Laserfiche WebLink
AIR CONDITIONING UNIT SCHEDULE <br />ACU ACU <br />ACU <br />UNIT NO. T L <br />0 <br />LOCATION <br />ROOF <br />ROOF <br />ROOF <br />SERVICE <br />TELLER <br />LOBBY <br />OFFICE <br />TOTAL COOLING - MIN MBH <br />49 <br />44 <br />46 <br />SENSIBLE COOUNG - MIN MBH <br />36 <br />31 <br />34 <br />SEER MIN <br />13 <br />13 <br />13 <br />COIL EAT DB B <br />78 66 <br />78 66 <br />76 65 <br />HEATING - MIN MBH <br />21 <br />13 <br />18 <br />HEATER KW AT USTED VOLTAGE <br />9 <br />9 <br />9 <br />HTR STEPS - MIN <br />2 <br />2 <br />2 <br />TOTAL AIR CFM <br />1,740 <br />1600 <br />11600 <br />OUTSIDE AIR CFM <br />250 <br />250 <br />250 <br />ESP IN WG <br />0.9 <br />0.9 <br />0.9 <br />RPM <br />-- <br />-- <br />-- <br />BHP - MAX <br />-- <br />-- <br />-- <br />MOTOR HP <br />1 <br />1 <br />1 <br />ELECT FLA MCA MOCP <br />49 59 60 <br />49 59 60 <br />49 59 60 <br />ELECT PH HZ <br />208 3 60 <br />208 3 60 <br />208 3 60 <br />WEIGHT LBS <br />850 <br />850 <br />850 <br />MANUFACTURER <br />TRANE <br />TRANE <br />TRANE <br />MODEL N0. <br />WSC-048-E <br />WSC-048-E <br />WSC-048-E <br />REMARKS <br />1-14 <br />1-14 <br />1-14 <br />REMARK NUMBERS: <br />1. NATIONAL SALES CONTRACT: WACHOVIA HAS ENTERED <br />INTO A NATIONAL SALES CONTRACT WITH TRANE. THE <br />GENERAL CONTRACTOR / HVAC SUB -CONTRACTORS <br />SHALL CONTACT BARNEY HIGH, LEED, AP, TRANE <br />NATIONAL ACCOUNT MANAGER AT (704) 529-3295 <br />(TELEPHONE) OR (704) 277-7126 (CELL PHONE) TO <br />PURCHASE AIR CONDITIONING EQUIPMENT SHOWN ON <br />THE DRAWINGS. NO SUBSTITUTIONS SHALL BE <br />ACCEPTED. <br />2. MINIMUM FILTER EFFICIENCIES PER ASHRAE STD. 52-76. <br />3. PROVIDE SINGLE POINT POWER CONNECTION <br />4. PROVIDE FACTORY FABRICATED ROOF CURB TO MATCH ROOF <br />SLOPE. VERIFY ROOF SLOPE WITH ARCHITECTURAL DRAWINGS. <br />5. PROVIDE THROUGH THE BASE ELECTRICAL WITH DISCONNECT <br />AND FACTORY POWERED CONVENIENCE OUTLET (ONE PER PROJECT) <br />ALL FINAL ELECTRICAL CONNECTIONS TO EQUIPMENT SHALL <br />BE MADE BY MECHANICAL CONTRACTOR. <br />6. PROVIDE MANUFACTURER'S 7-DAY PROGRAMMABLE, <br />ELECTRONIC NIGHT SETBACK THERMOSTAT (TRANE BAYSTAT050A). <br />7. R-41OA REFRIGERANT. <br />8. FILTERS: 145 FPM FACE VELOCITY; AEROSTAR MERV 13 GREEN <br />PLEAT, <br />(2) 20 x 30 X 2 FILTERS, 0.1 IN. WG. AIR PRESSURE DROP (CLEAN); <br />1.0 IN. WG AIR PRESSURE DROP (DIRTY), 0.24 IN WC AT 375 FPM (MAXIMUM). <br />ACCEPTABLE MANUFACTURERS: FILTRATION GROUP INC. (OR APPROVED). <br />9. EXTERNAL STATIC PRESSURES INCLUDES AN ALLOWANCE FOR DIRTY <br />AIR FILTERS (0.5" ESP DUCTWORK + 0.12" FILTERS). <br />10. PROVIDE CO2 SENSING OPTION WITH DUCT MOUNTED SENSOR. <br />11. PROVIDE HINGED ACCESS PANELS. <br />12. PROVIDE BLACK EPDXY PRE -COATED CONDENSER