JOINT FIRESTOP DETAIL
<br />DESIGN NO. HW-D-0181
<br />PENETRATION FIRESTOP DETAIL
<br />DESIGN NO. W-L-5028
<br />SCAT F: NTS
<br />SECTION A -A
<br />1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be
<br />constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall
<br />and Partition Designs in the UL Fire Resistance Directory and shall include the following
<br />construction features:
<br />A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to
<br />consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide and spaced
<br />max 24 in. OC.
<br />B. Gypsum Board, -%in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type,
<br />thickness, number of layers, fastener type and sheet orientation shall be as specified in the
<br />individual Wall and Partition Design. Max dram of opening 1
<br />s 7-1/2 in.
<br />The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly
<br />in which it is installed.
<br />2. Through Penetrants - One metallic pipe or tubing to be centered within the firestop system. Pipe
<br />or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of
<br />metallic pipes or tubing may be used:
<br />A. Steel Pipe - Nom 4 in. dram (or smaller) Schedule 40 (or heavier) steel pipe.
<br />B. Copper Tubing - Nom 2 in. dram (or smaller) Type L (or heavier) copper tubing.
<br />C. Copper Pipe - Nom 2 in. dram (or smaller) Regular (or heavier) copper pipe.
<br />3. Tube Insulation - Plastics+ - Nom3yin. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC)
<br />flexible foam furnished in the form of tubing. An annular space of min 0 in. (point contact)to max
<br />1-1/2 in. is required within the firestop system.
<br />See Plastics+ (OMFZ2)category in the Recognized Component Directory for names of manufacturers.
<br />Any Recognized Component tube insulation material meeting the above specifications and having a UL
<br />94 Flammability Classification of 94-5VA may be used.
<br />The hour T Rating of the firestop system is dependent on the hourly fire rating of the wall
<br />assembly in which it is installed, the size and type of through penetrant and the pipe covering
<br />thickness, as shown in the table below:
<br />Wall Assembly Type + Through Penetrant
<br />Rating Hr Max Diam In.
<br />I A 4
<br />I A,B, OR C 2
<br />2 A 4
<br />2 A,B, OR C 2
<br />+Indicates penetrant type as itemized in Item 2.
<br />4. Fill, Void or Cavity Material* - Sealant - Min%in. thickness of fill material applied within the
<br />annulus, flush with both surfaces of wall. At the point contact location between pipe covering and
<br />gypsum wallboard, a miny2in. dram bead of fill material shall be applied at the pipe covering/gypsum
<br />wallboard interface on both surfaces of wall.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF
<br />HILTI INC - FS-ONE Sealant
<br />*Bearing the UL Classification Mark
<br />PENETRATION FIRESTOP DETAIL
<br />DESIGN NO. CAJ-1081
<br />SCALE: NTS
<br />F RATING - 2 - 3 HR.
<br />T RATING - 0 HR.
<br />1. Floor or Wall Assembly Min 3-3/4 in. (2-Hr Rating) or min 4-1/2 in. (3-Hr Rating) thick
<br />reinforced lightweight or normal weight (100-150 pcf)concrete floor, or min 4-3/4 in. (2-Hr
<br />Rating) or min 5 in. (3-Hr Rating) thick reinforced lightweight or normal weight (100-150 pcf)
<br />concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*. Max dram of
<br />opening is 16 in.
<br />See Concrete Block (CAZT)category in the Fire Resistance Directory for names of manufacturers.
<br />2. Metallic Sleeve (Optional) 15)!32 Nom 16 in. dram (or smaller) steel pipe, conduit or steel EMT
<br />cast or grouted into floor or wall assembly, flush with floor or wall surfaces.
<br />3. Through Penetrants One metallic pipe, conduit or tubing to be installed either concentrically or
<br />eccentrically within the firestop system. Pipe, conduit or tubing to be rigidly supported on both
<br />sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or
<br />tubing may be used-
<br />A. Steel Pipe Nom 10 in. dram (or smaller) Schedule 10 (or heavier) steel pipe. The annular space
<br />shall be miny4in. to max 4 in.
<br />B. Steel Pipe Nom 24 in. dram (or smaller) Schedule 10 (or heavier) steel pipe. The annular space
<br />shall be minV4in. to max 1-15/16 in.
<br />C. Conduit Nom 6 in. dram (or smaller) steel conduit or nom 4 in. dram (or smaller) electrical
<br />metallic tubing. The annular shall be min'/4in. to max 4 in.
<br />D. Copper Tubing Nom 6 in. diam (or smaller)Type M (or heavier)copper tubing. The annular space
<br />shall be minV4in. to max 1-13/16 in.
<br />E. Copper Tubing Nom 4 in. (or smaller) Type M (or heavier) copper tubing. The annular space shall
<br />be a mini/4in. to max 4 in.
<br />4. Forming Material* Min 2-3/4 in. (2-Hr Rating)or min 3 in. (3-Hr Rating) thickness of min 3.5 pcf
<br />mineral fiber insulation firmly packed into opening as a permanent form. Forming material to be
<br />recessed from top surface of floor or from both surfaces of wall as required to accommodate the
<br />required thickness of fill material.
