Laserfiche WebLink
4 <br />K <br />`A <br />1 <br />E <br />n <br />C <br />B <br />1. SECTION C15000 - MECHANICAL SPECIFICATIONS <br />PART I - GENERAL <br />1.01 SCOPE <br />A. IT IS THE RESPONSIBILITY OF CONTRACTOR TO READ ALL SPECIFICATIONS AND <br />CONSULT ALL DRAWINGS WHICH MAY AFFECT THE INSTALLATION AND <br />COORDINATION OF HIS WORK WITH OTHER TRADES. CONTRACTOR SHALL <br />COORDINATE AND MAKE MINOR ADJUSTMENTS IN LOCATION OF EQUIPMENT <br />AND MATERIALS AS NECESSARY TO SECURE COORDINATION. <br />B. COMPLETED INSTALLATION SHALL CONFORM TO ALL APPLICABLE FEDERAL, <br />STATE AND LOCAL CODES AND ORDINANCES, INCLUDING BUT NOT LIMITED TO <br />THE LATEST APPROVED EDITIONS OF NFPA-96, NFPA-90A, NFPA-54, SMACNA, <br />ASHRAE 90.1 AND ASHRAE 62. <br />C. SYSTEM LAYOUT IS SCHEMATIC AND EXACT LOCATIONS SHALL BE <br />DETERMINED BY STRUCTURAL CONDITIONS, COORDINATION WITH OTHER <br />TRADES, COORDINATION WITH FINISHES AND OTHER CONDITIONS. <br />STRUCTURAL SUPPORTS SHALL NOT BE CUT OR ALTERED TO ASSURE FIT OF <br />HVAC SYSTEM. TEN FOOT CLEARANCE SHALL BE MAINTAINED BETWEEN <br />OUTSIDE AIR INTAKES AND EXHAUST FANS AND PLUMBING VENT TERMINALS. <br />D. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEFECTS, REPAIRS AND <br />REPLACEMENTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE (1) <br />YEAR AFTER FINAL PAYMENT IS APPROVED. CONTRACTOR SHALL HONOR <br />FACTORY WARRANTIES ON ALL EQUIPMENT PROVIDED AS PART OF THIS SYSTEM. <br />E. UPON COMPLETION OF PROJECT, ALL SYSTEM EQUIPMENT AND MATERIALS <br />SHALL BE IN NEW, CLEAN CONDITION WITH ALL DAMAGE RESTORED TO <br />CONDITION ACCEPTABLE TO THE OWNERS REPRESENTATIVE. ALL EQUIPMENT, <br />COMPONENTS, DUCTWORK, AND AIR DEVICES SHALL BE INSPECTED AND <br />THOROUGHLY CLEANED, CLEARED OF DEBRI, AND READY FOR USE. AT <br />COMPLETION OF JOB, ALL MISCELLANEOUS TOOLS, SCAFFOLDING, SURPLUS <br />MATERIALS, RUBBISH AND DEBRIS SHALL BE REMOVED BY CONTRACTOR. <br />F. CONTRACTOR SHALL PROVIDE TWO SETS OF 2" MERV 8 OR HIGHER THROW <br />AWAY TYPE FILTERS. A CLEAN SET SHALL BE PROVIDED PRIOR TO TEST AND <br />BALANCE AND AGAIN PRIOR TO OPENING. <br />PART II - PRODUCTS <br />2.01 HEATING AND COOLING EQUIPMENT (C15730) <br />A. FURNISH AND INSTALL R-410A ROOFTOP SINGLE PACKAGE COMBINATION <br />ELECTRIC COOLING AND NATURAL GAS FIRED HEATING UNITS BY LENNOX AS <br />SHOWN ON DRAWINGS. EQUIPMENT SHALL BE ARI CERTIFIED AND A.G.A. AND U.L. <br />LISTED. <br />B. ACCESSORIES SHALL INCLUDE LOW AND HIGH PRESSURE SAFETIES, CRANK <br />CASE HEATER, OVERCURRENT AND OVERTEMPERATURE SAFETY, <br />COMPRESSOR VIBRATION