Laserfiche WebLink
4 <br />3 <br />F <br />1 <br />E <br />0 <br />C <br />B <br />A <br />TO AC-1 <br />33; 150A <br />TO AC-2 <br />27; 100A <br />TO AC-3 <br />PANEL MDP <br />1200A MCB <br />F ............................. 250/3 25013 <br />PER NEC 230.71(A) THIS <br />DEVICE SHALL NOT BE j <br />CONSIDERED A SERVICE <br />DISCONNECTING MEANS <br />BECAUSE IT IS SOLELY 1 <br />USED FOR A SURGE <br />SUPPRESSION DEVICE. <br />i <br />TVSS � <br />I <br />I <br />SA <br />FIELD CONNECT �- <br />SURGE ARRESTOR <br />TO MAIN LUGS <br />FOUR 4" CONDUITS, <br />EACH WITH 4#350 KCMIL <br />250/3 <br />150/3 <br />100/3 <br />30/3 <br />250/3/ST <br />250/3/ST <br />110/3 <br />-0 o <br />SPACE <br />1#6 IN 3/4" CONDUIT TO <br />PHONE SERVICE <br />NEUTRALBAR <br />#4/0 MAIN BONDING <br />JUMPER <br />THE GFCI BRANCH BREAKERS IN PANELS <br />D1 AND D2 ARE 65K SERIES RATED WITH <br />AN UPSTREAM BREAKER NO LARGER THAN <br />250 AMP. THE 250 AMP PANELS D1 AND D2 <br />ARE 55" HIGH AND CANNOT BE STACKED. <br />j PANEL D1 j j PANEL D2 j <br />i 250A MLO i i 250A MLO i <br />I I I <br />I I <br />I I <br />I I I I <br />I I I I <br />I I <br />1 40; 250A <br />GROUND BAR (BONDED <br />TO THE ENCLOSURE) <br />GROUND PER NEC 250; 1#3/0 <br />MINIMUM IN 3/4"C TO MAIN WATER <br />SERVICE PIPE WITH 1#4 FROM THE <br />MAIN WATER SERVICE PIPE TO THE <br />REFER TO THE ELECTRICAL PLAN <br />GROUNDING COMPONENTS (I.E. <br />AND/OR SITE PLAN FOR ROUTING TO <br />GROUND ROD, CONCRETE <br />THE POWER COMPANY'S <br />ENCASED ELECTRODE) AND A #3/0 <br />TRANSFORMER AND THRU A METER <br />BONDING JUMPER (PER 250.53.0 <br />IF IT IS ON THE BUILDING (WITH CT <br />AND TABLE 250.66) TO THE STEEL <br />CABINET) OR ON THE TRANSFORMER. <br />STRUCTURE - IF APPLICABLE. <br />SINGLE LINE DIAGRAM <br />C2 NO SCALE <br />SINGLE -LINE DIAGRAM NOTES <br />1. VERIFY SERVICE LOCATIONS AND CONFORM TO THE REQUIREMENTS OF THE <br />POWER COMPANY AND/OR DEVELOPER. POWER COMPANY AND/OR DEVELOPER <br />SHALL BE CONTACTED PRIOR TO BEGINNING CONSTRUCTION TO ARRANGE AND <br />VERIFY FOR THE INSTALLATION OF THE POWER COMPANY SERVICE, METER, <br />AND OTHER ITEMS. <br />2. GROUND ALL EQUIPMENT AND SERVICES IN ACCORDANCE WITH ARTICLE 250 <br />OF THE NATIONAL ELECTRICAL CODE, LOCAL APPLICABLE CODES, AND ALSO <br />AS INDICATED ON DRAWINGS. <br />3. MAKE NECESSARY INSPECTIONS OF EXISTING SITE AND SERVICE LOCATIONS AS <br />REQUIRED FOR THIS WORK AND MAKE ALLOWANCE FOR EXISTING CONDITIONS <br />BEFORE SUBMITTING BID. VERIFY WORK REQUIRED WITH POWER COMPANY AND <br />TELEPHONE COMPANY. <br />4. CUT AND PATCH THE CONSTRUCTION WORK AS REQUIRED FOR PROPER <br />INSTALLATION OF THE ELECTRICAL WORK. ALL PATCHING SHALL MATCH THE <br />SURROUNDING WORK TO THE SATISFACTION OF THE ARCHITECT. ALL CONDUIT <br />SHALL BE INSTALLED CONCEALED UNLESS SPECIFICALLY APPROVED BY THE <br />ARCHITECT. COORDINATE SAW CUTTING WITH LANDLORD'S OR OWNER'S <br />REPRESENTATIVE. <br />5. WIRE AND CABLE: <br />A. CONDUCTORS SHALL BE COPPER, #12 AWG, MINIMUM UNLESS <br />SPECIFICALLY NOTED OTHERWISE. <br />B. CONDUCTOR #10 AWG AND SMALLER SHALL BE SOLID AND #8 AWG AND <br />LARGER SHALL BE STRANDED. INSULATION SHALL BE 600 VOLT, <br />THHN/THWN. <br />6. PROVIDE ENGRAVED LAMINATED PHENOLIC BLOCK -ON -WHITE (UNLESS NOTED <br />OTHERWISE) NAMEPLATES