent on the hourly fire rating of the wall <br />assembly in which it is installed, the size and type of through penetrant and the pipe covering <br />thickness, as shown in the table below: <br />Wall Assembly Type + Through Penetrant <br />Rating Hr Max Diam In. <br />I A 4 <br />I A,B, OR C 2 <br />2 A 4 <br />2 A,B, OR C 2 <br />+Indicates penetrant type as itemized in Item 2. <br />4. Fill, Void or Cavity Material* - Sealant - Min%in. thickness of fill material applied within the <br />annulus, flush with both surfaces of wall. At the point contact location between pipe covering and <br />gypsum wallboard, a miny2in. dram bead of fill material shall be applied at the pipe covering/gypsum <br />wallboard interface on both surfaces of wall. <br />HILTI CONSTRUCTION CHEMICALS, DIV OF <br />HILTI INC - FS-ONE Sealant <br />*Bearing the UL Classification Mark <br />PENETRATION FIRESTOP DETAIL <br />DESIGN NO. CAJ-1081 <br />SCALE: NTS <br />F RATING - 2 - 3 HR. <br />T RATING - 0 HR. <br />1. Floor or Wall Assembly Min 3-3/4 in. (2-Hr Rating) or min 4-1/2 in. (3-Hr Rating) thick <br />reinforced lightweight or normal weight (100-150 pcf)concrete floor, or min 4-3/4 in. (2-Hr <br />Rating) or min 5 in. (3-Hr Rating) thick reinforced lightweight or normal weight (100-150 pcf) <br />concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*. Max dram of <br />opening is 16 in. <br />See Concrete Block (CAZT)category in the Fire Resistance Directory for names of manufacturers. <br />2. Metallic Sleeve (Optional) 15)!32 Nom 16 in. dram (or smaller) steel pipe, conduit or steel EMT <br />cast or grouted into floor or wall assembly, flush with floor or wall surfaces. <br />3. Through Penetrants One metallic pipe, conduit or tubing to be installed either concentrically or <br />eccentrically within the firestop system. Pipe, conduit or tubing to be rigidly supported on both <br />sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or <br />tubing may be used- <br />A. Steel Pipe Nom 10 in. dram (or smaller) Schedule 10 (or heavier) steel pipe. The annular space <br />shall be miny4in. to max 4 in. <br />B. Steel Pipe Nom 24 in. dram (or smaller) Schedule 10 (or heavier) steel pipe. The annular space <br />shall be minV4in. to max 1-15/16 in. <br />C. Conduit Nom 6 in. dram (or smaller) steel conduit or nom 4 in. dram (or smaller) electrical <br />metallic tubing. The annular shall be min'/4in. to max 4 in. <br />D. Copper Tubing Nom 6 in. diam (or smaller)Type M (or heavier)copper tubing. The annular space <br />shall be minV4in. to max 1-13/16 in. <br />E. Copper Tubing Nom 4 in. (or smaller) Type M (or heavier) copper tubing. The annular space shall <br />be a mini/4in. to max 4 in. <br />4. Forming Material* Min 2-3/4 in. (2-Hr Rating)or min 3 in. (3-Hr Rating) thickness of min 3.5 pcf <br />mineral fiber insulation firmly packed into opening as a permanent form. Forming material to be <br />recessed from top surface of floor or from both surfaces of wall as required to accommodate the <br />required thickness of fill material. <br />THERMAFIBER L L C -Type SAF <br />5. Fill, Void or Cavity Material* - Sealant Min 1 in. thickness of fill material applied <br />within the annulus, flush with top surface of floor or with both surfaces of wall. Dry mix <br />material mixed with water at a rate of 2.1 parts dry mix to 1 part water by weight in accordance <br />with the accompanying installation instructions. <br />UNITED STATES GYPSUM CO - Type FC <br />5A. Fill, Void or Cavity Material* Not Shown l32 Two component fill material used as an alternate to <br />Item 5. Min 1 in. thickness of fill material applied within the annulus, flush with top side of <br />floor or both surfaces of wall. Ready -mixed component mixed with accelerator component at a rate <br />of 66 parts of ready -mixed component to 1 part accelerator component by weight in accordance with <br />the accompanying installation instructions. <br />UNITED STATES GYPSUM CO -Type RFC <br />*Bearing the UL Classification Mark <br />FIRE RESISTANCE DETAIL <br />DESIGN NO. U419 <br />SCALE: NTS <br />1. Floor and Ceiling Runners (Not shown) /32 Channel shaped, fabricated from min <br />25 MSG (min 20 MSG when Item 4A is used) corrosion -protected steel, min width <br />to accommodate stud size, with min 1 in. long legs, attached to floor and <br />ceiling with fasteners 24 in. OC max. <br />2. Steel Studs Channel shaped, fabricated from min 25 