ISOLATORS, FILTER DRIERS, REFRIGERANT SERVICE <br />VALVES, COIL HAIL GUARDS WHERE SCHEDULED, CONVENIENCE OUTLETS <br />FACTORY INSTALLED ON SCHEDULED UNITS, UNIT MOUNTED NON -FUSED <br />DISCONNECTS, LOW AMBIENT OPERATION DOWN TO 30 DEGREES F AND <br />EVAPORATOR FREEZE STAT. <br />C. COMPRESSORS SHALL BE FULLY HERMETIC SCROLL TYPE WITH INTERNAL <br />VIBRATION ISOLATORS. COMPRESSORS SHALL BE PROVIDED WITH A MINIMUM <br />FIVE (5) YEAR FULL WARRANTY. <br />D. THE UNIT HEAT EXCHANGERS SHALL BE STEEL WITH ALUMINIZED STEEL <br />COATING. HEATING CONTROLS SHALL CONSIST OF REDUNDANT GAS VALVES, <br />INTERMITTENT PILOT WITH ELECTRONIC SPARK OR HOT PLATE IGNITION SYSTEM, <br />COMBUSTION/EXHAUST FAN PROTECTED BY CENTRIFUGAL SWITCHES, HEAT <br />LIMIT SWITCHES, TIME -DELAY RELAY, FLAME, AND PILOT SENSORS. ALL UNITS <br />SHALL BE CAPABLE OF TWO STAGES OF HEAT. HEAT EXCHANGES SHALL HAVE A <br />TEN (10) YEAR WARRANTY. BURNERS SHALL BE ALUMINIZED IN -SHOT TYPE. THE <br />DRAFT MOTOR SHALL BE MONITORED BY THE CONTROL SYSTEM. <br />E. CHICK-FIL-A MAINTAINS A NATIONAL ACCOUNT FOR EQUIPMENT WITH LENNOX <br />CORPORATION. PRICING FOR THE EQUIPMENT HAS BEEN ESTABLISHED IN <br />ADVANCE. CONTACT LENNOX NATIONAL ACCOUNTS AT 972-497-6260 (OR BY <br />FAX AT 972-497-5112) FOR PRICING, ORDERING AND AVAILABILITY. <br />2.02 DUCTWORK (C15735) (SEE DWG M-301 FOR ADDITIONAL GREASE DUCT SYSTEM REQ.) <br />A. ACCEPTABLE MANUFACTURERS OF INSULATION ARE MANVILLE, OWENS <br />CORNING OR KNAUF. <br />B. ALL DUCTWORK SHALL BE SHEET METAL, UNLESS NOTED OTHERWISE (U.N.O.). <br />C. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSIONS, U.N.O. <br />D. CONSTRUCTION OF DUCTWORK SHALL MEET SMACNA 1" W.C. PRESSURE CLASS <br />STANDARD AND RECOMMENDATIONS. SMACNA SHALL BE FOLLOWED WITH <br />RESPECT TO GAGE THICKNESS, JOINTS, REINFORCING, CONSTRUCTION, <br />INSTALLATION AND SUPPORT FOR PRESSURE CLASS STATED. ALL TRANSVERSE <br />JOINTS IN RECTANGULAR AND ROUND DUCT INCLUDING DUCT CONNECTION TO <br />AIR DEVICE COLLAR SHALL BE SEALED PER SMACNA SEAL CLASS C WITH U.L. <br />DUCT MASTIC SEALANT APPROVED FOR INTENDED USE. DUCT TAPE IS NOT AN <br />ACCEPTABLE SUBSTITUTE FOR MASTIC UNLESS EQUAL TO HARDCAST FOIL -GRIP <br />1402 BUTYL RUBBER ADHESIVE TAPE. <br />E. DUCT SHALL BE SUPPORTED AT BASE OF DUCT DROPS. CURB DUCT RAILS ARE <br />NOT INTENDED TO AND SHALL NOT SUPPORT THE WEIGHT OF THE DUCT. <br />F. ALL DUCT INSULATION SHALL MEET MINIMUM R-VALUE REQUIRED BY ASHRAE 90.1 <br />LATEST EDITION. ALL DUCT WRAP SHALL BE MINIMUM 2" THICK, 3/4 PCF AND 6 R- <br />VALUE INSTALLED WITH EITHER