SECURED TO EQUIPMENT WITH ADHESIVE AND <br />SCREWS FOR PANELBOARDS, RELAY CABINETS, TRANSFORMERS, DISTRIBUTION <br />BOARDS, AND MAIN PANELBOARD - IDENTIFYING EQUIPMENT DESIGNATION <br />(CORRESPONDING WITH DESIGNATION USED ON DRAWINGS) AND EQUIPMENT <br />VOLTAGE. LETTERING SHALL BE 1/4" HIGH. PROVIDE LABELS FOR CIRCUIT <br />BREAKERS, FUSIBLE SWITCHES AND STARTERS IN PANELBOARDS AND <br />DISTRIBUTION BOARDS FOR EACH DEVICE IDENTIFYING EQUIPMENT <br />CONTROLLED. LETTERING SHALL BE 1/8" HIGH. <br />7. ALL DEVICES SHALL HAVE AN INTERRUPTING CAPACITY NOT LESS THAN THE <br />POWER COMPANY AVAILABLE FAULT CURRENT, OR AS INDICATED ON THE <br />DRAWINGS. <br />8. 120/208 VOLT BRANCH CIRCUIT PANELBOARD BREAKERS SHALL HAVE A MINIMUM <br />U.L. SERIES RATING OF 65 KAIC WITH UP -STREAM FEEDER BREAKERS AS NOTED. <br />9. AVAILABLE SPACE FOR MAIN PANELBOARD IS LIMITED. PANELBOARD MUST FIN IN <br />ALLOCATED SPACE. COORDINATE WITH CONSTRUCTION AS REQUIRED. <br />10. ALL WIRING SHALL BE IN CONDUIT, E.M.T OR RIGID. FLEXIBLE CONDUIT MAY <br />ONLY BE USED FOR FINAL CONNECTIONS AND WITH GREEN EQUIPMENT <br />GROUNDING CONDUCTORS. <br />------------- <br />j PANEL C j <br />i 250A MLO i <br />I I <br />I I <br />I I <br />1L-----J-------- <br />40; 250A 1 <br />BRANCH FEEDER MARK NUMBER <br />WITH AMPERAGE, REFER TO THE <br />CONDUIT AND CONDUCTORS <br />SCHEDULE (THIS SHEET) FOR <br />REQUIREMENTS (TYP) <br />------------- <br />j PANEL B j <br />i 250A MLO i <br />I <br />I <br />I <br />I I <br />1 I <br />I I <br />1 40; 250A <br />------------- <br />j PANEL A j <br />250A MLO <br />40; 250A <br />PANEL POS <br />100A MLO <br />PROVIDE A JUMPER ON THE <br />j LUGS OF PANEL-POS SO <br />THAT BOTH PHASE BARS <br />ARE TIED TO THE ONE 120V <br />PHASE CONDUCTOR FROM <br />--1--� THE PIB <br />4; 20A 4+IG; 20A <br />J <br />in <br />POWER INTERFACE BOX (PIB). PROVIDE INCOMING J-BOX <br />AND OUTGOING J-BOX FLUSH IN THE WALL WITH FLEX <br />CONDUIT CONNECTIONS TO THE PIB. THE CONDUCTORS <br />ARE TO CONNECT TO THE TERMINAL BLOCKS OF THE PIB. <br />SWITCHGEAR AND CONTROL EQUIPMENT NOTES <br />1. PURCHASE PANELBOARDS, SURGE ARRESTOR, AND TVSS FROM ONE OF THE TWO <br />NATIONAL ACCOUNTS VENDORS (SEE SHEET E-902 SECTION C16440, PANELBOARDS) <br />PROVIDING SQUARE-D EQUIPMENT. NO SUBSTITUTIONS ALLOWED. <br />2. PURCHASE CONTROL PANEL'CFA-T500' FROM SUNCOAST ENVIRONMENTAL, INC. (NO <br />SUBSTITUTIONS ALLOWED). ALL EQUIPMENT IN THE CONTROL PANEL SHALL BE INSTALLED, <br />WIRED AND CONNECTED AT THE FACTORY, INCLUDING AUTOMATIC LIGHTING CONTROL <br />SYSTEM, LIGHTING RELAYS, HVAC STARTERS, POWER SUPPLIES, MISCELLANEOUS RELAYS <br />AND CONTROLS, AND THERMOSTATS. <br />3. CONTRACTOR SHALL PROVIDE PANEL FEEDERS A, B, C, D, AND POS, BRANCH <br />CIRCUIT CONDUIT AND WIRE, AND INSTALL ALL EQUIPMENT AS REQUIRED. <br />4. ALL BREAKERS AND PANELS SHALL BE SQUARE-D. <br />5. TVSS AND SURGE ARRESTOR UNITS SHALL BE MOUNTED DIRECTLY ADJACENT TO THE <br />SIDE OF THE MAIN DISTRIBUTION PANEL IN NEMA 3R ENCLOSURES. CLOSE NIPPLE THE <br />UNITS TO THE SIDE OF THE PANEL. PROVIDE CONNECTION OF TVSS UNIT TO BREAKER <br />IN PANEL. CONNECT SURGE ARRESTOR TO MAIN INCOMING LUGS OF THE PANE. <br />CONNECT USING MINIMUM LENGTH OF WIRE WITHOUT SHARP BENDS IN THE WIRE AND <br />SHALL NOT BE LENGTHENED