MSG (min 20 MSG when Item <br />4A is used) corrosion -protected steel, min width as indicated under Item 4, min <br />1-1/4 in. flanges andln. return, spaced a max of 24 in. OC. Studs to be <br />cutygto3/ln less than assembly height. <br />3. Batts and Blankets* (Required as indicated under Item 4) 15/12 Mineral wool <br />batts, friction fitted between studs and runners. Min nom thickness as <br />indicated under Item 4. See Batts and Blankets (BKNV or BZJZ) Categories for <br />names of Classified companies. <br />3A. Batts and Blankets* (Optional) IYy Placed in stud cavities, any glass fiber <br />or mineral wool insulation bearing the UL Classification Marking as to Surface <br />Burning Characteristics and/or Fire Resistance. See Batts and Blankets ( KNV or <br />BZJZ) Categories for names of Classified companies. <br />4. Gypsum Board* Gypsum panels with beveled, square or tapered edges, applied <br />vertically or horizontally. Vertical joints centered over studs and staggered <br />one stud cavity on opposite sides of studs. Vertical joints in adjacent layers <br />(multilayer systems) staggered one stud cavity. Horizontal joints need not be backed <br />by steel framing. Horizontal edge joints and horizontal butt joints on opposite sides of <br />studs need not be staggered. Horizontal edge joints and horizontal butt joints in <br />adjacent layers (multilayer systems)staggered a min. of 12 in. The thickness and number <br />of layers for the 1 hr, 2 hr, 3 hr and 4 hr ratings are as follows: <br />Wallboard Protection on Each Side of Wall <br />No.of Layers Min Thkns <br />Min Stud & Thkns of Insulation <br />Rating Depth of Panel (Item 3) <br />1 3-1/2 1 layer,%in. thick Optional <br />1 2-1/2 1 layer,%2in. thick 1-1/2 in. <br />1 1-5/8 1 layer,3/4in, thick Optional <br />2 1-5/8 2 layers,'hin. thick Optional <br />2 1-5/8 2 layers,%in. thick Optional <br />3 1-5/8 3 layers,%2in. thick Optional <br />3 1-5/8 2 layers,3/4in, thick Optional <br />3 1-5/8 3 layersAin. thick Optional <br />4 1-5/8 4 layers,%in. thick Optional <br />4 1-5/8 4 layers,)/21n. thick Optional <br />4 2-1/2 2 layers 3/1n. thick 2 in. <br />CANADIAN GYPSUM COMPANY - %21n. thick Type C, IP-X2 or [PC -AR; WRC,%in. thick Type AR, C, IP-AR, <br />IP-X1, IP-X2, [PC -AR, SCX, SHX, WRX or WRC;y4in. thick Type IP-X3, ULTRACODE, ULTRACODE SHC <br />or ULTRACODE WRC. <br />UNITED STATES GYPSUM CO - %2in. thick TTe C, IP-X2, IPC-AR or WRC;%In. thick Type SCX, SHX, WRX, <br />IP-Xl, AR, C. WRC, FRX-G, IP-AR, IP-X2, IPC-AR ;/Ln. thick Type IP-X3, ULTRACODE, ULTRACODE <br />SHC or ULTRACDDE WRC. <br />USG MEXICO S A DE C V - 1/21n. thick Tye C, IP-X2, IPC-AR or WRC;`%ln. thick Type AR, C, IP-AR, <br />IP-Xl, IP-X2, IPC-AR, SCX, SHX, WRX, WRC or;/41n. thick Type IP-X3, ULTRACODE, ULTRACODE SHC or <br />ULTRACODE WRC. <br />4A. Gypsum Board* (As an alternate to Item 4) 15/32 %in. thick gypsum panels, <br />installed as described in Item 4 with Type S-12 steel screws. The length and <br />spacing of the screws as specified under Item 5. <br />CANADIAN GYPSUM COMPANY - Type FRX <br />UNITED STATES GYPSUM CO - Type FRX <br />USG MEXICO S A DE C V - Type SHX. <br />5. Fasteners (Not shown) - Type S or S-12 steel screws used to attach panels to <br />studs (Item 2) or furring channels (Item 6). Sin 1e layer systems: 1 in. long <br />fory2and%in. thick panels or 1-1/4 tn. long for lin. thick panels, <br />spaced 8 in. OC when panels are applied horizontally, or 8 in. OC along vertical <br />and bottom edges and 12 in. OC in the field when panels are applied vertically. Two layer <br />systems: First layer- 1 in. long fory2and%in, thick panels or 1-1/4 in. <br />long fora/1n. thick panels, spaced 16 in. OC. Second layer- 1-5/8 in. long for%21n., <br />%in. thick panels or 2-1/4 in. long for%in. thick panels, spaced 16 in. OC with screws <br />offset 8 in. from first layer. Three -layer systems: First layer- 1 in. long for <br />Y21n.,%in.thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long <br />for 2in.Ain. thick panels, spaced 24 in. OC. Third layer- 2-1/4 in. long forY2in., gin. thick <br />panels or 2-5/8 1n. long for%in. thick panels, spaced 12 in. OC. Screws offset min <br />in. from layer below. Four -layer systems: First layer- 1 in. long forll6in., <br />%in. thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long for%2in.,%in. <br />thick panels, spaced 24 in. OC. Third layer- 2-1/4 in. long foryin. thick panels