COIL <br />13. PROVIDE FIELD SUPPUED HIGH STATIC DRIVE KIT. <br />14. PROVIDE OA HOOD / DAMPER AND CONTROLS FOR CO2 OPERATION <br />USING MAXIMUM OA CFM SHOWN. <br />AIR DEVICE SCHEDULE <br />A C D E <br />SYMBOL <br />TYPE <br />AIR OUTLET <br />AIR OUTLET <br />AIR OUTLET <br />AIR OUTLET <br />MOUNTING <br />CEIUNG <br />CEIUNG <br />SIDEWALL <br />CEIUNG <br />FRAME <br />T-BAR <br />T-BAR <br />SURFACE <br />T-BAR <br />FACE <br />SQUARE PLAQUE <br />UNEAR 2 3 4" SLOTS <br />ADJ. DOUBLE DEFL. <br />SQUARE PLAQUE <br />STYLE <br />DAMPER <br />MODULAR 24 X 24 <br />OBD <br />48 LONG W BOOT <br />OBD <br />NOT MODULAR <br />OBD <br />MODULAR 24 X 24 1 <br />INTEGRAL <br />FINISH <br />OFF-WHITE <br />OFF-WHITE <br />OFF-WHITE <br />OFF-WHITE <br />MANUFACTURER <br />TITUS <br />TITUS <br />TITUS <br />_ <br />TITUS <br />MODEL NO. <br />OMNI <br />ML-38 <br />300FL <br />T2SQ-4 <br />REMARKS <br />1,2,3 <br />1.3.5 <br />_ <br />1.3 <br />1,3.4 <br />_ <br />B F <br />SYMBOL <br />TYPE <br />AIR INLET <br />AIR INLET <br />MOUNTING- <br />CEIUNG <br />SIDEWALL <br />FRAME <br />- _ <br />T-BAR <br />SURFACE <br />FACE <br />SQUARE PLAQUE <br />BAR <br />STYLE <br />MODULAR 24 X 24 <br />NOT MODULAR <br />DAMPER <br />NONE <br />NONE <br />FINISH <br />OFF-WHITE <br />OFF-WHITE ---- <br />- -- _ - <br />MANUFACTURER_ <br />- <br />TITUS <br />_ <br />TITUS <br />MODEL NO. <br />OMNI <br />REMARKS <br />-- 1,3 <br />1,3 <br />_ <br />REMARK NUMBERS: <br />1. REFER TO DRAWING FOR NECK SIZES. <br />2. FOUR WAY BLOW UNLESS OTHERWISE INDICATED ON DRAWING. PROVIDE INSULATED BACKPAN. <br />3. PROVIDE FLEXIBLE DUCT CONNECTION SIZED AT NECK SIZE OF AO. <br />4. SELF POWERED VAV DIFFUSER: COOUNG SETPOINT 70 DEGREES, HEATING SETPOINT 72 DEGREES. <br />5. PROVIDE FACTORY INSULATED PLENUM. <br />6. ACCEPTABLE MANUFACTURERS: TITUS,-CARNES, KRUEGER, NAILER AND PRICE. - -� <br />EXHAUST FAN SCHEDULE <br />EF <br />EF <br />EF <br />EF <br />EF <br />UNIT NO. <br />M <br />W <br />J <br />TF1 <br />TF2 <br />LOCATION <br />CEIUNG <br />CEIUNG <br />CEIUNG <br />CEIUNG <br />CEIUNG <br />SERVICE <br />MEN <br />WOMEN <br />JAN <br />ATM ROOM <br />TELE DATA <br />TOTAL AIR CFM <br />75 <br />90 <br />75 <br />280 <br />580 <br />ESP IN WG <br />0.25 <br />0.25 <br />0.25 <br />0.25 <br />0.25 <br />SOUND - MAX (SONES) <br />3 <br />3 <br />3 <br />3 <br />1.2 <br />RPM <br />1,200 <br />1,200 <br />1,200 <br />1.200 <br />1,375 <br />MOTOR HP OR WATTS <br />65W <br />65W <br />65W <br />172W <br />301W <br />ELECT MCA MOCP <br />-- <br />-- <br />-- <br />-- <br />-- <br />ELECT PH HZ <br />120 1 60 <br />120 1 60 <br />120 1 60 <br />120 1 60 <br />120 1 60 <br />WEIGHT LBS <br />30 <br />30 <br />30 <br />40 <br />40 <br />MANUFACTURER <br />COOK <br />COOK <br />COOK <br />COOK <br />COOK <br />MODEL NO. <br />GC-240 <br />GC-240 <br />GC-240 <br />GC-520 <br />GC-720 <br />REMARKS <br />1.2,4 <br />1.2,4 <br />1.4,5 <br />1.3.4 <br />1,3,4 <br />REMARK NUMBERS: <br />1. CENTRIFUGAL IN-UNE CEIUNG FAN, <br />DIRECT DRIVE, BACKDRAFT DAMPER, <br />PLUG-IN MOTOR SERVES AS <br />DISCONNECT, ADJUSTABLE MOTOR SPEED <br />CONTROLLER (FOR T&B). <br />2. PROVIDE 365-DAY DIGITAL.PROGRAMMABLE <br />TIME CLOCK, <br />INTERMATIC MODEL <br />E770115C OR <br />EQUAL <br />3. PROVIDE WALL MOUNTED <br />UNE VOLTAGE HIGH UMIT COOLING THERMSTAT SET AT 80 DEGREES F. <br />4. ACCEPTABLE MANUFACTURERS: COOK, CARNES AND GREENHECK. <br />5. PROVIDE 6 HR. MECHANICAL TIME <br />(MARKTIME 93505) <br />ADJACENT TO SPEED CONTROLLER <br />TO TURN FAN ON. <br />MECHANICAL (HVAC) NOTES: <br />1 A. REGULATORY REQUIREMENTS: PROVIDE ALL WORK TO MEET OR EXCEED MINIMUM <br />REGULATORY REQUIREMENTS INCLUDING: <br />FLORIDA BUILDING CODE: 2004 EDITION WITH 2O06 SUPPLEMENT <br />FLORIDA FIRE PREVENTION CODE: 2006 EDITION <br />ADVISE THE ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS THAT MAY BE <br />REQUIRED IN ORDER TO MEET CODE, PRIOR TO WORK (ORDERING, ROUGHING OR <br />INSTALLING). <br />B. COORDINATION: COORDINATE WITH OTHER WORK (INCLUDING ELECTRICAL, AND <br />ARCHITECTURAL) FOR AVAILABLE SPACE, SEQUENCE OF INSTALLATION, AND <br />INSTALLATION REQUIREMENTS, PRIOR TO COMMENCING CONSTRUCTION. ADVISE THE <br />ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS THAT MAY BE REQUIRED <br />FOR THE WORK TO BE PERFORMED. <br />C. EXISTING FIELD CONDITIONS: THE CONTRACT DOCUMENTS INDICATE THE DESIGN <br />INTENT USING AVAILABLE INFORMATION. THE CONTRACTOR IS TO ADVISE THE <br />ARCHITECT IF EXISTING CONDITIONS DIFFER FROM THOSE SHOWN. ALSO ADVISE THE <br />ARCHITECT IF CODE OR SAFETY CONFLICTS EXIST. THE CONTRACTOR IS REQUIRED TO <br />INSPECT THE SITE (PRIOR TO BID) TO BECOME FAMILIAR WITH CONDITIONS AND <br />INSTALLATION DETAILS THAT WILL AFFECT HIS WORK. CHANGES IN THE CONTRACT <br />SUM AND CONTRACT TIME WILL NOT BE ALLOWED FOR FAILURE TO INVESTIGATE FIELD <br />CONDITIONS. ALL WORK IS NEW, UNLESS NOTED OTHERWISE. <br />D. DEVICE LOCATIONS: REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF <br />AIR OUTLETS, AIR INLETS, AND OTHER CEIUNG ITEMS (TO AVOID CONFLICTS). LOCATE <br />ALL PIPING AND DUCTWORK IN FINISHED ROOMS OR SPACES WITHIN CONCEALED <br />LOCATIONS (FURRED CHASES OR SUSPENDED CEIUNGS, AS AVAILABLE). DO NOT <br />LOCATE PIPING OR DUCTWORK ABOVE ELECTRICAL SWITCHBOARDS OR PANELBOARDS. <br />E. SIZES: WHEN A PIPE OR A DUCT SIZE IS NOT INDICATED, SIZE THAT PIPE OR DUCT <br />USING THE LARGER ADJACENT UPSTREAM SIZE, UNLESS A SMALLER SIZE IS APPROVED <br />BY THE ARCHITECT. PROVIDE 3/4 INCH MINIMUM PIPE