FROM WIRE LENGTH PROVIDED WITH THE TVSS OR <br />SURGE SUPPRESSOR DEVICE. <br />J <br />131 CONDUIT AND CONDUCTORS SCHEDULE <br />Mark <br />No. <br />OCP <br />Device <br />(Amp/Poles) <br />Conductors <br />Total Am s <br />Conductors <br />Raceway Size Nominal <br />Inches <br />Phase &Neutral <br />Min Eq Grd <br />No. <br />Phase, Neutral & Equip Grd <br />With IG <br />60d C <br />75d C <br />Qty <br />Size <br />Type <br />Q /Set <br />Size <br />Sets <br />EMT <br />IMC <br />RIGID <br />PVC <br />EMT <br />IMC <br />PVC <br />1 <br />20/1 <br />20 <br />- <br />2 <br />12 <br />THHN <br />1 <br />12 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />2 <br />20/2 <br />20 <br />- <br />3 <br />12 <br />THHN <br />1 <br />12 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />3 <br />20/3 <br />20 <br />- <br />4 <br />12 <br />ITHHN <br />1 <br />12 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />4 <br />25/1 <br />30 <br />- <br />2 <br />10 <br />THHN <br />1 <br />10 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />5 <br />25/2 <br />30 <br />- <br />3 <br />10 <br />THHN <br />1 <br />10 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />6 <br />25/3 <br />30 <br />- <br />4 <br />10 <br />THHN <br />1 <br />10 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />7 <br />30/1 <br />30 <br />- <br />2 <br />10 <br />THHN <br />1 <br />10 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />8 <br />30/2 <br />30 <br />- <br />3 <br />10 <br />THHN <br />1 <br />10 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />9 <br />30/3 <br />30 <br />- <br />4 <br />10 <br />THHN <br />1 <br />10 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />10 <br />40/1 <br />40 <br />- <br />2 <br />8 <br />THHN <br />1 <br />10 <br />One <br />10.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />11 <br />40/2 <br />40 <br />- <br />3 <br />8 <br />THHN <br />1 <br />10 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />12 <br />40/3 <br />40 <br />- <br />4 <br />8 <br />THHN1 <br />1 <br />10 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />1.00 <br />13 <br />50/1 <br />55 <br />- <br />2 <br />6 <br />THHN <br />1 <br />10 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />14 <br />50/2 <br />55 <br />- <br />3 <br />6 <br />THHN <br />1 <br />10 <br />One <br />0.75 <br />0.75 <br />0.75 <br />0.75 <br />1.00 <br />1.00 <br />1.00 <br />15 <br />50/3 <br />55 <br />- <br />4 <br />6 <br />THHN <br />1 <br />10 <br />One <br />1.00 <br />1.00 <br />1.00 <br />1.00 <br />1.00 <br />1.00 <br />1.00 <br />16 <br />60/1 <br />70 <br />- <br />2 <br />4 <br />THW <br />1 <br />8 <br />One <br />1.00 <br />1.00 <br />1.00 <br />1.00 <br />1.25 <br />1.00 <br />1.25 <br />17 <br />60/2 <br />70 <br />- <br />3 <br />4 <br />THW <br />1 <br />8 <br />One <br />1.25 <br />1.00 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />18 <br />60/3 <br />70 <br />- <br />4 <br />4 <br />THW <br />1 <br />8 <br />One <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />19 <br />70/1 <br />70 <br />- <br />2 <br />4 <br />THW <br />1 <br />8 <br />One <br />1.00 <br />1.00 <br />1.00 <br />1.00 <br />1.25 <br />1.00 <br />1.25 <br />20 <br />70/2 <br />70 <br />- <br />3 <br />4 <br />THW <br />1 <br />8 <br />One <br />1.25 <br />1.00 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />21 <br />70/3 <br />70 <br />- <br />1 4 <br />4 <br />ITHW <br />1 <br />8 <br />1 One <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />22 <br />80/2 <br />85 <br />- <br />3 <br />3 <br />THW <br />1 <br />8 <br />One <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />23 <br />80/3 <br />85 <br />- <br />4 <br />3 <br />THW <br />1 <br />8 <br />One <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.50 <br />1.25 <br />1.50 <br />24 <br />90/2 <br />95 <br />- <br />3 <br />2 <br />THW <br />1 <br />8 <br />One <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.50 <br />1.25 <br />1.50 <br />25 <br />90/3 <br />95 <br />- <br />4 <br />2 <br />THW <br />1 <br />8 <br />One <br />1.50 <br />1.25 <br />1.50 <br />1.50 <br />1.50 <br />1.50 <br />1.50 <br />26 <br />100/2 <br />110 <br />- <br />3 <br />1 <br />THW <br />1 <br />6 <br />One <br />1.50 <br />1.50 <br />1.50 <br />1.50 <br />2.00 <br />2.00 <br />2.00 <br />27 <br />100/3 <br />110 <br />- <br />4 <br />1 <br />THW <br />1 <br />6 <br />One <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />28 <br />110/2 <br />- <br />115 <br />3 <br />2 <br />THW <br />1 <br />6 <br />One <br />1.25 <br />1.25 <br />1.25 <br />1.25 <br />1.50 <br />1.25 <br />1.50 <br />29 <br />110/3 <br />- <br />115 <br />4 <br />2 <br />THW <br />1 <br />6 <br />One <br />1.50 <br />1.25 <br />1.50 <br />1.50 <br />1.50 <br />1.50 <br />1.50 <br />30 <br />125/2 <br />- <br />130 <br />3 <br />1 <br />THW <br />1 <br />6 <br />One <br />1.50 <br />1.50 <br />1.50 <br />1.50 <br />2.00 <br />2.00 <br />2.00 <br />31 <br />125/3 <br />- <br />130 <br />4 <br />1 <br />THW <br />1 <br />6 <br />One <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />32 <br />150/2 <br />- <br />150 <br />3 <br />1 /0 <br />THW <br />1 <br />6 <br />One <br />2.00 <br />1.50 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />33 <br />150/3 <br />- <br />150 1 <br />4 <br />1 /0 ITHW <br />1 <br />6 1 <br />One <br />2.00 12.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />34 <br />175/2 <br />- <br />175 <br />3 <br />2/0 <br />THW <br />1 <br />6 <br />One <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />35 <br />175/3 <br />- <br />175 <br />4 <br />2/0 <br />THW <br />1 <br />6 <br />One <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.50 <br />2.50 <br />2.50 <br />36 <br />200/2 <br />- <br />200 <br />3 <br />3/0 <br />THW <br />1 <br />6 <br />One <br />2.00 <br />2.00 <br />2.00 <br />2.00 <br />2.50 <br />2.50 <br />2.50 <br />37 <br />200/3 <br />- <br />200 <br />4 <br />3/0 <br />THW <br />1 <br />6 <br />One <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />38 <br />225/2 <br />- <br />230 <br />3 <br />4/0 <br />THW <br />1 <br />4 <br />One <br />2.50 <br />2.00 <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />39 <br />225/3 <br />- <br />230 <br />4 <br />4/0 <br />THW <br />1 <br />4 <br />One <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />3.00 <br />3.00 <br />40 <br />250/3 <br />- <br />255 <br />4 <br />250 <br />THW <br />1 <br />4 <br />One <br />2.50 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />41 A <br />300/3 <br />- <br />285 <br />4 <br />300 <br />THW <br />1 <br />4 <br />One <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />41 B <br />300/3 <br />- <br />310 <br />4 <br />350 <br />THW <br />1 <br />4 <br />One <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3..00 <br />3.00 <br />42A <br />350/3 <br />- <br />335 <br />4 <br />400 <br />THW <br />1 <br />4 <br />One <br />3.00 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />42B <br />350/3 <br />- <br />380 <br />4 <br />500 <br />THW <br />1 <br />4 <br />One <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />43A <br />400/3 <br />- <br />380 <br />4 <br />500 <br />THW <br />1 <br />3 <br />One <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />43B <br />400/3 <br />- <br />400 <br />4 <br />3/0 <br />THW <br />1 <br />3 <br />Two <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />2.50 <br />44A <br />600/3 <br />- <br />570 <br />4 <br />300 <br />THW <br />1 <br />1 <br />Two <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />44B <br />600/3 <br />- <br />620 <br />4 <br />350 <br />THW <br />1 <br />1 <br />Two <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.00 <br />3.50 <br />45A <br />800/3 <br />- <br />760 <br />4 <br />500 <br />THW <br />1 <br />1/0 <br />Two <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />45B <br />800/3 <br />- <br />820 <br />4 <br />600 <br />THW <br />1 <br />1 /0 <br />Two <br />4.00 <br />4.00 <br />4.00 <br />4.00 <br />4.00 <br />4.00 <br />4.00 <br />46 1 <br />1000/3 <br />- <br />1005 <br />4 <br />400 <br />THW <br />1 <br />2/0 <br />Three <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />47 <br />1200/3 <br />- <br />1240 <br />4 <br />350 <br />THW <br />1 <br />3/0 <br />Four <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />3.50 <br />4.00 <br />48 <br />1600/3 <br />- <br />1675 <br />4 1400 <br />1 <br />THW <br />1 <br />4/0 <br />Five 1 <br />4.00 1 <br />4.00 14.00 <br />4.00 <br />4.00 <br />4.00 <br />4.00 <br />Notes: <br />Conductors are rated at 600 volt or below and are to be copper. <br />NEC Table 310.15(B)(16) - formerly Table 310.16 - is used for the basis of the conductor ampacities, <br />which is not more than three current carrying conductors in a raceway at an ambient temperature <br />of 30 deg C with 60 deg C rated conductors and connectors per 110.14-C-1 for up to 100 amp <br />rated and up to #1 AWG conductors for equipment terminations and 75 deg C rated conductors <br />and termination connectors for larger than 100 amp or above #1 AWG conductors. <br />NEC Tables 4, 5, and Appendix C is used for the basis of the conduit sizes. Table C1 for EMT, <br />Table C4 for IMC, Table C8 for Rigid, and Table C10 for PVC (Sch 40). <br />All Branch Feeders and Branch Circuits shall include a green Equipment Grounding Conductor. <br />Omit Grounding conductor on Service Entrance Feeders. <br />Omit Neutral conductor on all Delta primary transformer feeders or 3 phase loads not requiring a neutral. <br />The above conductors are not calculated for Voltage Drop. Any circuits that exceed 100 feet shall <br />be calculated by the Installer to have less than a three percent voltage drop on feeders and five <br />percent on branch circuits per the NEC. <br />Remote Panel POS <br />12 Ckt 120V 1-Phase 3-Wire w/ I.G. NOTE: THIS CABLE IS FACTORY WIRED