or 2-%in. <br />long for%in. thick panels,spaced 24 in. OC. Fourth layer - 2-%in. long forl/21n. thick <br />panels or 3 in. long for%ln. thick panels,spaced 12 in. OC. Screws offset min. 6 in. <br />from layer below. <br />6. Furring Channels (Optional, not shown, for single or double layer systems) - Resilient furring <br />channels fabricated from min 25 MSG corrosion -protected steel, spaced vertically a max of 24 in. <br />OC. Flange portion attached to each intersecting stud with 2 in. long Type S-12 steel screws. <br />Not for use with Item 4A. <br />7.Joint Tape and Compound Vinyl or casein, dry or premixed joint compound applied in two coats to <br />joints and screw heads of outer layers. Paper tape, nom 2 in. wide, embedded in first layer of <br />compound over all joints of outer layer panels. Paper tape a joint compound may be omitted <br />when gypsum panels are supplied with a square edge. <br />B. Siding, Brick or Stucco (Optional, not shown) - Aluminum, vinyl or steel siding, brick veneer <br />or stucco, meeting the requirements of local code agencies, installed over gypsum panels. Brick <br />veneer attached to studs with corrugated metal wall ties attached to each stud with steel screws, <br />not more than each sixth course of brick. <br />9. Caulking and Sealants* (Optional, not shown) - A bead of acoustical sealant applied around the <br />partition perimeter for sound control. <br />UNITED STATES GYPSUM CO - Type AS <br />*Bearing the UL Classification Mark <br />PENETRATION FIRESTOP DETAIL <br />DESIGN NO. W-L-1001 <br />SCALE: NTS <br />SECTION A -A <br />(Formerly System No. 147) <br />F Ratings 1 1, 2, 3 and 4 Hr (See Items 2 and 3) <br />T Ratings - 0, 1, 2, 3, and 4 Hr (See Item 3) <br />L Rating At Ambient - less than 1 CFM/sq ft <br />L Rating At 400 F - less than 1 CFM/sq ft <br />1. Wall Assembly The 1, 2, 3 or 4 hr fire -rated gypsum wallboard/stud wall assembly shall be <br />constructed of the materials and in the manner described in the individual U300 or U400 Series Wall <br />or Partition Designs in the UL Fire Resistance Directory and all include the following construction <br />features: <br />A. Studs Wall framing may consist of either wood studs (max 2 h fire rated assemblies) or steel <br />channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC with nom 2 by 4 in. <br />lumber end plates and cross braces. Steel studs to be min 3%1n.wide by 1-3/8 in. deep channels <br />spaced max 24 in. OC. <br />B. Gypsum Board* Nomy2or%gin, thick, 4 ft. wide with square or, tapered edges. The gypsum <br />wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as <br />specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max <br />dram <br />of opening is 13-1/2 in. <br />2. Pipe or Conduit Nom 12 in. dram (or smaller) Schedule 10 (or heavier) steel pipe, nom 12 in. <br />dram (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in. dram (or smaller) <br />Class 50 (or heavier) ductile iron pressure pipe, nom 6 in. diam.(or smaller) steel conduit, <br />nom 4 in. dram (or smaller) steel electrical metallic tubing, nom 6 in. dram (or smaller) <br />Type L or (or heavier) copper tubing or nom 1 in. dram (or smaller) flexible <br />steel conduit. When copper pipe is used, max F Rating of firestop system (Item 3)is 2 h. <br />Steel pipes or conduits larger than nom 4 in, diam may only be used <br />in walls constructed using steel channel studs. A max of one pipe or conduit is permitted in the <br />firestop system. Pipe or conduit to be installed near center of stud cavity width and to be rigidly <br />supported on both sides of wall assembly. <br />3. Fill, Void or Cavity Material* 15), Caulk Caulk fill material installed to completely fill annular <br />space between pipe or conduit and gypsum wallboard and with a min%1n.diam bead of caulk <br />applied to perimeter of pipe or conduit at its egress from the wall.Caulk installed symmetrically on <br />both sides of wall assembly. The hourly F Rating of the firestop system is dependent upon the <br />hourly fire rating of the wall assembly in which it is installed, as shown in the following table. <br />The hourly T Rating of the firestop system is dependent upon the type or size of the pipe or <br />conduit and the hourly fire rating of the wall assembly in which it is installed, as tabulated below: <br />Max Pipe or Conduit Diam In. Annular Space In. F Rating Hr T Rating Hr <br />1 0 tows 1 or 2 0+, 1 or 2 <br />1 1/ to�6 3 or 4 3 or 4 <br />4 0 to 1-Y2 1 or 2 0 <br />6 1/4to%2 3 or 4 0 <br />12 W6tog Ior 2 0 <br />+When copper pipe is used, T Rating is 0 h. <br />MINNESOTA MINING & MFG CO - CP 25WB+. <br />*Bearing the UL Classification Mark <br />FIRE RESISTANCE DETAIL <br />DESIGN NO. U901 <br />SCALE: NTS <br />= `--t- - - <br />1. Concrete Blocks* Various designs. Classification B-4 (4 hr). <br />See Concrete Blocks category for lists of eligible manufacturers. <br />2. Mortar Blocks laid in full bed of mortar, nom.