4
<br />3
<br />F
<br />1
<br />E
<br />0
<br />C
<br />B
<br />A
<br />TO AC-1
<br />33; 150A
<br />TO AC-2
<br />27; 100A
<br />TO AC-3
<br />PANEL MDP
<br />1200A MCB
<br />F ............................. 250/3 25013
<br />PER NEC 230.71(A) THIS
<br />DEVICE SHALL NOT BE j
<br />CONSIDERED A SERVICE
<br />DISCONNECTING MEANS
<br />BECAUSE IT IS SOLELY 1
<br />USED FOR A SURGE
<br />SUPPRESSION DEVICE.
<br />i
<br />TVSS �
<br />I
<br />I
<br />SA
<br />FIELD CONNECT �-
<br />SURGE ARRESTOR
<br />TO MAIN LUGS
<br />FOUR 4" CONDUITS,
<br />EACH WITH 4#350 KCMIL
<br />250/3
<br />150/3
<br />100/3
<br />30/3
<br />250/3/ST
<br />250/3/ST
<br />110/3
<br />-0 o
<br />SPACE
<br />1#6 IN 3/4" CONDUIT TO
<br />PHONE SERVICE
<br />NEUTRALBAR
<br />#4/0 MAIN BONDING
<br />JUMPER
<br />THE GFCI BRANCH BREAKERS IN PANELS
<br />D1 AND D2 ARE 65K SERIES RATED WITH
<br />AN UPSTREAM BREAKER NO LARGER THAN
<br />250 AMP. THE 250 AMP PANELS D1 AND D2
<br />ARE 55" HIGH AND CANNOT BE STACKED.
<br />j PANEL D1 j j PANEL D2 j
<br />i 250A MLO i i 250A MLO i
<br />I I I
<br />I I
<br />I I
<br />I I I I
<br />I I I I
<br />I I
<br />1 40; 250A
<br />GROUND BAR (BONDED
<br />TO THE ENCLOSURE)
<br />GROUND PER NEC 250; 1#3/0
<br />MINIMUM IN 3/4"C TO MAIN WATER
<br />SERVICE PIPE WITH 1#4 FROM THE
<br />MAIN WATER SERVICE PIPE TO THE
<br />REFER TO THE ELECTRICAL PLAN
<br />GROUNDING COMPONENTS (I.E.
<br />AND/OR SITE PLAN FOR ROUTING TO
<br />GROUND ROD, CONCRETE
<br />THE POWER COMPANY'S
<br />ENCASED ELECTRODE) AND A #3/0
<br />TRANSFORMER AND THRU A METER
<br />BONDING JUMPER (PER 250.53.0
<br />IF IT IS ON THE BUILDING (WITH CT
<br />AND TABLE 250.66) TO THE STEEL
<br />CABINET) OR ON THE TRANSFORMER.
<br />STRUCTURE - IF APPLICABLE.
<br />SINGLE LINE DIAGRAM
<br />C2 NO SCALE
<br />SINGLE -LINE DIAGRAM NOTES
<br />1. VERIFY SERVICE LOCATIONS AND CONFORM TO THE REQUIREMENTS OF THE
<br />POWER COMPANY AND/OR DEVELOPER. POWER COMPANY AND/OR DEVELOPER
<br />SHALL BE CONTACTED PRIOR TO BEGINNING CONSTRUCTION TO ARRANGE AND
<br />VERIFY FOR THE INSTALLATION OF THE POWER COMPANY SERVICE, METER,
<br />AND OTHER ITEMS.
<br />2. GROUND ALL EQUIPMENT AND SERVICES IN ACCORDANCE WITH ARTICLE 250
<br />OF THE NATIONAL ELECTRICAL CODE, LOCAL APPLICABLE CODES, AND ALSO
<br />AS INDICATED ON DRAWINGS.