<br />THERMAFIBER L L C -Type SAF
<br />5. Fill, Void or Cavity Material* - Sealant Min 1 in. thickness of fill material applied
<br />within the annulus, flush with top surface of floor or with both surfaces of wall. Dry mix
<br />material mixed with water at a rate of 2.1 parts dry mix to 1 part water by weight in accordance
<br />with the accompanying installation instructions.
<br />UNITED STATES GYPSUM CO - Type FC
<br />5A. Fill, Void or Cavity Material* Not Shown l32 Two component fill material used as an alternate to
<br />Item 5. Min 1 in. thickness of fill material applied within the annulus, flush with top side of
<br />floor or both surfaces of wall. Ready -mixed component mixed with accelerator component at a rate
<br />of 66 parts of ready -mixed component to 1 part accelerator component by weight in accordance with
<br />the accompanying installation instructions.
<br />UNITED STATES GYPSUM CO -Type RFC
<br />*Bearing the UL Classification Mark
<br />FIRE RESISTANCE DETAIL
<br />DESIGN NO. U419
<br />SCALE: NTS
<br />1. Floor and Ceiling Runners (Not shown) /32 Channel shaped, fabricated from min
<br />25 MSG (min 20 MSG when Item 4A is used) corrosion -protected steel, min width
<br />to accommodate stud size, with min 1 in. long legs, attached to floor and
<br />ceiling with fasteners 24 in. OC max.
<br />2. Steel Studs Channel shaped, fabricated from min 25 MSG (min 20 MSG when Item
<br />4A is used) corrosion -protected steel, min width as indicated under Item 4, min
<br />1-1/4 in. flanges andln. return, spaced a max of 24 in. OC. Studs to be
<br />cutygto3/ln less than assembly height.
<br />3. Batts and Blankets* (Required as indicated under Item 4) 15/12 Mineral wool
<br />batts, friction fitted between studs and runners. Min nom thickness as
<br />indicated under Item 4. See Batts and Blankets (BKNV or BZJZ) Categories for
<br />names of Classified companies.
<br />3A. Batts and Blankets* (Optional) IYy Placed in stud cavities, any glass fiber
<br />or mineral wool insulation bearing the UL Classification Marking as to Surface
<br />Burning Characteristics and/or Fire Resistance. See Batts and Blankets ( KNV or
<br />BZJZ) Categories for names of Classified companies.
<br />4. Gypsum Board* Gypsum panels with beveled, square or tapered edges, applied
<br />vertically or horizontally. Vertical joints centered over studs and staggered
<br />one stud cavity on opposite sides of studs. Vertical joints in adjacent layers
<br />(multilayer systems) staggered one stud cavity. Horizontal joints need not be backed
<br />by steel framing. Horizontal edge joints and horizontal butt joints on opposite sides of
<br />studs need not be staggered. Horizontal edge joints and horizontal butt joints in
<br />adjacent layers (multilayer systems)staggered a min. of 12 in. The thickness and number
<br />of layers for the 1 hr, 2 hr, 3 hr and 4 hr ratings are as follows:
<br />Wallboard Protection on Each Side of Wall
<br />No.of Layers Min Thkns
<br />Min Stud & Thkns of Insulation
<br />Rating Depth of Panel (Item 3)
<br />1 3-1/2 1 layer,%in. thick Optional
<br />1 2-1/2 1 layer,%2in. thick 1-1/2 in.
<br />1 1-5/8 1 layer,3/4in, thick Optional
<br />2 1-5/8 2 layers,'hin. thick Optional
<br />2 1-5/8 2 layers,%in. thick Optional
<br />3 1-5/8 3 layers,%2in. thick Optional
<br />3 1-5/8 2 layers,3/4in, thick Optional
<br />3 1-5/8 3 layersAin. thick Optional
<br />4 1-5/8 4 layers,%in. thick Optional
<br />4 1-5/8 4 layers,)/21n. thick Optional
<br />4 2-1/2 2 layers 3/1n. thick 2 in.
<br />CANADIAN GYPSUM COMPANY - %21n. thick Type C, IP-X2 or [PC -AR; WRC,%in. thick Type AR, C, IP-AR,
<br />IP-X1, IP-X2, [PC -AR, SCX, SHX, WRX or WRC;y4in. thick Type IP-X3, ULTRACODE, ULTRACODE SHC
<br />or ULTRACODE WRC.
<br />UNITED STATES GYPSUM CO - %2in. thick TTe C, IP-X2, IPC-AR or WRC;%In. thick Type SCX, SHX, WRX,
<br />IP-Xl, AR, C. WRC, FRX-G, IP-AR, IP-X2, IPC-AR ;/Ln. thick Type IP-X3, ULTRACODE, ULTRACODE
<br />SHC or ULTRACDDE WRC.
<br />USG MEXICO S A DE C V - 1/21n. thick Tye C, IP-X2, IPC-AR or WRC;`%ln. thick Type AR, C, IP-AR,
<br />IP-Xl, IP-X2, IPC-AR, SCX, SHX, WRX, WRC or;/41n. thick Type IP-X3, ULTRACODE, ULTRACODE SHC or
<br />ULTRACODE WRC.
<br />4A. Gypsum Board* (As an alternate to Item 4) 15/32 %in. thick gypsum panels,
<br />installed as described in Item 4 with Type S-12 steel screws. The length and
<br />spacing of the screws as specified under Item 5.
<br />CANADIAN GYPSUM COMPANY - Type FRX
<br />UNITED STATES GYPSUM CO - Type FRX
<br />USG MEXICO S A DE C V - Type SHX.