A VAPOR BARRIER WITH MAXIMUM PERMEANCE <br />0.05 OR A MINIMUM 2 MIL ALUMINUM REINFORCED FOIUKRAFT FACING. <br />G. ALL DUCT DROPS FROM THE ROOFTOP UNITS SHALL BE EXTERNALLY INSULATED. <br />H. SUPPLY AND RETURN AIR DUCTWORK SERVING ALL AREAS SHALL BE <br />EXTERNALLY INSULATED. <br />I. ALL AIR CONVEYANCE COMPONENTS SUCH AS, BUT NOT LIMITED TO DUCT, DUCT <br />PLENUMS, GRILLES/DIFFUSERS, BACK PANS, AND BOOTS SHALL BE INSULATED. <br />INSULATION TYPE IS COVERED ELSEWHERE IN THIS SPECIFICATION. <br />J. RESTROOM RECTANGULAR EXHAUST AIR DUCTWORK SHALL BE LINED WITH <br />1" THICK, 1-1/2 PCF INSULATION. RESTROOM ROUND EXHAUST DUCT SHALL <br />BE EXTERNALLY INSULATED PER SECTION 2.02F. <br />K. TRUNK DUCTS SHALL BE ISOLATED FROM UNIT VIBRATION WITH THE USE OF <br />NFPA AND U.L. APPROVED FLEXIBLE CONNECTORS INSTALLED AT THE TOP OF <br />BOTH SUPPLY AND RETURN DROPS. <br />L. INSULATED FLEXIBLE DUCT MAY BE UTILIZED FOR RUNOUTS TO GRILLES AND <br />DIFFUSERS ONLY IN THE HORIZONTAL POSITION AND IN MAXIMUM LENGTHS OF <br />4'-0", NO EXCEPTIONS. SEE TAKE -OFF DETAIL ON DRAWING M-401. <br />M. CONSTRUCTION OF FLEXIBLE DUCTWORK SHALL INCLUDE SPIRAL METAL HELIX <br />BONDED TO A POLYESTER CORE, FIBERGLASS INSULATION WITH POLYETHYLENE <br />OR MYLAR VAPOR BARRIER. ALL COMPONENTS SHALL HAVE APPROPRIATE U.L. <br />APPROVAL AND SHALL BE EQUIVALENT TO THERMAFLEX MKE. <br />N. FLEXIBLE DUCT SHALL BE INSTALLED PER THE "ADC FLEXIBLE DUCT PERFORMANCE <br />AND INSTALLATION STANDARDS, 4TH ED" USING FOIL TAPE AND DRAWBAND ON THE <br />INNER CORE AND TAPE OR DRAWBAND ON THE OUTER JACKET. <br />O. DUCT TAPE SHALL BE EQUAL TO FASSON 181-B FX, 2-1/2" WIDE. <br />P. SINGLE THICKNESS TURNING VANES SHALL BE INSTALLED AT 90 DEGREE TURNS <br />IN SUPPLY DUCTWORK WHERE ANY ONE DIMENSION IS GREATER THAN 12". <br />Q. RADIUSED ELBOWS MAY BE SUBSTITUTED FOR 90 DEGREE ELBOWS AT THE <br />DISCRETION OF THE CONTRACTOR. CENTERLINE RADIUS EQUAL TO; R=W PER <br />FIGURE NO. 4-2 IN SMACNA HVAC DUCT CONSTRUCTION STANDARDS. <br />R. EXTERNAL INSULATION ON BOTTOM OF DUCTS 24" OR WIDER SHALL BE <br />SUPPORTED WITH STICK PINS ON 18" CENTERS. STICK PIN WASHERS SHALL BE <br />COVERED WITH DUCT TAPE OR MASTIC. <br />2.03 CONTROLS (C15735) <br />A. SYSTEMS SHALL BE COMPLETE WITH CONNECTIONS TO CFA-500 TEMPERATURE <br />CONTROL PANEL AS MANUFACTURED BY SUNCOAST ENVIRONMENTAL <br />CONTROLS (S.E.C.) (PH: 877-544-6679). THE PANEL IS PROVIDED AND MOUNTED <br />BY THE ELECTRICAL CONTRACTOR. CONTROL WIRING TERMINATIONS ARE BY <br />THE MECHANICAL CONTRACTOR. <br />B. THE SMOKE DETECTORS SHALL BE FACTORY