<br />3. MAKE NECESSARY INSPECTIONS OF EXISTING SITE AND SERVICE LOCATIONS AS
<br />REQUIRED FOR THIS WORK AND MAKE ALLOWANCE FOR EXISTING CONDITIONS
<br />BEFORE SUBMITTING BID. VERIFY WORK REQUIRED WITH POWER COMPANY AND
<br />TELEPHONE COMPANY.
<br />4. CUT AND PATCH THE CONSTRUCTION WORK AS REQUIRED FOR PROPER
<br />INSTALLATION OF THE ELECTRICAL WORK. ALL PATCHING SHALL MATCH THE
<br />SURROUNDING WORK TO THE SATISFACTION OF THE ARCHITECT. ALL CONDUIT
<br />SHALL BE INSTALLED CONCEALED UNLESS SPECIFICALLY APPROVED BY THE
<br />ARCHITECT. COORDINATE SAW CUTTING WITH LANDLORD'S OR OWNER'S
<br />REPRESENTATIVE.
<br />5. WIRE AND CABLE:
<br />A. CONDUCTORS SHALL BE COPPER, #12 AWG, MINIMUM UNLESS
<br />SPECIFICALLY NOTED OTHERWISE.
<br />B. CONDUCTOR #10 AWG AND SMALLER SHALL BE SOLID AND #8 AWG AND
<br />LARGER SHALL BE STRANDED. INSULATION SHALL BE 600 VOLT,
<br />THHN/THWN.
<br />6. PROVIDE ENGRAVED LAMINATED PHENOLIC BLOCK -ON -WHITE (UNLESS NOTED
<br />OTHERWISE) NAMEPLATES SECURED TO EQUIPMENT WITH ADHESIVE AND
<br />SCREWS FOR PANELBOARDS, RELAY CABINETS, TRANSFORMERS, DISTRIBUTION
<br />BOARDS, AND MAIN PANELBOARD - IDENTIFYING EQUIPMENT DESIGNATION
<br />(CORRESPONDING WITH DESIGNATION USED ON DRAWINGS) AND EQUIPMENT
<br />VOLTAGE. LETTERING SHALL BE 1/4" HIGH. PROVIDE LABELS FOR CIRCUIT
<br />BREAKERS, FUSIBLE SWITCHES AND STARTERS IN PANELBOARDS AND
<br />DISTRIBUTION BOARDS FOR EACH DEVICE IDENTIFYING EQUIPMENT
<br />CONTROLLED. LETTERING SHALL BE 1/8" HIGH.
<br />7. ALL DEVICES SHALL HAVE AN INTERRUPTING CAPACITY NOT LESS THAN THE
<br />POWER COMPANY AVAILABLE FAULT CURRENT, OR AS INDICATED ON THE
<br />DRAWINGS.
<br />8. 120/208 VOLT BRANCH CIRCUIT PANELBOARD BREAKERS SHALL HAVE A MINIMUM
<br />U.L. SERIES RATING OF 65 KAIC WITH UP -STREAM FEEDER BREAKERS AS NOTED.
<br />9. AVAILABLE SPACE FOR MAIN PANELBOARD IS LIMITED. PANELBOARD MUST FIN IN
<br />ALLOCATED SPACE. COORDINATE WITH CONSTRUCTION AS REQUIRED.
<br />10. ALL WIRING SHALL BE IN CONDUIT, E.M.T OR RIGID. FLEXIBLE CONDUIT MAY
<br />ONLY BE USED FOR FINAL CONNECTIONS AND WITH GREEN EQUIPMENT
<br />GROUNDING CONDUCTORS.