TO THE POWER INTERFACE BOX <br />- - - - - - - - - - - - - - - - - - - I <br />1 POWERVAR UPM BATTERY BACKUP <br />I <br />I <br />I <br />I <br />I <br />---- --1, <br />0 I <br />0 0 I <br />ABCE1440 -11G <br />(UL 1449 LISTED) <br />I <br />UPM OUTPUT <br />I RECEPTACLE <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />- - - <br />-+------ <br />J -- 1 <br />ll� <br />TYPICAL ISOLATED o <br />GROUND <br />RECEPTACLE ° <br />0 0 <br />ISOLATED <br />GROUND 1 STANDARD <br />BAR I GROUND <br />CONTRACTOR TO INSTALL #10 AWG BAR <br />JUMPER BETWEEN FEEDER LUGS <br />a <br />H <br />0 <br />POWER INTERFACE BOX (PIB) <br />w <br />O_ <br />TB1 PIB <br />OUTPUT <br />a <br />TERMINALSPIB <br />w <br />NORMAL BYPASS <br />OUTLET <br />U <br />TB2IMPUT <br />O <br />Z <br />POWER <br />TERMINALS <br />INPUT OUTPUT <br />L2 N G <br />POWER POWER <br />I I <br />I I <br />NOTES <br />I l <br />III <br />1. DASHED LINES INDICATE FIELD WIRING. SOLID BOLD LINES INDICATE CABLE & PLUGS THAT CONNECT TO THE UPM & PIB OUTLETS. I I I <br />I i L-----TO GROUND BAR <br />2. WIRING FROM INPUT BREAKER A-10 TO PIB MUST BE RUN IN SEPARATE CONDUIT OR MC CABLE FROM OUTPUT WIRING. I L------To NEUTRAL BAR <br />3. BRANCH CIRCUIT WIRING MUST BE RUN IN DEDICATED CONDUITS OR MC CABLE NOT SHARED WITH OTHER EQUIPMENT. 20 AMP M RATED <br />BREAKER <br />4. ALL BRANCH CIRCUIT RECEPTACLES MUST BE ISOLATED GROUND (IG) TYPE AND ORANGE COLORED TO IDENTIFY CRITICAL CIRCUIT. <br />5. POWERVAR UPM BATTERY BACKUP IS MOUNTED ON TOP OF THE PIB AND CONNECTS WITH CABLE PLUGS AND OUTLETS. <br />POS AND LAPC/PIB WIRING DIAGRAM <br />NO SCALE <br />E o00� <br />0 D <br />O <br />A- <br />Chick-fil-A <br />5200 Buffington Road <br />Atlanta, Georgia <br />30349-2998 <br />Kurzynske <br />& Associates <br />2900 Lebanon Pike, Ste 201 <br />Nashville, Tennessee 37214 <br />Telephone: (615) 255-5203 <br />Fax: (615) 255-5207 <br />D Email: mail@kurzynske.com <br />,�,�tltlttttt#` <br />Na. 53568 ►,t� <br />�� • •mil rt <br />Q. STATE OF r`%+ <br />-� s •,�•O R IV <br />'S�ON At •� •`` • <br />This item has been electronically signed <br />and sealed by Mark T. Kurzynske, PE <br />on the date shown using a Digital <br />Signature. Printed copies of this <br />document are not considered signed <br />and sealed and the signature must be <br />verified on any electronic copies. <br />Mark <br />Kurzynske <br />Digitally signed by <br />C Mark T Kurzynske <br />Date: 2020.11.24 <br />15:0 • 1-06'00' <br />1 D <br />U) <br />M=J U= <br />r <br />Q M <br />-Lim > M <br />1 J J J LL <br />D <br />0 <br />m J_ <br />>M <br />J = <br />ow o= <br />UJ a, a <br />B W <br />N tiN <br />FSR#04040 <br />BUILDING TYPE / SIZE: P13 LC ALL <br />RELEASE: v2.20.02 <br />REVISION SCHEDULE <br />NO. DATE DESCRIPTION <br />1 11/25/2020 For Bid <br />CONS U LTANT PROJECT# 20090.CC.S <br />A <br />PRINTED FOR PERMIT <br />DATE 07/29/2020 <br />DRAWN BY ES <br />Information contained on this drawing and in all digital files <br />produced for above named project may not be reproduced in <br />any manner without express written or verbal consent from <br />authorized project representatives. <br />W <br />SHEET <br />SINGLE LINE DIAGRAM <br />a <br />AND NOTES <br />SHEET NUMBER <br />E=502 <br />4 <br />�3 <br />2 <br />1 <br />