INSTALLED AND WIRED BY <br />THE ROOFTOP UNIT MANUFACTURER. <br />C. A FACTORY INSTALLED SMOKE DETECTOR IN THE RETURN AIR SECTION OF <br />EACH AIR CONDITIONING UNIT SHALL STOP THE INDOOR FAN AND CLOSE THE <br />OUTSIDE AIR DAMPER IN THE EVENT OF EXCESSIVE TEMPERATURE OR SMOKE. <br />SMOKE DETECTOR SHALL BE LOCATED PRIOR TO ANY EXHAUST FROM THE <br />BUILDING OR MIXING WITH FRESH AIR MAKE-UP. UPON DETECTION, THE <br />SYSTEM SHALL NOT RESTART UNTIL THE DEVICE IS MANUALLY RESET. DEVICES <br />SHALL BE LOCATED WHERE THEY CAN BE EASILY ACCESSED AND WHERE <br />CLEAR OF FILTERS. <br />D. CHICK-FIL-A HAS A NATIONAL ACCOUNT WITH SUNCOAST ENVIRONMENTAL <br />CONTROLS FOR THE SMOKE DETECTOR TEST/RESET ANNUNCIATOR STATIONS. <br />THE TEST/RESET STATIONS WILL BE PURCHASED BY THE ELECTRICAL <br />CONTRACTOR AS A PART OF A NATIONAL ACCOUNT PACKAGE AND TURNED OVER <br />TO THE MECHANICAL CONTRACTOR FOR INSTALLATION. <br />E. THE REMOTE TEST/RESET ANNUNCIATORS SHALL BE PROVIDED BY THE ELECTRICAL <br />CONTRACTOR AND INSTALLED BY THE MECHANICAL CONTRACTOR. INSTALLATION <br />BY MECHANICAL SHALL INCLUDE MOUNTING OF THE ANNUNCIATORS AND ALL <br />WIRING FROM EACH DEVICE TO THE RTU. ELECTRICAL WILL PROVIDE A JUNCTION <br />BOX IN THE WALL WITH 1/2" CONDUIT STUBBED UP ABOVE THE CEILING FOR EACH <br />REMOTE TEST STATION AS SHOWN ON THE ELECTRICAL PLANS. ANNUCIATOR SHALL <br />BE SUNCOAST CONTROLS REMOTE TEST/RESET STATION WITH POWER LED, <br />TROUBLE LED, ALARM LED, 90DB HORN AND TEST/RESET BUTTON. <br />F. THE RESTROOM FAN SHALL BE INTERLOCKED TO THE LIGHTS SERVING THE MEN <br />AND WOMEN'S RESTROOMS. THE HOOD FANS SHALL BE CONTROLLED VIA THE <br />SUNCOAST CFA-500 CONTROL PANEL. WIRING, RELAYS AND SWITCHES FOR <br />CONTROL OF ALL FANS ARE BY ELECTRICAL CONTRACTOR. <br />G. LENNOX UNITS - THERMOSTATS ARE PROVIDED AND INTEGRATED INTO THE <br />TEMPERATURE CONTROL PANEL BY SUNCOAST ENVIRONMENT CONTROLS. <br />SUNCOAST WILL PROVIDE A NETWORK THERMOSTAT US32-CFA THERMOSTAT PRE - <br />WIRED IN THE TEMPERATURE CONTROL PANEL. A REMOTE TEMPERATURE <br />SENSOR FOR EACH THERMOSTAT IS ALSO PROVIDED. MECHANICAL CONTRACTOR <br />SHALL INSTALL ALL WIRING BETWEEN THE THERMOSTAT, THE REMOTE SENSOR <br />AND THE ROOFTOP UNIT. <br />H. MECHANICAL CONTRACTOR SHALL INSTALL CONTROL WIRING IN 1/2" CONDUIT <br />WHERE REQUIRED BY CODE. WHERE NOT REQUIRED TO BE IN CONDUIT, ALL <br />WIRING SHALL BE RUN PARALLEL TO STRUCTURAL MEMBERS OR <br />PERPENDICULAR WITH NO DIAGONAL ROUTING. ALL WIRING SHALL BE <br />SECURED TO THE FRAMING TO PREVENT SAGGING IN RUNS. WIRING TO <br />ROOFTOP UNITS SHALL