<br />5. Fasteners (Not shown) - Type S or S-12 steel screws used to attach panels to
<br />studs (Item 2) or furring channels (Item 6). Sin 1e layer systems: 1 in. long
<br />fory2and%in. thick panels or 1-1/4 tn. long for lin. thick panels,
<br />spaced 8 in. OC when panels are applied horizontally, or 8 in. OC along vertical
<br />and bottom edges and 12 in. OC in the field when panels are applied vertically. Two layer
<br />systems: First layer- 1 in. long fory2and%in, thick panels or 1-1/4 in.
<br />long fora/1n. thick panels, spaced 16 in. OC. Second layer- 1-5/8 in. long for%21n.,
<br />%in. thick panels or 2-1/4 in. long for%in. thick panels, spaced 16 in. OC with screws
<br />offset 8 in. from first layer. Three -layer systems: First layer- 1 in. long for
<br />Y21n.,%in.thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long
<br />for 2in.Ain. thick panels, spaced 24 in. OC. Third layer- 2-1/4 in. long forY2in., gin. thick
<br />panels or 2-5/8 1n. long for%in. thick panels, spaced 12 in. OC. Screws offset min
<br />in. from layer below. Four -layer systems: First layer- 1 in. long forll6in.,
<br />%in. thick panels, spaced 24 in. OC. Second layer- 1-5/8 in. long for%2in.,%in.
<br />thick panels, spaced 24 in. OC. Third layer- 2-1/4 in. long foryin. thick panels or 2-%in.
<br />long for%in. thick panels,spaced 24 in. OC. Fourth layer - 2-%in. long forl/21n. thick
<br />panels or 3 in. long for%ln. thick panels,spaced 12 in. OC. Screws offset min. 6 in.
<br />from layer below.
<br />6. Furring Channels (Optional, not shown, for single or double layer systems) - Resilient furring
<br />channels fabricated from min 25 MSG corrosion -protected steel, spaced vertically a max of 24 in.
<br />OC. Flange portion attached to each intersecting stud with 2 in. long Type S-12 steel screws.
<br />Not for use with Item 4A.
<br />7.Joint Tape and Compound Vinyl or casein, dry or premixed joint compound applied in two coats to
<br />joints and screw heads of outer layers. Paper tape, nom 2 in. wide, embedded in first layer of
<br />compound over all joints of outer layer panels. Paper tape a joint compound may be omitted
<br />when gypsum panels are supplied with a square edge.
<br />B. Siding, Brick or Stucco (Optional, not shown) - Aluminum, vinyl or steel siding, brick veneer
<br />or stucco, meeting the requirements of local code agencies, installed over gypsum panels. Brick
<br />veneer attached to studs with corrugated metal wall ties attached to each stud with steel screws,
<br />not more than each sixth course of brick.
<br />9. Caulking and Sealants* (Optional, not shown) - A bead of acoustical sealant applied around the
<br />partition perimeter for sound control.
<br />UNITED STATES GYPSUM CO - Type AS
<br />*Bearing the UL Classification Mark
<br />PENETRATION FIRESTOP DETAIL
<br />DESIGN NO. W-L-1001
<br />SCALE: NTS
<br />SECTION A -A
<br />(Formerly System No. 147)
<br />F Ratings 1 1, 2, 3 and 4 Hr (See Items 2 and 3)
<br />T Ratings - 0, 1, 2, 3, and 4 Hr (See Item 3)
<br />L Rating At Ambient - less than 1 CFM/sq ft
<br />L Rating At 400 F - less than 1 CFM/sq ft
<br />1. Wall Assembly The 1, 2, 3 or 4 hr fire -rated gypsum wallboard/stud wall assembly shall be
<br />constructed of the materials and in the manner described in the individual U300 or U400 Series Wall
<br />or Partition Designs in the UL Fire Resistance Directory and all include the following construction
<br />features:
<br />A. Studs Wall framing may consist of either wood studs (max 2 h fire rated assemblies) or steel
<br />channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC with nom 2 by 4 in.
<br />lumber end plates and cross braces. Steel studs to be min 3%1n.wide by 1-3/8 in. deep channels
<br />spaced max 24 in. OC.
<br />B. Gypsum Board* Nomy2or%gin, thick, 4 ft. wide with square or, tapered edges. The gypsum
<br />wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as
<br />specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max
<br />dram
<br />of opening is 13-1/2 in.
<br />2. Pipe or Conduit Nom 12 in. dram (or smaller) Schedule 10 (or heavier) steel pipe, nom 12 in.
<br />dram (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in. dram (or smaller)
<br />Class 50 (or heavier) ductile iron pressure pipe, nom 6 in. diam.(or smaller) steel conduit,
<br />nom 4 in. dram (or smaller) steel electrical metallic tubing, nom 6 in. dram (or smaller)
<br />Type L or (or heavier) copper tubing or nom 1 in. dram (or smaller) flexible
<br />steel conduit. When copper pipe is used, max F Rating of firestop system (Item 3)is 2 h.
<br />Steel pipes or conduits larger than nom 4 in, diam may only be used
<br />in walls constructed using steel channel studs. A max of one pipe or conduit is permitted in the
<br />firestop system. Pipe or conduit to be installed near center of stud cavity width and to be rigidly
<br />supported on both sides of wall assembly.