%in. thick, of not less than 2-1/4 and not <br />more than 3-1/2 parts of clean sharp sand to 1 part Portland cement (proportioned by volume)and <br />not more than 50 percent hydrated lime (by cement volume). Vertical joints staggered. <br />3. Portland Cement Stucco or Gypsum Plaster If used, add'/2hr, to Classification <br />4. Loose Masonry Fill If all core spaces are filled with loose dry expanded slag, burned clay or <br />shale (rotary kiln process), water repellant vermiculite masonry fill insulation, or silicone <br />treated perlite loose fill insulation,. Class 0-2 (2 hr) or C-3 (3 hr) concrete blocks will provide <br />a 4 hr fire resistance rating. <br />*Bearing the UL Classification Mark <br />FIRE RESISTANCE DETAIL <br />DESIGN NO. U914 <br />SCALE: NTS <br />a ❑gip❑ <br />24' <br />1. Concrete Blocks* Various designs. Classification D-2 (2 hr). See Concrete Blocks category for <br />list of eligible manufacturers. <br />2. Mortar Blocks laid in full bed of mortar, nom%in. thick, of not less than 2-1/4 and not more <br />than 3-1/2 parts clean sharp sand to 1 part Portland cement (proportioned by volume)and not more <br />than 50 percent hydrated lime (by cement volume). Vertical joints staggered. <br />3. Furring Channels Min 0.019 in, thick (25 gauge) gale steel, 1-3/8 in. wide on top and 2-3/4 in. <br />wide at bottom byy8in. deep. Spaced 24 in. OC perpendicular to floor with a channel parallel to <br />and approximately 3 in. above floor and 3 in. below ceiling. Clearance between vertical and <br />horizontal channels'/L1n. <br />4. Channel Fasteners 1-1/4 in, long masonry screws withX6in, body andNi6in. diameter head. <br />Fasteners spaced 24 in. O.C. with the fasteners staggered on each long leg of the furring channel. <br />4A. Steel Framing Members* (Not Shown) - Alternate method used to attach furring channels (Item <br />3) to concrete blocks (Item 1). Clips spaced 48 in. OC., and secured to blocks withy4in. dia. By 3 <br />in. long concrete expansion anchor (Item 4B) through the center grommet. <br />Furring channels are friction fitted into clips. <br />PAC INTERNATIONAL - Type RSIC-1. <br />4B. Concrete Expansion Anchor (Not Shown) - 'Ain. dia. by 3 in. long carbon steel, pre -assembled, <br />nail drive expansion anchor with mushroom head driven into the web of the concrete block. Min. <br />embedment in concrete block of 1-3/8 in. and evaluated in accordance with ASTM E 486 to have <br />Ultimate load capacities of 980 lbs (tension)and 1400 lbs (shear)when used in 2000 psi concrete. <br />5. Gypsum Board*Y2in. thick, 4 ft wide, secured to furring channels with wallboard fasteners <br />(Item 6). Gypsum plaster not more than%bin. thick may be applied to wallboard in addition to <br />joint treatment. <br />AMERICAN GYPSUM CO - Types AG-C,AGX-C. <br />BORAL GYPSUM INC - Type BG-C. <br />CANADIAN GYPSUM COMPANY - Types C, IP-X2, IPC-AR. <br />CONTINENTAL GYPSUM COMPANY - Types CO-C,CG5-5,CGTC-C. <br />G-P GYPSUM CORP, SUB OF <br />GEORGIA-PACIFIC CORP - Type 5. <br />JAMES HARDIE GYPSUM INC - Type Max°C". <br />LAFARGE NORTH AMERICA INC - Types LGFC-C,LGFC-C/A. <br />NATIONAL GYPSUM CO - Type FSW-C. <br />PABCO GYPSUM, DIV OF <br />PACIFIC COAST BUILDING PRODUCTS INC - Type PG-C. <br />STANDARD GYPSUM L L C - Type SG-C. <br />TEMPLE -INLAND FOREST PRODUCTS CORP - Type TG-C. <br />UNITED STATES GYPSUM CO - Types C,IP-X2,IPC-AR. <br />USG MEXICO S A DE C V - Types C, IP-X2, IPC-AR. <br />6. Wallboard Fasteners 1 in. long, self -drilling, self -tapping steel screws with bugle heads. <br />Fasteners attached to each furring channel and spaced 8 in. OC at butt joints and 12 in. OC in the <br />field of the board parallel with furring channels. Clearance <br />tween fasteners and edges of wallboard 3/4 in. <br />7. Joint System 15)� (Not shown) Paper tape embedded in cementitious compound over joints. Paper tape <br />and exposed screw heads covered with two