BE ROUTED THROUGH THE FACTORY THRU-BASE <br />FITTING IN THE UNIT BASE. NO SPLICING OF WIRING WILL BE ACCEPTED. ALL <br />WIRING ABOVE THE ROOF SHALL BE INSTALLED IN EXTERIOR GRADE FLEXIBLE <br />CONDUIT. ALL CONTROL WIRING AND CONTROL WIRING CONDUIT SHALL BE <br />FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR. WIRING SHALL <br />BE INSTALLED IN ACCORDANCE WITH LATEST EDITION OF NEC. ALL LOW <br />VOLTAGE CONTROL WIRING SHALL BE NO LESS THAN 18 AWG MIN. CONTROL <br />WIRING CONDUCTORS SHALL BE SIZED TO ACCOUNT FOR LOAD AND LENGTH <br />OF RUN TO ALLOW SUFFICIENT VOLTAGE AVAILABLE AT CONTROLLED DEVICE <br />TO OPERATE THE SYSTEM RELIABLY. <br />PART III - EXECUTION <br />3.01 SCOPE <br />A. FURNISH AND INSTALL SYSTEM IN ACCORDANCE WITH REFERENCED <br />STANDARDS, APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS <br />AND AS INDICATED ON DRAWINGS. <br />B. CONTRACTOR SHALL INSTRUCT THE OWNER'S REPRESENTATIVE IN ALL <br />MATTERS PERTAINING TO THE PROPER MAINTENANCE OF EQUIPMENT <br />FURNISHED UNDER THIS CONTRACT THROUGH DEMONSTRATION AND <br />EXPLANATION OF OPERATING & MAINTENANCE MANUALS. <br />C. CONTRACTOR SHALL PROVIDE A "SAMPLE MAINTENANCE PROPOSAL" TO THE <br />OWNER'S REPRESENTATIVE IN ALL MATTERS PERTAINING TO THE PROPER <br />MAINTENANCE OF EQUIPMENT FURNISHED UNDER THIS CONTRACT. <br />D. CONTRACTOR SHALL COMPLETE A/C EQUIPMENT STARTUP DOCUMENTATION <br />PROVIDED BY OWNER AND/OR MANUFACTURER. THIS SHALL INCLUDE RE - <br />TORQUE OF ALL FIELD AND FACTORY HIGH VOLTAGE CONNECTIONS. <br />3.02 LEED PROJECTS <br />A. CONTRACTOR SHALL COMPLETE RECEIPT INSPECTION CHECKLISTS PROVIDED IN <br />THE COMMISSIONING PLAN WITHIN 5 DAYS OF RECEIVING EQUIPMENT ON SITE. <br />B. CONTRACTOR SHALL COMPLETE PRE -FUNCTIONAL CHECKLISTS PROVIDED IN <br />THE COMMISSIONING PLAN. CHECKLISTS SHALL BE RETURNED AT LEAST 5 DAYS <br />PRIOR TO SCHEDULING FUNCTIONAL PERFORMANCE TESTING. <br />C. CONTRACTOR SHALL PROVIDE A TECHNICIAN TO ASSIST THE THIRD PARTY <br />COMMISSIONING AUTHORITY WITH FUNCTIONAL TESTING. FUNCTIONAL TESTING <br />SHALL OCCUR AFTER ALL CONTROLS HAVE BEEN INSTALLED AND VERIFIED AND <br />AFTER TEST AND BALANCE IS COMPLETE. THE FUNCTIONAL PERFORMANCE <br />TEST PROCEDURES CAN BE FOUND IN THE COMMISSIONING PLAN. <br />D. IF THE TOTAL TIME REQUIRED TO CORRECT PROBLEMS DURING TESTING IS <br />GREATER THAT FORTY-FIVE (45) MINUTES (UNLESS EXTENUATING <br />CIRCUMSTANCES EXIST), THE TEST SHALL BE CONSIDERED FAILED AND MUST <br />BE REPEATED IN ITS ENTIRETY. <br />E. RE -TESTING: DURING THE COURSE OF THE RETEST, IF AT ANY POINT A MAJOR <br />DEFICIENCY IS DISCOVERED, THE TEST WILL BE STOPPED. REPEAT TESTS <br />UNTIL ACCEPTABLE RESULTS ARE ACHIEVED. IF MORE THAN TWO FUNCTIONAL <br />PERFORMANCE TESTS (ONE INITIAL TEST AND ONE RETEST) FOR ANY TYPE OF <br />EQUIPMENT DUE TO ISSUES THAT THE CONTRACTOR HAD DIRECT OR <br />INDIRECT CONTROL OVER ARE REQUIRED, THE COSTS FOR THE CXA TO <br />WITNESS RETESTING OF SIMILAR TYPES OF EQUIPMENT UNTIL SATISFACTORY <br />RESULTS ARE OBTAINED SHALL BE THE RESPONSIBILITY OF THE <br />CONTRACTOR. <br />3.03 TEST & BALANCE <br />A. OWNER SHALL TEST AND BALANCE MECHANICAL SYSTEM IN ACCORDANCE <br />WITH NEBB, NBC OR AABC STANDARDS TO ASSURE CONFORMANCE WITH <br />DESIGN. G.C. WILL MAKE MECHANICAL CONTRACTOR AVAILABLE DURING TEST <br />AND BALANCE TO ASSIST TESTING AGENCY AND TO MAKE CORRECTIONS <br />IMMEDIATELY NECESSARY. CONTRACTOR SHALL CORRECT ITEMS ON <br />WRITTEN TEST AND BALANCE REPORT. <br />B. ALL EQUIPMENT TO BE BALANCED MUST HAVE GONE THRU SUCCESSFUL START- <br />UP PROCEDURE BY THE MECHANICAL CONTRACTOR (MC) PRIOR TO TAB VISIT. <br />C. THE FLOOR OF THE RESTAURANT SHALL BE CLEARED OF DEBRIS, STAGED <br />CONSTRUCTION MATERIALS, EQUIPMENT, ETC. WHICH MAY, IN THE OPINION OF <br />THE TAB TECHNICIAN, OBSTRUCT ACCESS TO AIR DISTRIBUTION COMPONENTS <br />IN AND ABOVE THE CEILING. <br />D. EQUIPMENT ACCESS PANELS, DUCT AIR DEVICES SUCH AS BALANCING <br />DAMPERS AND ACTUATORS SHALL BE ACCESSIBLE AND CLEAR OF PIPING, <br />CONDUIT, FRAMING, SUPPORTS ETC... <br />E. PROVIDE AN 8 FT PORTABLE A -FRAME STYLE LADDER DEDICATED FOR THE TAB <br />TECHNICIAN'S USE DURING THE ENTIRE TAB EFFORT DURATION. <br />F. THE MC SHALL BE AVAILABLE DURING THE ENTIRE DURATION OF THE TAB <br />EFFORT AND HAVE ON -SITE THE RESOURCES AND TOOLS TO MAKE <br />CORRECTIONS AS NEEDED UNDER THE DIRECTION OF THE TAB TECHNICIAN. <br />NATIONAL ACCOUNTS <br />1. LENNOX EQUIPMENT - CONTACT LENNOX NATIONAL ACCOUNTS AT <br />972-497-6260 (OR BY FAX AT 972-497-5112) FOR PRICING, ORDERING AND <br />AVAILABILITY. LENNOX EQUIPMENT NOT PURCHASED THRU LENNOX <br />NATIONAL ACCOUNTS WILL NOT BE ACCEPTED. <br />2. LOREN COOK FAN AND CURB PACKAGE - THE MECHANICAL CONTRACTOR IS <br />REQUIRED TO PURCHASE THE FAN/CURB PACKAGE DIRECTLY FROM TOM <br />BARROW COMPANY. CONTACT MR. SCOTT GEORGE AT 404-351-1010 FOR <br />PRICING AND AVAILABILITY. FANS AND CURBS NOT PURCHASED THRU TOM <br />BARROW COMPANY WILL NOT BE ACCEPTED. <br />3. PRICE AIR DEVICES - THE MECHANICAL CONTRACTOR IS REQUIRED TO <br />PURCHASE THE AIR DEVICES DIRECTLY FROM TOM BARROW COMPANY. <br />CONTACT MR. SCOTT GEORGE AT 404-351-1010 