<br />-------------
<br />j PANEL C j
<br />i 250A MLO i
<br />I I
<br />I I
<br />I I
<br />1L-----J--------
<br />40; 250A 1
<br />BRANCH FEEDER MARK NUMBER
<br />WITH AMPERAGE, REFER TO THE
<br />CONDUIT AND CONDUCTORS
<br />SCHEDULE (THIS SHEET) FOR
<br />REQUIREMENTS (TYP)
<br />-------------
<br />j PANEL B j
<br />i 250A MLO i
<br />I
<br />I
<br />I
<br />I I
<br />1 I
<br />I I
<br />1 40; 250A
<br />-------------
<br />j PANEL A j
<br />250A MLO
<br />40; 250A
<br />PANEL POS
<br />100A MLO
<br />PROVIDE A JUMPER ON THE
<br />j LUGS OF PANEL-POS SO
<br />THAT BOTH PHASE BARS
<br />ARE TIED TO THE ONE 120V
<br />PHASE CONDUCTOR FROM
<br />--1--� THE PIB
<br />4; 20A 4+IG; 20A
<br />J
<br />in
<br />POWER INTERFACE BOX (PIB). PROVIDE INCOMING J-BOX
<br />AND OUTGOING J-BOX FLUSH IN THE WALL WITH FLEX
<br />CONDUIT CONNECTIONS TO THE PIB. THE CONDUCTORS
<br />ARE TO CONNECT TO THE TERMINAL BLOCKS OF THE PIB.
<br />SWITCHGEAR AND CONTROL EQUIPMENT NOTES
<br />1. PURCHASE PANELBOARDS, SURGE ARRESTOR, AND TVSS FROM ONE OF THE TWO
<br />NATIONAL ACCOUNTS VENDORS (SEE SHEET E-902 SECTION C16440, PANELBOARDS)
<br />PROVIDING SQUARE-D EQUIPMENT. NO SUBSTITUTIONS ALLOWED.
<br />2. PURCHASE CONTROL PANEL'CFA-T500' FROM SUNCOAST ENVIRONMENTAL, INC. (NO
<br />SUBSTITUTIONS ALLOWED). ALL EQUIPMENT IN THE CONTROL PANEL SHALL BE INSTALLED,
<br />WIRED AND CONNECTED AT THE FACTORY, INCLUDING AUTOMATIC LIGHTING CONTROL
<br />SYSTEM, LIGHTING RELAYS, HVAC STARTERS, POWER SUPPLIES, MISCELLANEOUS RELAYS
<br />AND CONTROLS, AND THERMOSTATS.
<br />3. CONTRACTOR SHALL PROVIDE PANEL FEEDERS A, B, C, D, AND POS, BRANCH
<br />CIRCUIT CONDUIT AND WIRE, AND INSTALL ALL EQUIPMENT AS REQUIRED.
<br />4. ALL BREAKERS AND PANELS SHALL BE SQUARE-D.
<br />5. TVSS AND SURGE ARRESTOR UNITS SHALL BE MOUNTED DIRECTLY ADJACENT TO THE
<br />SIDE OF THE MAIN DISTRIBUTION PANEL IN NEMA 3R ENCLOSURES. CLOSE NIPPLE THE
<br />UNITS TO THE SIDE OF THE PANEL. PROVIDE CONNECTION OF TVSS UNIT TO BREAKER
<br />IN PANEL. CONNECT SURGE ARRESTOR TO MAIN INCOMING LUGS OF THE PANE.
<br />CONNECT USING MINIMUM LENGTH OF WIRE WITHOUT SHARP BENDS IN THE WIRE AND
<br />SHALL NOT BE LENGTHENED FROM WIRE LENGTH PROVIDED WITH THE TVSS OR
<br />SURGE SUPPRESSOR DEVICE.
<br />J
<br />131 CONDUIT AND CONDUCTORS SCHEDULE
<br />Mark
<br />No.
<br />OCP
<br />Device
<br />(Amp/Poles)
<br />Conductors
<br />Total Am s
<br />Conductors
<br />Raceway Size Nominal
<br />Inches
<br />Phase &Neutral
<br />Min Eq Grd
<br />No.