layers of compound. Edges of compound feathered out. <br />*Bearing the UL Classification Mark <br />-JOINT FIRESTOP DETAIL <br />DESIGN NO. HW-D-0098 <br />SCALE: NTS <br />FRONT VIEW SECTION A -A <br />1. Metal roof deck assembly (non fire -rated) <br />2. Concrete wall assembly (2-hr fire rated): <br />A. Lightweight or normal weight concrete wall (min. 6 in. thick) <br />B. Any UL/ULC classified concrete block wall. <br />3. Mineral wall (min. 4 pcf density) compressed 33 percent and inserted into joint, <br />flush with both sides of wall. (see no.3 below) <br />4. Hilti CP 777 speed plugs friction fitted to completely fill flute, flush with both <br />sides of wall (see note no. 3 below) <br />5. Minimunyein. (wet) thickness Hilti CP 672 firestop joint spray to completely cover <br />mineral wool and to overlap a minimum%2in. onto concrete wall and metal deck on <br />both sides of wall assembly. <br />Notes: <br />1. Steel floor units may be sprayed with a minimum5A6 in. thickness to maximum <br />1-yin thickness of UL classified monokote type MK-6/HY fireproofing manufactured <br />by W.R. Grace <br />2. When the steel deck is coated with fireproofing,Hilti CP 672 shall overlap the wall <br />a min.!/2in and overlap the fireproofing a min.2 in. on both sides of the wall. <br />3. As an alternated to Hilti CP 777 speed plugs, mineral wool (minimum 4 pcf density) <br />compressed 33 percent may be used. <br />4.T-Rating may not equal F-rating in accordance with UL 2079 <br />5. Fire Rating of joint is only as good as performance of metal roof deck assembly <br />under fire conditions. <br />All configuration shown are suggestions only and must be approved by the specifying <br />architects or engineers for the project. <br />This is not a UL Classified systems, But a modification of the closest applicable system <br />(Reference: UL System No. HW-D-0098) <br />FIRE RESISTANCE DETAIL <br />DESIGN NO. X528 <br />SCALE: NTS <br />113/° <br />li <br />�' <br />11 <br />�N)III <br />iiiiiiiiiiuiiiiii <br />' I FURR DUT TO ACCOMODATE <br />I �_,! PLUMBING VENT AND <br />I------------ • CLEAN -OUT <br />1. Steel Column Min sizes of W-shaped and tubular steel columns which appear in the AISC Steel <br />Construction Manual as shown under Item 2. <br />2. Gypsum Board* For I Hr rating, any /gin, or f21n. thick gypsum wallboard Classified for use <br />in fire resistance assemblies. For 2 Hr and 3 Hr ratings, any %in. or Y21n. thick gypsum <br />wallboard Classified for use in other 2 Hr, 3 Hr or 4 Hr Column Designs. Min total thickness of <br />layersin inches for the various ratings and min column sizes are as follows: <br />W Shaped Rating (Hr) Corner Details For Various Rating <br />Column 1 2 3 1 Hr 2 Hr 3 Hr <br />Min Column <br />Size <br />Total thickness (In.) <br />W4xl3 11-1/2 2-1/4 B C D <br />W6xl5.5 1 1-1/2 2-1/4 B C D <br />W10x49 1/21-1/8 1-7/8 A B C <br />Applied in layers as noted in the above illustrations. Boards are to be applied vertically <br />without horizontal joints. <br />See Gypsum Board (CKNX)category for names of manufacturers. <br />2A. Gypsum Board* As an alternate to Item 2-XI.n. thick gypsum wallboard. For 2 Hr rating, 1-1/2 <br />Ln. total thickness, installed in accordance with corner detail B. For 3 Hr rating, 2-114 in. total <br />thickness installed 1n accordance with corner detail C.Boards are to be applied vertically without <br />horizontal joints. <br />CANADIAN GYPSUM COMPANY - Type IP-X3, ULTRACODE, ULTRACODE SHC or ULTRACODE WRC. <br />UNITED STATES GYPSUM CO - Type IP-X3, ULTRACODE, ULTRACODE SHC or ULTRACODE WRC. <br />USG MEXICO S A DE C V - Type IP-X3,ULTRACODE, ULTRACDDE SHC or ULTRACODE WRC. <br />3. Steel Stud 1-5/8 in. wide with 1-5/16 and 1-7/16 in. legs having a 1/4- in. folded flange, <br />fabricated from No. 25 MSG gale steel. Length to be'/2in.less than the assembly height. <br />3A. As an alternate to Item 3 Steel Framing Members* galv. steel clips spaced 4 ft OC and 1-1/4 in. <br />from top and bottem of column.A No.28 MSG galv steel support angle with 1-1/4 in. length shall be <br />placed over clips and secured with screws attaching the wallboards. The clips for use with wide <br />flange columns only. <br />COLUMN & BEAM INC - Types CB, CB1Clips. <br />4. Corner Beads No.28 MSG gale steel,)-1/4 in. legs to be attached to the wallboard with No.6 by <br />1 in. screws spaced 12 in. OC max. <br />5. Tie Wire No.18 SWG steel wire spaced 