<br />3. Fill, Void or Cavity Material* 15), Caulk Caulk fill material installed to completely fill annular
<br />space between pipe or conduit and gypsum wallboard and with a min%1n.diam bead of caulk
<br />applied to perimeter of pipe or conduit at its egress from the wall.Caulk installed symmetrically on
<br />both sides of wall assembly. The hourly F Rating of the firestop system is dependent upon the
<br />hourly fire rating of the wall assembly in which it is installed, as shown in the following table.
<br />The hourly T Rating of the firestop system is dependent upon the type or size of the pipe or
<br />conduit and the hourly fire rating of the wall assembly in which it is installed, as tabulated below:
<br />Max Pipe or Conduit Diam In. Annular Space In. F Rating Hr T Rating Hr
<br />1 0 tows 1 or 2 0+, 1 or 2
<br />1 1/ to�6 3 or 4 3 or 4
<br />4 0 to 1-Y2 1 or 2 0
<br />6 1/4to%2 3 or 4 0
<br />12 W6tog Ior 2 0
<br />+When copper pipe is used, T Rating is 0 h.
<br />MINNESOTA MINING & MFG CO - CP 25WB+.
<br />*Bearing the UL Classification Mark
<br />FIRE RESISTANCE DETAIL
<br />DESIGN NO. U901
<br />SCALE: NTS
<br />= `--t- - -
<br />1. Concrete Blocks* Various designs. Classification B-4 (4 hr).
<br />See Concrete Blocks category for lists of eligible manufacturers.
<br />2. Mortar Blocks laid in full bed of mortar, nom.%in. thick, of not less than 2-1/4 and not
<br />more than 3-1/2 parts of clean sharp sand to 1 part Portland cement (proportioned by volume)and
<br />not more than 50 percent hydrated lime (by cement volume). Vertical joints staggered.
<br />3. Portland Cement Stucco or Gypsum Plaster If used, add'/2hr, to Classification
<br />4. Loose Masonry Fill If all core spaces are filled with loose dry expanded slag, burned clay or
<br />shale (rotary kiln process), water repellant vermiculite masonry fill insulation, or silicone
<br />treated perlite loose fill insulation,. Class 0-2 (2 hr) or C-3 (3 hr) concrete blocks will provide
<br />a 4 hr fire resistance rating.
<br />*Bearing the UL Classification Mark
<br />FIRE RESISTANCE DETAIL
<br />DESIGN NO. U914
<br />SCALE: NTS
<br />a ❑gip❑
<br />24'
<br />1. Concrete Blocks* Various designs. Classification D-2 (2 hr). See Concrete Blocks category for
<br />list of eligible manufacturers.
<br />2. Mortar Blocks laid in full bed of mortar, nom%in. thick, of not less than 2-1/4 and not more
<br />than 3-1/2 parts clean sharp sand to 1 part Portland cement (proportioned by volume)and not more
<br />than 50 percent hydrated lime (by cement volume). Vertical joints staggered.
<br />3. Furring Channels Min 0.019 in, thick (25 gauge) gale steel, 1-3/8 in. wide on top and 2-3/4 in.
<br />wide at bottom byy8in. deep. Spaced 24 in. OC perpendicular to floor with a channel parallel to
<br />and approximately 3 in. above floor and 3 in. below ceiling. Clearance between vertical and
<br />horizontal channels'/L1n.
<br />4. Channel Fasteners 1-1/4 in, long masonry screws withX6in, body andNi6in. diameter head.
<br />Fasteners spaced 24 in. O.C. with the fasteners staggered on each long leg of the furring channel.
<br />4A. Steel Framing Members* (Not Shown) - Alternate method used to attach furring channels (Item
<br />3) to concrete blocks (Item 1). Clips spaced 48 in. OC., and secured to blocks withy4in. dia. By 3
<br />in. long concrete expansion anchor (Item 4B) through the center grommet.
<br />Furring channels are friction fitted into clips.
<br />PAC INTERNATIONAL - Type RSIC-1.
<br />4B. Concrete Expansion Anchor (Not Shown) - 'Ain. dia. by 3 in. long carbon steel, pre -assembled,
<br />nail drive expansion anchor with mushroom head driven into the web of the concrete block. Min.
<br />embedment in concrete block of 1-3/8 in. and evaluated in accordance with ASTM E 486 to have
<br />Ultimate load capacities of 980 lbs (tension)and 1400 lbs (shear)when used in 2000 psi concrete.
<br />5. Gypsum Board*Y2in. thick, 4 ft wide, secured to furring channels with wallboard fasteners
<br />(Item 6). Gypsum plaster not more than%bin. thick may be applied to wallboard in addition to
<br />joint treatment.
<br />AMERICAN GYPSUM CO - Types AG-C,AGX-C.
<br />BORAL GYPSUM INC - Type BG-C.
<br />CANADIAN GYPSUM COMPANY - Types C, IP-X2, IPC-AR.
<br />CONTINENTAL GYPSUM COMPANY - Types CO-C,CG5-5,CGTC-C.
<br />G-P GYPSUM CORP, SUB OF
<br />GEORGIA-PACIFIC CORP - Type 5.
<br />JAMES HARDIE GYPSUM INC - Type Max°C".