<br />Phase, Neutral & Equip Grd
<br />With IG
<br />60d C
<br />75d C
<br />Qty
<br />Size
<br />Type
<br />Q /Set
<br />Size
<br />Sets
<br />EMT
<br />IMC
<br />RIGID
<br />PVC
<br />EMT
<br />IMC
<br />PVC
<br />1
<br />20/1
<br />20
<br />-
<br />2
<br />12
<br />THHN
<br />1
<br />12
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />2
<br />20/2
<br />20
<br />-
<br />3
<br />12
<br />THHN
<br />1
<br />12
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />3
<br />20/3
<br />20
<br />-
<br />4
<br />12
<br />ITHHN
<br />1
<br />12
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />4
<br />25/1
<br />30
<br />-
<br />2
<br />10
<br />THHN
<br />1
<br />10
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />5
<br />25/2
<br />30
<br />-
<br />3
<br />10
<br />THHN
<br />1
<br />10
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />6
<br />25/3
<br />30
<br />-
<br />4
<br />10
<br />THHN
<br />1
<br />10
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />7
<br />30/1
<br />30
<br />-
<br />2
<br />10
<br />THHN
<br />1
<br />10
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />8
<br />30/2
<br />30
<br />-
<br />3
<br />10
<br />THHN
<br />1
<br />10
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />9
<br />30/3
<br />30
<br />-
<br />4
<br />10
<br />THHN
<br />1
<br />10
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />10
<br />40/1
<br />40
<br />-
<br />2
<br />8
<br />THHN
<br />1
<br />10
<br />One
<br />10.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />11
<br />40/2
<br />40
<br />-
<br />3
<br />8
<br />THHN
<br />1
<br />10
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />12
<br />40/3
<br />40
<br />-
<br />4
<br />8
<br />THHN1
<br />1
<br />10
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />1.00
<br />13
<br />50/1
<br />55
<br />-
<br />2
<br />6
<br />THHN
<br />1
<br />10
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />14
<br />50/2
<br />55
<br />-
<br />3
<br />6
<br />THHN
<br />1
<br />10
<br />One
<br />0.75
<br />0.75
<br />0.75
<br />0.75
<br />1.00
<br />1.00
<br />1.00
<br />15
<br />50/3
<br />55
<br />-
<br />4
<br />6
<br />THHN
<br />1
<br />10
<br />One
<br />1.00
<br />1.00
<br />1.00
<br />1.00
<br />1.00
<br />1.00
<br />1.00
<br />16
<br />60/1
<br />70
<br />-
<br />2
<br />4
<br />THW
<br />1
<br />8
<br />One
<br />1.00
<br />1.00
<br />1.00
<br />1.00
<br />1.25
<br />1.00
<br />1.25
<br />17
<br />60/2
<br />70
<br />-
<br />3
<br />4
<br />THW
<br />1
<br />8
<br />One
<br />1.25
<br />1.00
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />18
<br />60/3
<br />70
<br />-
<br />4
<br />4
<br />THW
<br />1
<br />8
<br />One
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />19
<br />70/1
<br />70
<br />-
<br />2
<br />4
<br />THW
<br />1
<br />8
<br />One
<br />1.00
<br />1.00
<br />1.00
<br />1.00
<br />1.25
<br />1.00
<br />1.25
<br />20
<br />70/2
<br />70
<br />-
<br />3
<br />4
<br />THW
<br />1
<br />8
<br />One
<br />1.25
<br />1.00
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />21
<br />70/3
<br />70
<br />-
<br />1 4
<br />4
<br />ITHW
<br />1
<br />8
<br />1 One