24 in. OC used with second layer of wallboard. <br />6. Screws For attaching first layer of wallboard to steel studs, and third layer of wallboard to 2 <br />in. by 2 in. steel angle (25 Ga) to be No. 6 by 1 in. (or 1-1/4 in. for%in. thick wallboard) <br />Phillips head self -drilling, self -tapping double lead screwspaced 24 in. OC For attaching <br />second layer of wallboard to steel studs and fourth layer of wallboard to 2 in. by 2 in. steel <br />angle <br />(25 Ga) to be No. 6 by 1-3/4 in. (or 2-1/4 in. for:y4in. thick wallboard) steel screws of the <br />same type spaced 12 in. OC For attaching third layer of wallboard to steel studs to be <br />No. 8 by 2-1/4 in. screws of the same type spaced 12 in. OC <br />7.Finishing S stem (Not Shown) - Joint compound applied over corner beads to a <br />thickness of i6 in. <br />*Bearing the UL Classification Mark <br />FIRE RESISTANCE DETAIL <br />DESIGN NO. U905 <br />SCALE: NTS <br />m . <br />z <br />3 ' D.. - D ' D <br />�� <br />A ' `1 <br />1. Concrete Blocks* Various designs. Classification D-2 (2 hr). <br />See Concrete Blocks category for list of eligible manufacturers. <br />- 2. Mortar Blocks laid in full bed of mortar, nom.%in. thick, of not less than 2-1/4 and not more <br />than 3-1/2 parts of clean sharp sand to 1 part Portland cement (proportioned by volume) and not <br />more than 50 percent hydrated lime (by cement volume). Vertical joints staggered. <br />3. Portland Cement Stucco or Gypsum Plaster Add!/2hr to classification if used. Where combustible <br />members are framed in wall, plaster or stucco must be applied on the face opposite framing to <br />achieve a max. Classification of 1-1/2 hr. Attached to concrete blocks (Item 1). <br />4. Loose Masonry Fill If all core spaces are filled with loose dry expanded slag, expanded clay or <br />shale (Rotary Kiln Process), water repellant vermiculite masonry fill insulation, or silicone <br />treated perlite loose fill insulation add 2 hr to classification. <br />5. Foamed Plastic* (Optional -Not Shown) - 1-1/2 in. thick max, 4 ft wide sheathing attached to <br />concrete blocks (Item 1). <br />CELOTEX CORP -Type Thermax <br />SCALE: NTS <br />FRONT VIEW SECTION A -A <br />1. Metal roof deck assembly (non fire -rated) <br />2. Concrete wall assembly (2-hr fire rated): <br />A. Lightweight or normal weight concrete wall (min. 6 in. thick) <br />B. Any UL/ULC classified concrete block wall. <br />3. Mineral wall (min.4 pcf density) compressed 33 percent and inserted into joint, <br />flush with both sides of wall. (see no.3 below) <br />4. Minimuni/gin. (wet) thickness Hilti CP 672 firestop joint spray to completely cover <br />mineral wool and to overlap a minimum%21n. onto concrete wall and metal deck on <br />both sides of wall assembly. <br />Notes: <br />1. Steel floor units may be sprayed with a minimum%&in.thickness to maximum <br />1-3/4in thickness of UL classified monokote type MK-6/HY fireproofing manufactured <br />by W.R. Grace <br />2. When the steel deck is coated with fireproofing, Hilti CP 672 shall overlap the wall <br />a min.y2in and overlap the fireproofing a min. 2 in. on both sides of the wall. <br />3.T-Rating may not equal F-rating in accordance with UL 2079 <br />4. Fire -Rating of joint is only as good as performance of metal roof deck assembly <br />under fire conditions. <br />All configuration shown are suggestions only and must be approved by the specifying <br />architects or engineers for the project. <br />This is not a UL Classified systems, But a modification of the closest applicable system <br />(Reference: UL System No. HW-D-0181) <br />JOINT FIRESTOP DETAIL <br />DESIGN NO. HW-D-0098 <br />SCALE: NTS <br />FRONT VIEW SECTION A -A <br />).Floor Assembly The fire rated fluted steel unit/concrete floor assembly shall be constructed of <br />the materials and in a manner described in the individual D700 or D900 Floor -Ceiling Design in the <br />UL Fire Resistance Directory and shall include the following construction features: <br />A. Steel Floor and Form Units* Max 2 in. deep gals steel fluted floor units. <br />B. Concrete Min 2-1/2 in thick reinforced concrete as measured from top plane of the floor units. <br />C. Spray -Applied Fire Resistive Materials* (Optional) - (Not Shown) - Prior to the installation <br />of the <br />forming material and fill, void or cavity material (Items 3A, 3B) the steel floor units may be <br />sprayed with a