<br />LAFARGE NORTH AMERICA INC - Types LGFC-C,LGFC-C/A.
<br />NATIONAL GYPSUM CO - Type FSW-C.
<br />PABCO GYPSUM, DIV OF
<br />PACIFIC COAST BUILDING PRODUCTS INC - Type PG-C.
<br />STANDARD GYPSUM L L C - Type SG-C.
<br />TEMPLE -INLAND FOREST PRODUCTS CORP - Type TG-C.
<br />UNITED STATES GYPSUM CO - Types C,IP-X2,IPC-AR.
<br />USG MEXICO S A DE C V - Types C, IP-X2, IPC-AR.
<br />6. Wallboard Fasteners 1 in. long, self -drilling, self -tapping steel screws with bugle heads.
<br />Fasteners attached to each furring channel and spaced 8 in. OC at butt joints and 12 in. OC in the
<br />field of the board parallel with furring channels. Clearance
<br />tween fasteners and edges of wallboard 3/4 in.
<br />7. Joint System 15)� (Not shown) Paper tape embedded in cementitious compound over joints. Paper tape
<br />and exposed screw heads covered with two layers of compound. Edges of compound feathered out.
<br />*Bearing the UL Classification Mark
<br />-JOINT FIRESTOP DETAIL
<br />DESIGN NO. HW-D-0098
<br />SCALE: NTS
<br />FRONT VIEW SECTION A -A
<br />1. Metal roof deck assembly (non fire -rated)
<br />2. Concrete wall assembly (2-hr fire rated):
<br />A. Lightweight or normal weight concrete wall (min. 6 in. thick)
<br />B. Any UL/ULC classified concrete block wall.
<br />3. Mineral wall (min. 4 pcf density) compressed 33 percent and inserted into joint,
<br />flush with both sides of wall. (see no.3 below)
<br />4. Hilti CP 777 speed plugs friction fitted to completely fill flute, flush with both
<br />sides of wall (see note no. 3 below)
<br />5. Minimunyein. (wet) thickness Hilti CP 672 firestop joint spray to completely cover
<br />mineral wool and to overlap a minimum%2in. onto concrete wall and metal deck on
<br />both sides of wall assembly.
<br />Notes:
<br />1. Steel floor units may be sprayed with a minimum5A6 in. thickness to maximum
<br />1-yin thickness of UL classified monokote type MK-6/HY fireproofing manufactured
<br />by W.R. Grace
<br />2. When the steel deck is coated with fireproofing,Hilti CP 672 shall overlap the wall
<br />a min.!/2in and overlap the fireproofing a min.2 in. on both sides of the wall.
<br />3. As an alternated to Hilti CP 777 speed plugs, mineral wool (minimum 4 pcf density)
<br />compressed 33 percent may be used.
<br />4.T-Rating may not equal F-rating in accordance with UL 2079
<br />5. Fire Rating of joint is only as good as performance of metal roof deck assembly
<br />under fire conditions.
<br />All configuration shown are suggestions only and must be approved by the specifying
<br />architects or engineers for the project.
<br />This is not a UL Classified systems, But a modification of the closest applicable system
<br />(Reference: UL System No. HW-D-0098)
<br />FIRE RESISTANCE DETAIL
<br />DESIGN NO. X528
<br />SCALE: NTS
<br />113/°
<br />li
<br />�'
<br />11
<br />�N)III
<br />iiiiiiiiiiuiiiiii
<br />' I FURR DUT TO ACCOMODATE
<br />I �_,! PLUMBING VENT AND
<br />I------------ • CLEAN -OUT
<br />1. Steel Column Min sizes of W-shaped and tubular steel columns which appear in the AISC Steel
<br />Construction Manual as shown under Item 2.
<br />2. Gypsum Board* For I Hr rating, any /gin, or f21n. thick gypsum wallboard Classified for use
<br />in fire resistance assemblies. For 2 Hr and 3 Hr ratings, any %in. or Y21n. thick gypsum
<br />wallboard Classified for use in other 2 Hr, 3 Hr or 4 Hr Column Designs. Min total thickness of
<br />layersin inches for the various ratings and min column sizes are as follows:
<br />W Shaped Rating (Hr) Corner Details For Various Rating
<br />Column 1 2 3 1 Hr 2 Hr 3 Hr
<br />Min Column
<br />Size
<br />Total thickness (In.)
<br />W4xl3 11-1/2 2-1/4 B C D
<br />W6xl5.5 1 1-1/2 2-1/4 B C D
<br />W10x49 1/21-1/8 1-7/8 A B C
<br />Applied in layers as noted in the above illustrations. Boards are to be applied vertically
<br />without horizontal joints.
<br />See Gypsum Board (CKNX)category for names of manufacturers.
<br />2A. Gypsum Board* As an alternate to Item 2-XI.n. thick gypsum wallboard. For 2 Hr rating, 1-1/2
<br />Ln. total thickness, installed in accordance with corner detail B. For 3 Hr rating, 2-114 in. total
<br />thickness installed 1n accordance with corner detail C.Boards are to be applied vertically without
<br />horizontal joints.
<br />CANADIAN GYPSUM COMPANY - Type IP-X3, ULTRACODE, ULTRACODE SHC or ULTRACODE WRC.
<br />UNITED STATES GYPSUM CO - Type IP-X3, ULTRACODE, ULTRACODE SHC or ULTRACODE WRC.