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />22
<br />80/2
<br />85
<br />-
<br />3
<br />3
<br />THW
<br />1
<br />8
<br />One
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />23
<br />80/3
<br />85
<br />-
<br />4
<br />3
<br />THW
<br />1
<br />8
<br />One
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.50
<br />1.25
<br />1.50
<br />24
<br />90/2
<br />95
<br />-
<br />3
<br />2
<br />THW
<br />1
<br />8
<br />One
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.50
<br />1.25
<br />1.50
<br />25
<br />90/3
<br />95
<br />-
<br />4
<br />2
<br />THW
<br />1
<br />8
<br />One
<br />1.50
<br />1.25
<br />1.50
<br />1.50
<br />1.50
<br />1.50
<br />1.50
<br />26
<br />100/2
<br />110
<br />-
<br />3
<br />1
<br />THW
<br />1
<br />6
<br />One
<br />1.50
<br />1.50
<br />1.50
<br />1.50
<br />2.00
<br />2.00
<br />2.00
<br />27
<br />100/3
<br />110
<br />-
<br />4
<br />1
<br />THW
<br />1
<br />6
<br />One
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />28
<br />110/2
<br />-
<br />115
<br />3
<br />2
<br />THW
<br />1
<br />6
<br />One
<br />1.25
<br />1.25
<br />1.25
<br />1.25
<br />1.50
<br />1.25
<br />1.50
<br />29
<br />110/3
<br />-
<br />115
<br />4
<br />2
<br />THW
<br />1
<br />6
<br />One
<br />1.50
<br />1.25
<br />1.50
<br />1.50
<br />1.50
<br />1.50
<br />1.50
<br />30
<br />125/2
<br />-
<br />130
<br />3
<br />1
<br />THW
<br />1
<br />6
<br />One
<br />1.50
<br />1.50
<br />1.50
<br />1.50
<br />2.00
<br />2.00
<br />2.00
<br />31
<br />125/3
<br />-
<br />130
<br />4
<br />1
<br />THW
<br />1
<br />6
<br />One
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />32
<br />150/2
<br />-
<br />150
<br />3
<br />1 /0
<br />THW
<br />1
<br />6
<br />One
<br />2.00
<br />1.50
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />33
<br />150/3
<br />-
<br />150 1
<br />4
<br />1 /0 ITHW
<br />1
<br />6 1
<br />One
<br />2.00 12.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />34
<br />175/2
<br />-
<br />175
<br />3
<br />2/0
<br />THW
<br />1
<br />6
<br />One
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />35
<br />175/3
<br />-
<br />175
<br />4
<br />2/0
<br />THW
<br />1
<br />6
<br />One
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.50
<br />2.50
<br />2.50
<br />36
<br />200/2
<br />-
<br />200
<br />3
<br />3/0
<br />THW
<br />1
<br />6
<br />One
<br />2.00
<br />2.00
<br />2.00
<br />2.00
<br />2.50
<br />2.50
<br />2.50
<br />37
<br />200/3
<br />-
<br />200
<br />4
<br />3/0
<br />THW
<br />1
<br />6
<br />One
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />38
<br />225/2
<br />-
<br />230
<br />3
<br />4/0
<br />THW
<br />1
<br />4
<br />One
<br />2.50
<br />2.00
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />39
<br />225/3
<br />-
<br />230
<br />4
<br />4/0
<br />THW
<br />1
<br />4
<br />One
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />3.00
<br />3.00
<br />40
<br />250/3
<br />-
<br />255
<br />4
<br />250
<br />THW
<br />1
<br />4
<br />One
<br />2.50
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />41 A
<br />300/3
<br />-
<br />285
<br />4
<br />300
<br />THW
<br />1
<br />4
<br />One