minw16in. to max 1-3/4 in. thickness of firesistive material. <br />W R GRACE & CO - CONN <br />CONSTRUCTIDN PRODUCTS DIV - Type MK-6-HY <br />IA. Roof Assembly (Not Shown) - As an alternate to the floor assembly, a fire rated fluted steel <br />deck roof assembly may be used. The roof assembly shall be constructed of the materials and in the <br />manner described in the individual P900 Series Roof -Ceiling <br />Design in the UL Fire Resistance Directory. The hourly rating of the roof assembly shall be equal <br />to or greater than the hourly rating of the wall assembly.The roof assembly shall include the <br />following construction features: <br />A. Steel Roof Deck Max 2 in. deep galv steel fluted roof deck. <br />B. Roof Insulation Min 2-1/4 in. thick poured insulating concrete, as measured from the top plane <br />of the floor units. <br />1B.Roof Assembly As an alternate to Items 1 and lA,a fire rated protected fluted steel deck roof <br />assembly may be used. The roof assembly shall be constructed of the materials and in the manner <br />described in the individual P700 Series Roof -Ceiling Design <br />n the UL Fire Resistance Directory. The hourly rating of the roof assembly shall be equal to or <br />greater than the hourly rating of the wall assembly. The roof assembly shall include the following <br />construction features. - <br />A. Steel Roof Deck Max 2 in. deep galv steel fluted roof deck. <br />B. Spray - Applied Fire Resistive Materials* (Not Shown)% Prior to the installation of the steel <br />ceiling runners, Forming Material and Fill, Void or Cavity Material (Items 2A, 3A, 3B), the roof <br />assembly shall be sprayed with the type and thickness of fire resistive material indicated in the <br />individual P700 Series design. <br />2. Wall Assembly Min 6 in. thick steel -reinforced lightweight or normal weight (100-150 pcf) <br />structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. <br />See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. <br />3. Joint System Max separation between bottom of floor or roof and top of wall at time of <br />installation of joint system is 1 in. The joint system is designed to accommodate a max 12.5 <br />percent compression or extension from its installed width. The joint system shall consist of the <br />following: <br />AFormingMatra m 4. f mineral I insulation m n e 1 1 No 0 pc i e al woo bat( i sulatio compressed and firmly packed to <br />completely fill the flutes and the gap between the top of the wall and bottom of the floor or roof <br />as a permanent form. Batt insulation cut to the shape of the fluttted steel deck, approx 33 percent <br />larger than the flutes. Pieces compressed and installed vertically into the flutes above the top of <br />the wall. Additional pieces of batt insulation, min 6 <br />HILTI INC - CP777 Speed Plugs <br />B. Fill, Void or Cavity Material* Minyein. wet thickness of fill material sprayed or troweled on <br />each side of the wall to completely cover mineral wool forming material and to overlap a min ofY2 <br />in. onto wall and steel deck on both sides of wall. When spray -applied fire resistive material* is <br />applied to the steel steel deck, the fill material is to overlap the wall a min of%2in. and the <br />spray -applied fire resistive material a min of 2 in. on both sides of wall <br />HILTI CONSTRUCTION CHEMICAL, DIV OF <br />HILTI INC - CP672 Firestop Spray <br />JOINT FIRESTOP DETAIL <br />DESIGN NO. HW-D-0181 <br />SCALE: NTS <br />D. . <br />__ � j <br />, <br />�____-__1_ <br />).Floor <br />Assembly The 2 hr fire -rated fluted steel deck/concrete floor assembly shall be <br />constructed of the materials and in the manner described in the individual D700 Floor-Ceiing Design <br />Ln the UL Fire Resistance Directory and shall include the following construction features: <br />A. Steel Floor And Form Units* Max 3 in. deep galv steel fluted floor units. <br />B. Concrete Min 2-1/2 in. thick reinforced concrete,as measured from the top plane of the floor <br />units. <br />C. Spray -Applied Fire Resistive Materals* (Optional)t5& (Not ShownAh Prior to the installation of the <br />forming material and fill, void or cavity material (Item 3A, 3B) the steel floor units may be <br />spra ed with a <br />m1nT6 to max 1-3/4 in. thickness of fire resistive material in accordance with the specifications in <br />the individual D700 Series Design. <br />HILTI CONSTRUCTION CHEMICALS, DIV