<br />USG MEXICO S A DE C V - Type IP-X3,ULTRACODE, ULTRACDDE SHC or ULTRACODE WRC.
<br />3. Steel Stud 1-5/8 in. wide with 1-5/16 and 1-7/16 in. legs having a 1/4- in. folded flange,
<br />fabricated from No. 25 MSG gale steel. Length to be'/2in.less than the assembly height.
<br />3A. As an alternate to Item 3 Steel Framing Members* galv. steel clips spaced 4 ft OC and 1-1/4 in.
<br />from top and bottem of column.A No.28 MSG galv steel support angle with 1-1/4 in. length shall be
<br />placed over clips and secured with screws attaching the wallboards. The clips for use with wide
<br />flange columns only.
<br />COLUMN & BEAM INC - Types CB, CB1Clips.
<br />4. Corner Beads No.28 MSG gale steel,)-1/4 in. legs to be attached to the wallboard with No.6 by
<br />1 in. screws spaced 12 in. OC max.
<br />5. Tie Wire No.18 SWG steel wire spaced 24 in. OC used with second layer of wallboard.
<br />6. Screws For attaching first layer of wallboard to steel studs, and third layer of wallboard to 2
<br />in. by 2 in. steel angle (25 Ga) to be No. 6 by 1 in. (or 1-1/4 in. for%in. thick wallboard)
<br />Phillips head self -drilling, self -tapping double lead screwspaced 24 in. OC For attaching
<br />second layer of wallboard to steel studs and fourth layer of wallboard to 2 in. by 2 in. steel
<br />angle
<br />(25 Ga) to be No. 6 by 1-3/4 in. (or 2-1/4 in. for:y4in. thick wallboard) steel screws of the
<br />same type spaced 12 in. OC For attaching third layer of wallboard to steel studs to be
<br />No. 8 by 2-1/4 in. screws of the same type spaced 12 in. OC
<br />7.Finishing S stem (Not Shown) - Joint compound applied over corner beads to a
<br />thickness of i6 in.
<br />*Bearing the UL Classification Mark
<br />FIRE RESISTANCE DETAIL
<br />DESIGN NO. U905
<br />SCALE: NTS
<br />m .
<br />z
<br />3 ' D.. - D ' D
<br />��
<br />A ' `1
<br />1. Concrete Blocks* Various designs. Classification D-2 (2 hr).
<br />See Concrete Blocks category for list of eligible manufacturers.
<br />- 2. Mortar Blocks laid in full bed of mortar, nom.%in. thick, of not less than 2-1/4 and not more
<br />than 3-1/2 parts of clean sharp sand to 1 part Portland cement (proportioned by volume) and not
<br />more than 50 percent hydrated lime (by cement volume). Vertical joints staggered.
<br />3. Portland Cement Stucco or Gypsum Plaster Add!/2hr to classification if used. Where combustible
<br />members are framed in wall, plaster or stucco must be applied on the face opposite framing to
<br />achieve a max. Classification of 1-1/2 hr. Attached to concrete blocks (Item 1).
<br />4. Loose Masonry Fill If all core spaces are filled with loose dry expanded slag, expanded clay or
<br />shale (Rotary Kiln Process), water repellant vermiculite masonry fill insulation, or silicone
<br />treated perlite loose fill insulation add 2 hr to classification.
<br />5. Foamed Plastic* (Optional -Not Shown) - 1-1/2 in. thick max, 4 ft wide sheathing attached to
<br />concrete blocks (Item 1).
<br />CELOTEX CORP -Type Thermax
<br />SCALE: NTS
<br />FRONT VIEW SECTION A -A
<br />1. Metal roof deck assembly (non fire -rated)
<br />2. Concrete wall assembly (2-hr fire rated):
<br />A. Lightweight or normal weight concrete wall (min. 6 in. thick)
<br />B. Any UL/ULC classified concrete block wall.
<br />3. Mineral wall (min.4 pcf density) compressed 33 percent and inserted into joint,
<br />flush with both sides of wall. (see no.3 below)
<br />4. Minimuni/gin. (wet) thickness Hilti CP 672 firestop joint spray to completely cover
<br />mineral wool and to overlap a minimum%21n. onto concrete wall and metal deck on
<br />both sides of wall assembly.
<br />Notes:
<br />1. Steel floor units may be sprayed with a minimum%&in.thickness to maximum
<br />1-3/4in thickness of UL classified monokote type MK-6/HY fireproofing manufactured
<br />by W.R. Grace
<br />2. When the steel deck is coated with fireproofing, Hilti CP 672 shall overlap the wall
<br />a min.y2in and overlap the fireproofing a min. 2 in. on both sides of the wall.
<br />3.T-Rating may not equal F-rating in accordance with UL 2079
<br />4. Fire -Rating of joint is only as good as performance of metal roof deck assembly
<br />under fire conditions.
<br />All configuration shown are suggestions only and must be approved by the specifying
<br />architects or engineers for the project.
<br />This is not a UL Classified systems, But a modification of the closest applicable system
<br />(Reference: UL System No. HW-D-0181)
<br />JOINT FIRESTOP DETAIL
<br />DESIGN NO. HW-D-0098
<br />SCALE: NTS
<br />FRONT VIEW SECTION A -A
<br />).Floor Assembly The fire rated fluted steel unit/concrete floor assembly shall be constructed of
<br />the materials and in a manner described in the individual D700 or D900 Floor -Ceiling Design in the
<br />UL Fire Resistance Directory and shall include the following construction features:
<br />A. Steel Floor and Form Units* Max 2 in. deep gals steel fluted floor units.