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />41 B
<br />300/3
<br />-
<br />310
<br />4
<br />350
<br />THW
<br />1
<br />4
<br />One
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3..00
<br />3.00
<br />42A
<br />350/3
<br />-
<br />335
<br />4
<br />400
<br />THW
<br />1
<br />4
<br />One
<br />3.00
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />42B
<br />350/3
<br />-
<br />380
<br />4
<br />500
<br />THW
<br />1
<br />4
<br />One
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />43A
<br />400/3
<br />-
<br />380
<br />4
<br />500
<br />THW
<br />1
<br />3
<br />One
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />43B
<br />400/3
<br />-
<br />400
<br />4
<br />3/0
<br />THW
<br />1
<br />3
<br />Two
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />2.50
<br />44A
<br />600/3
<br />-
<br />570
<br />4
<br />300
<br />THW
<br />1
<br />1
<br />Two
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />44B
<br />600/3
<br />-
<br />620
<br />4
<br />350
<br />THW
<br />1
<br />1
<br />Two
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.00
<br />3.50
<br />45A
<br />800/3
<br />-
<br />760
<br />4
<br />500
<br />THW
<br />1
<br />1/0
<br />Two
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />45B
<br />800/3
<br />-
<br />820
<br />4
<br />600
<br />THW
<br />1
<br />1 /0
<br />Two
<br />4.00
<br />4.00
<br />4.00
<br />4.00
<br />4.00
<br />4.00
<br />4.00
<br />46 1
<br />1000/3
<br />-
<br />1005
<br />4
<br />400
<br />THW
<br />1
<br />2/0
<br />Three
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />47
<br />1200/3
<br />-
<br />1240
<br />4
<br />350
<br />THW
<br />1
<br />3/0
<br />Four
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />3.50
<br />4.00
<br />48
<br />1600/3
<br />-
<br />1675
<br />4 1400
<br />1
<br />THW
<br />1
<br />4/0
<br />Five 1
<br />4.00 1
<br />4.00 14.00
<br />4.00
<br />4.00
<br />4.00
<br />4.00
<br />Notes:
<br />Conductors are rated at 600 volt or below and are to be copper.
<br />NEC Table 310.15(B)(16) - formerly Table 310.16 - is used for the basis of the conductor ampacities,
<br />which is not more than three current carrying conductors in a raceway at an ambient temperature
<br />of 30 deg C with 60 deg C rated conductors and connectors per 110.14-C-1 for up to 100 amp
<br />rated and up to #1 AWG conductors for equipment terminations and 75 deg C rated conductors
<br />and termination connectors for larger than 100 amp or above #1 AWG conductors.
<br />NEC Tables 4, 5, and Appendix C is used for the basis of the conduit sizes. Table C1 for EMT,
<br />Table C4 for IMC, Table C8 for Rigid, and Table C10 for PVC (Sch 40).
<br />All Branch Feeders and Branch Circuits shall include a green Equipment Grounding Conductor.
<br />Omit Grounding conductor on Service Entrance Feeders.
<br />Omit Neutral conductor on all Delta primary transformer feeders or 3 phase loads not requiring a neutral.
<br />The above conductors are not calculated for Voltage Drop. Any circuits that exceed 100 feet shall
<br />be calculated by the Installer to have less than a three percent voltage drop on feeders and five
<br />percent on branch circuits per the NEC.