OF <br />HILTI INC % Type MK-6-HY <br />2. Wall Assembly Min 8 in. thick reinforced lightweight or normal weight (100-150 pcf) structural <br />concrete. Wall shall be installed parallel with the flutes of the steel floor and form units (Item <br />IA). Wall may <br />also be constructed of any UL Classified 2 fire rated Concrete Blocks*.When wall is constructed of <br />concrete blocks, the top course of block shall be filled with concrete, grout or mortar. <br />See Concrete Blocks (CAZT)category in the Fire Resistance Directory for names of manufacturers. <br />3. Joint System Max separation between bottom of spray -applied fire resistive and top of the wall <br />at time of installation of joint system is 1 in. The joint system is designed to accommodate a max <br />12.5 percent compression or extension from its installed width. The joint system consists of the <br />following: <br />A. Forming Material* Min 4 pcf mineral wool batt insulation cut into strips with a width approx <br />equal to the overall thickness of the wall. Strips compressed 33 percent in thickness and inserted <br />Into the gap between the top of the wall and the bottom of the floor units. When the void beneath <br />the <br />protected steel deck is located entirely above the wall, the void shall be completely filled with <br />mineral wool insulation compressed 33 percent in thickness. When void beneath the steel deck is <br />located in part abo <br />the wall, that portion of the void above the wall shall be packed with additional strips of <br />mineral wool batt insulation compressed 33 percent in thickness. <br />ROCK WODL MANUFACTURING CO 15� Delta Boerd <br />B. Fill, Void or Cavity Material* Minl/gln. wet thickness of fill material sprayed or troweled on <br />each side of the wall to completely cover mineral wool forming material and to overlap a min of%2 <br />in. onto wall and steel deck on both sides of wall. When spray -applied fire resistive material* 15 <br />applied to the steel floor and form units, the fill material is to overlap the wall a min ofY2in. <br />and the spray -applied fire resistive material a min of 2 in. on both sides of wall. <br />HILTI CONSTRUCTION CHEMICAL, DIV OF <br />HILTIINC.- CP672 Firestop Spray <br />P u b 11'6 XG <br />SUPER MARKETS <br />CORPORATE OFFICES, FACILITIES DESIGN <br />BOX 407, LAKELAND, FL 33802 <br />(8631680.5295 <br />PHYSICAL ADDRESS: <br />3300 PUBLIX CORPORATE PARKWAY, <br />LAKELAND, FL 33811-3311 <br />PUBLIX FACILITIES <br />DESIGN DEPARTMENT <br />DAVID TAULBEE, AIA <br />ARCHITECT- FL. REG, 91318 <br />DAVID RUBIN, AIA <br />ARCHITECT -FL. REG.92557 <br />GA. REG.] 1881 <br />SC. REG.7477 <br />Al. REG,6234 <br />TN.REG.103497 <br />JOHN W. KITCHENS, PE <br />CIVIL/STRUCTURAL - FL, REG. 45277 <br />GA. REG. 020251 <br />SG REG.]6340 <br />AL REG.20382 <br />TN.REG.101507 <br />PAUL C. HARMAN, PE <br />STRUCTURAL- FL. REG. 51959 <br />GA.REG.27740 <br />SC. REG. 21754 <br />AL. REG.24905 <br />TN. REG.107882 <br />JOHN J. CARAMALIS, PE <br />MECHANICAL - FL REG. A3889 <br />GA. REG. 021246 <br />SG REG.16521 <br />AL REG.20581 <br />TN. REG.108507 <br />ANTHONY CLEMENTI, PE <br />MECHANICAL - FL REG. 54781 <br />GA. REG.31882 <br />SC. REG. 25591 <br />AL REG.28469 <br />TN. REG. I]1382 <br />RAYMOND J. SIRIANNI, PE <br />ELECTRICAL - FL REG. 54085 <br />GA.REG.025636 <br />SC. REG. 19743 <br />AL REG.23065 <br />TN. REG.108038 <br />NORMAN MEIER, PE <br />ELECTRICAL - FL. REG. 59422 <br />GA. REG. 31492 <br />SC. REG. 25290 <br />AL REG.28079 <br />© COPYRIGHT 2008 <br />PUBLIX SUPER MARKETS, INC <br />THESE CONSTRUCTION DOCUMENTS ARE THE PROPERTY <br />OF PUBLIX SUPER MARKETS, INC. AND ARE NOT TO BE <br />COPIED OR REUSED FOR ANY SPECIFIC BUILDING WITHOUT <br />WRITTEN PERMISSION. THESE DRAWINGS SHALL NOT BE <br />DUPLICATED WITHOUT PRIOR WRITTEN PERMISSION OF <br />PUBLIX SUPER MARKETS, INC. <br />THE DESIGN INDICATED IN THESE CONSTRUCTION <br />DOCUMENTS DOES; TO THE BEST OF MY KNOWLEDGE, <br />INFORMATION, AND BELIEF; COMPLY WITH THE APPLICABLE <br />MINIMUM BUILDING CODES <br />N 1 1 2008 <br />l� <br />�{ <br />PLOT DATE: <br />1 Q P-0 <br />REVISION DATA: <br />#1245 (REPL. #0390) <br />ZEPHYR COMMONS <br />PRETTY POND RD. & HWY. 301 <br />ZEPHYRHILLS, PASCO CO., <br />FLORIDA <br />54,4 <br />M2707 <br />DRAWING TITLE: <br />UL DESIGNS <br />SCALE: NONE <br />UL-1 <br />10-JAN-2008 11:18 xmwc P:\1200-1299\1245\1245u1.dgn <br />of 1 <br />