<br />B. Concrete Min 2-1/2 in thick reinforced concrete as measured from top plane of the floor units.
<br />C. Spray -Applied Fire Resistive Materials* (Optional) - (Not Shown) - Prior to the installation
<br />of the
<br />forming material and fill, void or cavity material (Items 3A, 3B) the steel floor units may be
<br />sprayed with a minw16in. to max 1-3/4 in. thickness of firesistive material.
<br />W R GRACE & CO - CONN
<br />CONSTRUCTIDN PRODUCTS DIV - Type MK-6-HY
<br />IA. Roof Assembly (Not Shown) - As an alternate to the floor assembly, a fire rated fluted steel
<br />deck roof assembly may be used. The roof assembly shall be constructed of the materials and in the
<br />manner described in the individual P900 Series Roof -Ceiling
<br />Design in the UL Fire Resistance Directory. The hourly rating of the roof assembly shall be equal
<br />to or greater than the hourly rating of the wall assembly.The roof assembly shall include the
<br />following construction features:
<br />A. Steel Roof Deck Max 2 in. deep galv steel fluted roof deck.
<br />B. Roof Insulation Min 2-1/4 in. thick poured insulating concrete, as measured from the top plane
<br />of the floor units.
<br />1B.Roof Assembly As an alternate to Items 1 and lA,a fire rated protected fluted steel deck roof
<br />assembly may be used. The roof assembly shall be constructed of the materials and in the manner
<br />described in the individual P700 Series Roof -Ceiling Design
<br />n the UL Fire Resistance Directory. The hourly rating of the roof assembly shall be equal to or
<br />greater than the hourly rating of the wall assembly. The roof assembly shall include the following
<br />construction features. -
<br />A. Steel Roof Deck Max 2 in. deep galv steel fluted roof deck.
<br />B. Spray - Applied Fire Resistive Materials* (Not Shown)% Prior to the installation of the steel
<br />ceiling runners, Forming Material and Fill, Void or Cavity Material (Items 2A, 3A, 3B), the roof
<br />assembly shall be sprayed with the type and thickness of fire resistive material indicated in the
<br />individual P700 Series design.
<br />2. Wall Assembly Min 6 in. thick steel -reinforced lightweight or normal weight (100-150 pcf)
<br />structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
<br />See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
<br />3. Joint System Max separation between bottom of floor or roof and top of wall at time of
<br />installation of joint system is 1 in. The joint system is designed to accommodate a max 12.5
<br />percent compression or extension from its installed width. The joint system shall consist of the
<br />following:
<br />AFormingMatra m 4. f mineral I insulation m n e 1 1 No 0 pc i e al woo bat( i sulatio compressed and firmly packed to
<br />completely fill the flutes and the gap between the top of the wall and bottom of the floor or roof
<br />as a permanent form. Batt insulation cut to the shape of the fluttted steel deck, approx 33 percent
<br />larger than the flutes. Pieces compressed and installed vertically into the flutes above the top of
<br />the wall. Additional pieces of batt insulation, min 6
<br />HILTI INC - CP777 Speed Plugs
<br />B. Fill, Void or Cavity Material* Minyein. wet thickness of fill material sprayed or troweled on
<br />each side of the wall to completely cover mineral wool forming material and to overlap a min ofY2
<br />in. onto wall and steel deck on both sides of wall. When spray -applied fire resistive material* is
<br />applied to the steel steel deck, the fill material is to overlap the wall a min of%2in. and the
<br />spray -applied fire resistive material a min of 2 in. on both sides of wall
<br />HILTI CONSTRUCTION CHEMICAL, DIV OF
<br />HILTI INC - CP672 Firestop Spray
<br />JOINT FIRESTOP DETAIL
<br />DESIGN NO. HW-D-0181
<br />SCALE: NTS
<br />D. .
<br />__ � j
<br />,
<br />�____-__1_
<br />).Floor
<br />Assembly The 2 hr fire -rated fluted steel deck/concrete floor assembly shall be
<br />constructed of the materials and in the manner described in the individual D700 Floor-Ceiing Design
<br />Ln the UL Fire Resistance Directory and shall include the following construction features:
<br />A. Steel Floor And Form Units* Max 3 in. deep galv steel fluted floor units.
<br />B. Concrete Min 2-1/2 in. thick reinforced concrete,as measured from the top plane of the floor
<br />units.
<br />C. Spray -Applied Fire Resistive Materals* (Optional)t5& (Not ShownAh Prior to the installation of the
<br />forming material and fill, void or cavity material (Item 3A, 3B) the steel floor units may be
<br />spra ed with a
<br />m1nT6 to max 1-3/4 in. thickness of fire resistive material in accordance with the specifications in
<br />the individual D700 Series Design.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF
<br />HILTI INC % Type MK-6-HY
<br />2. Wall Assembly Min 8 in. thick reinforced lightweight or normal weight (100-150 pcf) structural
<br />concrete. Wall shall be installed parallel with the flutes of the steel floor and form units (Item
<br />IA). Wall may
<br />also be constructed of any UL Classified 2 fire rated Concrete Blocks*.When wall is constructed of
<br />concrete blocks, the top course of block shall be filled with concrete, grout or mortar.