<br />Remote Panel POS
<br />12 Ckt 120V 1-Phase 3-Wire w/ I.G. NOTE: THIS CABLE IS FACTORY WIRED TO THE POWER INTERFACE BOX
<br />- - - - - - - - - - - - - - - - - - - I
<br />1 POWERVAR UPM BATTERY BACKUP
<br />I
<br />I
<br />I
<br />I
<br />I
<br />---- --1,
<br />0 I
<br />0 0 I
<br />ABCE1440 -11G
<br />(UL 1449 LISTED)
<br />I
<br />UPM OUTPUT
<br />I RECEPTACLE
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />I
<br />- - -
<br />-+------
<br />J -- 1
<br />ll�
<br />TYPICAL ISOLATED o
<br />GROUND
<br />RECEPTACLE °
<br />0 0
<br />ISOLATED
<br />GROUND 1 STANDARD
<br />BAR I GROUND
<br />CONTRACTOR TO INSTALL #10 AWG BAR
<br />JUMPER BETWEEN FEEDER LUGS
<br />a
<br />H
<br />0
<br />POWER INTERFACE BOX (PIB)
<br />w
<br />O_
<br />TB1 PIB
<br />OUTPUT
<br />a
<br />TERMINALSPIB
<br />w
<br />NORMAL BYPASS
<br />OUTLET
<br />U
<br />TB2IMPUT
<br />O
<br />Z
<br />POWER
<br />TERMINALS
<br />INPUT OUTPUT
<br />L2 N G
<br />POWER POWER
<br />I I
<br />I I
<br />NOTES
<br />I l
<br />III
<br />1. DASHED LINES INDICATE FIELD WIRING. SOLID BOLD LINES INDICATE CABLE & PLUGS THAT CONNECT TO THE UPM & PIB OUTLETS. I I I
<br />I i L-----TO GROUND BAR
<br />2. WIRING FROM INPUT BREAKER A-10 TO PIB MUST BE RUN IN SEPARATE CONDUIT OR MC CABLE FROM OUTPUT WIRING. I L------To NEUTRAL BAR
<br />3. BRANCH CIRCUIT WIRING MUST BE RUN IN DEDICATED CONDUITS OR MC CABLE NOT SHARED WITH OTHER EQUIPMENT. 20 AMP M RATED
<br />BREAKER
<br />4. ALL BRANCH CIRCUIT RECEPTACLES MUST BE ISOLATED GROUND (IG) TYPE AND ORANGE COLORED TO IDENTIFY CRITICAL CIRCUIT.
<br />5. POWERVAR UPM BATTERY BACKUP IS MOUNTED ON TOP OF THE PIB AND CONNECTS WITH CABLE PLUGS AND OUTLETS.
<br />POS AND LAPC/PIB WIRING DIAGRAM
<br />NO SCALE
<br />E o00�
<br />0 D
<br />O
<br />A-
<br />Chick-fil-A
<br />5200 Buffington Road
<br />Atlanta, Georgia
<br />30349-2998
<br />Kurzynske
<br />& Associates
<br />2900 Lebanon Pike, Ste 201
<br />Nashville, Tennessee 37214
<br />Telephone: (615) 255-5203
<br />Fax: (615) 255-5207
<br />D Email: mail@kurzynske.com
<br />,�,�tltlttttt#`
<br />Na. 53568 ►,t�
<br />�� • •mil rt
<br />Q. STATE OF r`%+
<br />-� s •,�•O R IV
<br />'S�ON At •� •`` •
<br />This item has been electronically signed
<br />and sealed by Mark T. Kurzynske, PE
<br />on the date shown using a Digital
<br />Signature. Printed copies of this
<br />document are not considered signed
<br />and sealed and the signature must be
<br />verified on any electronic copies.
<br />Mark
<br />Kurzynske
<br />Digitally signed by
<br />C Mark T Kurzynske
<br />Date: 2020.11.24
<br />15:0 • 1-06'00'
<br />1 D
<br />U)
<br />M=J U=
<br />r
<br />Q M
<br />-Lim > M
<br />1 J J J LL
<br />D
<br />0
<br />m J_
<br />>M
<br />J =
<br />ow o=
<br />UJ a, a
<br />B W
<br />N tiN
<br />FSR#04040
<br />BUILDING TYPE / SIZE: P13 LC ALL
<br />RELEASE: v2.20.02
<br />REVISION SCHEDULE
<br />NO. DATE DESCRIPTION
<br />1 11/25/2020 For Bid
<br />CONS U LTANT PROJECT# 20090.CC.S
<br />A
<br />PRINTED FOR PERMIT
<br />DATE 07/29/2020
<br />DRAWN BY ES
<br />Information contained on this drawing and in all digital files
<br />produced for above named project may not be reproduced in
<br />any manner without express written or verbal consent from
<br />authorized project representatives.
<br />W
<br />SHEET
<br />SINGLE LINE DIAGRAM
<br />a
<br />AND NOTES
<br />SHEET NUMBER
<br />E=502
<br />4
<br />�3
<br />2