Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FfF <br />DUPLEX OUTLET ABOVE COUNTER <br />FETw.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />61 <br />�?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />114 :1 <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />1-H <br />PUSH BUTTON SWITCH (OPTIONAL) <br />�D <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TV <br />TELEVISION (OPTIONAL) <br />®2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />M <br />ELECTRIC METER <br />NMI <br />PANEL <br />DISCONNECT SWITCH <br />G � <br />ROUGH -IN FOR OPT, CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />L T J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />150A/200A INDOOR <br />PANELCENTER <br />NEMA 1 <br />150 AMPI <br />200 AMP <br />#14 to lights & outlets <br />#12 to appliances and GA <br />#10 to WH <br />#8 to Range <br />#6 to HVAC <br />METER II <br />MO V <br />150=2/0 <br />200=4/0 in 2" Conduit <br />200 amp <br />150 amp <br />UNDERGROUND IDis <br />SERVICE BY POWER CO.---, <br />INTERSYSTEM <br />BONDING <br />TERMINATION PER <br />Bare Cu Ground <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />0 <br />PLUMBING RISER <br />NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />DEDICATED RECEPTACLE <br />H.B. FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />DISC. <br />� 7 � <br />- RANGE <br />PER SPECS / Ttr Ht / r\ <br />PENDANT AS / <br />U.�C5. SWITCH <br />FC R 1SI5OSAL <br />INK / DISC <br />\ AF E D.W. -- - <br />PATS' GFI <br />�----- — GFI �-------�—�-- <br />� <br />WP <br />GE M I <br />j U.C. OUTLET <br />I <br />U.C. OUTLET <br />FOR DW <br />I ROUGH -IN FOR <br />OPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />1 <br />1 <br />FA 0 RM <br />i <br />I <br />I <br />I ' <br />I <br />I <br />i \ <br />nu <br />'DD. <br />ROUGH -IN FOR <br />OPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />� <br />` <br />V/'` <br />V OWNER' S S ITE <br />I <br />a <br />SCALE: NTS <br />I <br />I <br />I <br />GI <br />I <br />--_— <br />OPT, I <br />REF. <br />I <br />ki <br />ROUGH -IN FOR \ <br />OPT. CLG. FAN/ <br />IGHT PRE-WIRE6; <br />BEDROOM <br />n <br />X E <br />ROUGH -IN FOR <br />/ OPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />12 <br />I /%� E <br />BED�IbO� <br />� 1 <br />\ ,l CSD <br />/ C.M <br />AR <br />OUGH-IN FOR <br />/ /BOPT. CLG. FAN <br />��4WR/E <br />tt <br />S. <br />- - -f'GFI @ 44" <br />- i <br />A.F.F. <br />-- - �• <br />j GFI <br />OPT.- <br />D. <br />I 11 I I I <br />_r_ <br />I � I <br />GFI F. 44" <br />� A.F.F. � <br />GFI FOR I <br />GAR. DOOI� <br />2 CAR GARAG EGFI <br />I I <br />� W"I.C. I 1 <br />I I <br />I I <br />I I <br />I I <br />1 0 1 <br />j W.H.I VERIFY LOCATION <br />ELECTRICAL PANEL _IRRIGATION <br />GFI @ 44"A.F.F. <br />RECEPT. —T= (V 1W WP H.B. <br />FOR ALARM VERIFY METER GFI <br />SYSTEM LOCATION WITH <br />BUILD R <br />15-0" <br />NTRY <br />ELECTRICAL PLAN - ELEV-Al <br />SCALE: %4"=1'-0" <br />n0 <br />tr) <br />:. <br />�o <br />a cv cc sMl <br />•4f <br />'g C7 �i <br />® <br />X N <br />m <br />W <br />m cca =mac <br />iei a+ to .€ucx <br />� . <br />N <br />G <br />CL- La <br />M <br />CD, <br />0 <br />CV <br />CD <br />CV <br />0 <br />n <br />s <br />Q P ' <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />W <br />4C <br />�E <br />O M U <br />s, <br />v <br />N 0 <br />C , - N co <br />oD r` <br />rn <br />3 N <br />tnN0 4 <br />IC13tq <br />I`+ni <br />V <br />N c'7 V �3yy # LL <br />W LL U_ . 0- <br />0_ <br />a Y <br />Z <br />� <br />j r- <br />c 'T rn <br />Z :E! 9 <br />W <br />m N of �0 <br />W <br />Z <br />I IL <br />og 5 <br />ct °. m w <br />LOCO) C"Z a r <br />Z <br />N OU < o <br />W <br />N (h <br />00 <br />N <br />z o � <br />—! <br />U) <br />to <br />z <br />�1' <br />� a <br />LL <br />T <br />N <br />U-i <br />- .- <br />U <br />O <br />N <br />ws <br />.) <br />U <br />w <br />r— — E <br />— <br />3 <br />rjl'9j�, <br />C.3 0 � <br />• <br />i <br />c �' <br />¢ N 0 <br />�10 <br />Y <br />o <br />M <br />0 � <br />w <br />z <br />L.L E <br />U <br />z o <br />Z p <br />4 <br />Q O <br />o <br />Ze <br />r`° B <br />0 <br />U <br />�o <br />�E <br />��n, <br />U <br />ZCo <br />�z <br />wz <br />a, I— <br />8 <br />w <br />�o <br />mo <br />Oz <br />m J <br />m <br />Q <br />0 <br />¢� <br />0<� <br />Z <br />o <br />g <br />Ia <br />A <br />CC) <br />< <br />OK <br />d Z <br />N F <br />m <br />o� <br />�3 <br />�O <br />F <br />O <br />� <br />Li <br />a <br />0 <br />zl¢ <br />C:O <br />0 <br />= <br />> <br />Lm <br />LO <br />cc <br />cc <br />L0 <br />d. <br />O <br />O <br />Y <br />Y <br />� <br />}, <br />_M <br />U <br />W <br />m <br />LL0 <br />U) <br />r <br />Q� <br />+�„j <br />p <br />- N <br />c) <br />r <br />LL. N <br />M <br />LO 0 <br />Ln <br />r <br />Q <br />r <br />(0� <br />E <br />c <br />M <br />Z° <br />to <br />Z <br />: <br />E O <br />U) <br />m <br />E <br />a <br />c <br />c <br />0-U <br />_j <br />Q 0 <br />JOB <br />NO: <br />23-04657 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4 <br />