<br />See Concrete Blocks (CAZT)category in the Fire Resistance Directory for names of manufacturers.
<br />3. Joint System Max separation between bottom of spray -applied fire resistive and top of the wall
<br />at time of installation of joint system is 1 in. The joint system is designed to accommodate a max
<br />12.5 percent compression or extension from its installed width. The joint system consists of the
<br />following:
<br />A. Forming Material* Min 4 pcf mineral wool batt insulation cut into strips with a width approx
<br />equal to the overall thickness of the wall. Strips compressed 33 percent in thickness and inserted
<br />Into the gap between the top of the wall and the bottom of the floor units. When the void beneath
<br />the
<br />protected steel deck is located entirely above the wall, the void shall be completely filled with
<br />mineral wool insulation compressed 33 percent in thickness. When void beneath the steel deck is
<br />located in part abo
<br />the wall, that portion of the void above the wall shall be packed with additional strips of
<br />mineral wool batt insulation compressed 33 percent in thickness.
<br />ROCK WODL MANUFACTURING CO 15� Delta Boerd
<br />B. Fill, Void or Cavity Material* Minl/gln. wet thickness of fill material sprayed or troweled on
<br />each side of the wall to completely cover mineral wool forming material and to overlap a min of%2
<br />in. onto wall and steel deck on both sides of wall. When spray -applied fire resistive material* 15
<br />applied to the steel floor and form units, the fill material is to overlap the wall a min ofY2in.
<br />and the spray -applied fire resistive material a min of 2 in. on both sides of wall.
<br />HILTI CONSTRUCTION CHEMICAL, DIV OF
<br />HILTIINC.- CP672 Firestop Spray
<br />P u b 11'6 XG
<br />SUPER MARKETS
<br />CORPORATE OFFICES, FACILITIES DESIGN
<br />BOX 407, LAKELAND, FL 33802
<br />(8631680.5295
<br />PHYSICAL ADDRESS:
<br />3300 PUBLIX CORPORATE PARKWAY,
<br />LAKELAND, FL 33811-3311
<br />PUBLIX FACILITIES
<br />DESIGN DEPARTMENT
<br />DAVID TAULBEE, AIA
<br />ARCHITECT- FL. REG, 91318
<br />DAVID RUBIN, AIA
<br />ARCHITECT -FL. REG.92557
<br />GA. REG.] 1881
<br />SC. REG.7477
<br />Al. REG,6234
<br />TN.REG.103497
<br />JOHN W. KITCHENS, PE
<br />CIVIL/STRUCTURAL - FL, REG. 45277
<br />GA. REG. 020251
<br />SG REG.]6340
<br />AL REG.20382
<br />TN.REG.101507
<br />PAUL C. HARMAN, PE
<br />STRUCTURAL- FL. REG. 51959
<br />GA.REG.27740
<br />SC. REG. 21754
<br />AL. REG.24905
<br />TN. REG.107882
<br />JOHN J. CARAMALIS, PE
<br />MECHANICAL - FL REG. A3889
<br />GA. REG. 021246
<br />SG REG.16521
<br />AL REG.20581
<br />TN. REG.108507
<br />ANTHONY CLEMENTI, PE
<br />MECHANICAL - FL REG. 54781
<br />GA. REG.31882
<br />SC. REG. 25591
<br />AL REG.28469
<br />TN. REG. I]1382
<br />RAYMOND J. SIRIANNI, PE
<br />ELECTRICAL - FL REG. 54085
<br />GA.REG.025636
<br />SC. REG. 19743
<br />AL REG.23065
<br />TN. REG.108038
<br />NORMAN MEIER, PE
<br />ELECTRICAL - FL. REG. 59422
<br />GA. REG. 31492
<br />SC. REG. 25290
<br />AL REG.28079
<br />© COPYRIGHT 2008
<br />PUBLIX SUPER MARKETS, INC
<br />THESE CONSTRUCTION DOCUMENTS ARE THE PROPERTY
<br />OF PUBLIX SUPER MARKETS, INC. AND ARE NOT TO BE
<br />COPIED OR REUSED FOR ANY SPECIFIC BUILDING WITHOUT
<br />WRITTEN PERMISSION. THESE DRAWINGS SHALL NOT BE
<br />DUPLICATED WITHOUT PRIOR WRITTEN PERMISSION OF
<br />PUBLIX SUPER MARKETS, INC.
<br />THE DESIGN INDICATED IN THESE CONSTRUCTION
<br />DOCUMENTS DOES; TO THE BEST OF MY KNOWLEDGE,
<br />INFORMATION, AND BELIEF; COMPLY WITH THE APPLICABLE
<br />MINIMUM BUILDING CODES
<br />N 1 1 2008
<br />l�
<br />�{
<br />PLOT DATE:
<br />1 Q P-0
<br />REVISION DATA:
<br />#1245 (REPL. #0390)
<br />ZEPHYR COMMONS
<br />PRETTY POND RD. & HWY. 301
<br />ZEPHYRHILLS, PASCO CO.,
<br />FLORIDA
<br />54,4
<br />M2707
<br />DRAWING TITLE:
<br />UL DESIGNS
<br />SCALE: NONE
<br />UL-1