FOR PRICING AND <br />AVAILABILITY. AIR DEVICES NOT PURCHASED THRU TOM BARROW COMPANY <br />WILL NOT BE ACCEPTED. <br />4. AIR DOORS - THE MECHANICAL CONTRACTOR IS REQUIRED TO PURCHASE THE <br />AIR DOORS DIRECTLY FROM TOM BARROW COMPANY. CONTACT MR. SCOTT <br />GEORGE AT 404-351-1010 FOR PRICING AND AVAILABILITY. AIR DOORS NOT <br />PURCHASED THRU TOM BARROW COMPANY WILL NOT BE ACCEPTED. <br />5. SUNCOAST ENVIRONMENTAL CONTROLS - THE CFA 500 PANEL AND THE <br />TEST/RESET STATIONS WILL BE PURCHASED AND PROVIDED BY THE electrical <br />CONTRACTOR AS A PART OF A NATIONAL ACCOUNT PACKAGE. SEE PART II <br />PARAGRAPH 3A, 3D, AND 3E OF THE MECHANICAL SPECIFICATIONS FOR MORE <br />INFORMATION. <br />6. HALTON HOODS - CHICK-FIL-A WILL PURCHASE AND PROVIDE THE HOODS FOR <br />INSTALLATION BY THE MECHANICAL CONTRACTOR. THE MECHANICAL <br />CONTRACTOR SHALL BE RESPONSIBLE FOR RECEIVING THE HOODS. CONTACT <br />HALTON CO. AT 270-237-5600 FOR MORE INFO. <br />7. ROYAL METAL PRODUCTS START COLLARS - THE MECHANICAL CONTRACTOR <br />IS REQUIRED TO PURCHASE THE START COLLARS DIRECTLY FROM TOM <br />BARROW COMPANY. CONTACT MR. SCOTT GEORGE AT 404-351-1010 FOR <br />PRICING AND AVAILABILITY. START COLLARS NOT PURCHASED THRU TOM <br />BARROW COMPANY WILL NOT BE ACCEPTED. <br />E <br />f17 <br />C <br />B <br />Z <br />0 <br />c.i <br />M <br />A <br />Z <br />0 <br />V <br />W <br />0 <br />LL <br />0°0 ° <br />o� <br />Chick-fil-A <br />5200 Buffington Road <br />Atlanta, Georgia <br />30349-2998 <br />Kurzynske <br />& Associates <br />2900 Lebanon Pike, Ste 201 <br />Nashville, Tennessee 37214 <br />Telephone: (615) 255-5203 <br />Fax: (615) 255-5207 <br />Email: mail@kurzynske.com <br />MARK T. KURZYNSKE <br />FLORIDA LICENSE # 53568 <br />11111111111j <br />•` <br />�j; C'E N Z;4' <br />d9 <br />s o <br />�� • N VF. <br />r: <br />STAT� <br />O R 1 o%' (���•` <br />03/2 9/2 1 <br />Q <br />J (A <br />LL <br />Um Cn > M <br />W J <br />Q J <br />m <br />V� J= <br />om o= <br />a <br />N �N <br />BUILDING TYPE / SIZE: P13 LC ALL <br />RELEASE: v2.20.02 <br />REVISION SCHEDULE <br />NO. DATE DESCRIPTION <br />CONSULTANT PROJECT# 20090.CC.S <br />PRINTED FOR FOR CONSTRUCTION <br />DATE 07/29/2020 <br />DRAWN BY BLM <br />Information contained on this drawing and in all digital files <br />produced for above named project may not be reproduced in <br />any manner without express written or verbal consent from <br />authorized project representatives. <br />SHEET <br />MECHANICAL <br />SPECIFICATIONS <br />SHEET NUMBER <br />M=901 <br />4 <br />3 <br />2 <br />1 <br />