SIZE, UNLESS SPECIFICALLY <br />NOTED OTHERWISE. FOR SIZES NOT INDICATED ON PLANS, REFER TO EQUIPMENT <br />DETAILS, FLOW DIAGRAMS, RISER DIAGRAMS, AND OTHER LOCATIONS IN THE CONTRACT <br />DOCUMENTS (DRAWINGS AND SPECIFICATIONS) FOR INFORMATION. <br />F. BASIS OF DESIGN: THE MECHANICAL CONTRACT DOCUMENTS HAVE BEEN PREPARED <br />USING THE FOLLOWING DATA IN THE CALCULATIONS (SIMPLIFIED FOR PRESENTATION <br />HERE): <br />INDOOR OUTDOOR <br />SUMMER 75 DB/50% RH 92 DB/79 WB <br />WINTER 72 DB 40 DB <br />G. PRIOR TO ROUGHING OR ORDERING, VERIFY ADEQUATE CLEARANCES FOR DUCTWORK, <br />OTHER WORK, ELECTRICAL CONDUITS AND LIGHTING. <br />2 SCOPE OF WORK: <br />A. PROVIDE NEW ROOFTOP UNITS, DUCTWORK, CEIUNG EXHAUST FANS AND ACCESSORIES. <br />B. PROVIDE NEW AHU'S, CU'S, EF'S, CEILING AIR DEVICES, AND ASSOCIATED DUCTWORK, <br />AS SHOWN. <br />C. T&B: <br />1) T&B NEW ACU, EF, DIFFUSERS, AND DAMPERS, AND PROVIDE FINAL T&B REPORT <br />3 PROVIDE ALL NECESSARY FEES AND PERMITS. REVIEW OPERATION OF EACH SYSTEM WITH <br />OWNER'S REPRESENTATIVE. PROVIDE ONE YEAR WARRANTY ON ENTIRE SYSTEM. PROVIDE <br />RECORD DRAWING (CONTRACTOR FURNISHED PRINT). SUBMITTALS: SUBMIT PRODUCT DATA <br />FOR EACH NEW MECHANICAL DEVICE AND TEST AND BALANCE REPORT. <br />5 ACCESS DOORS: PROVIDE 18 INCH X 18 INCH (MINIMUM) PAINTED, ALUMINUM ACCESS <br />DOOR (WITH FULL HINGE AND KEY) FOR ACCESS TO VALVES, EQUIPMENT, AND <br />ACCESSORIES IN PLASTER, DRYWALL, OR INACCESSIBLE CEILINGS OR IN WALLS. PROVIDE <br />INSULATED ACCESS DOORS (DO NOT SUBSTITUTE PANELS) IN DUCTWORK FOR ACCESS TO <br />DAMPERS AND OTHER OPERATING DEVICES (INCLUDING UPSTREAM OF ELECTRIC RESISTANCE <br />DUCT HEATERS AND AT DUCT MOUNTED SMOKE DETECTORS). GROUP DEVICES AT ON <br />LOCATION, AS AVAILABLE. <br />5 AIR DISTRIBUTION: <br />A. DUCTWORK: <br />1) TEST (BY FEEL OR TEMPERATURE CHANGE) EACH DUCTWORK SYSTEM FOR <br />LEAKS BEFORE INSULATING. RESEAL, AS REQUIRED. <br />2) DUCT DIMENSIONS INDICATE AIR FLOW SIZES. <br />3) AT CONTRACTOR'S OPTION, EQUAL AREA DUCTWORK HAVING A MAXIMUM 4 TO 1 <br />ASPECT RATIO MAY BE SUBSTITUTED FOR DUCT DIMENSIONS SHOWN. <br />4) FLEXIBLE DUCTWORK (USED TO CONNECT TO SUPPLY AIR OUTLETS: THERMAFLEX <br />TYPE M-KE (OR AS APPROVED). <br />5) BRANCH DUCT CONNECTIONS (POSITIVE AND NEGATIVE PRESSURE): ON <br />RECTANGULAR DUCTS, PROVIDE VOLUME EXTRACTORS OR 45 DEGREE ENTRIES; <br />ON CIRCULAR DUCTS, PROVIDE CONICAL TAPS (WITH DAMPERS). PROVIDE THESE <br />CONNECTIONS ON EACH BRANCH DUCT CONNECTION FOR EACH SYSTEM; DO NOT <br />SUBSTITUTE "T" CONNECTIONS. <br />6) INSTALL DUCTWORK AND ACCESSORIES IN ACCORDANCE WITH SMACNA HVAC DUCT <br />CONSTRUCTION STANDARDS - METAL AND FLEXIBLE. <br />6 ALL BRANCH TAKE -OFFS TO DIFFUSERS SHALL HAVE BALANCING DAMPERS. <br />7 MOUNT T'STATS 4'-0" A.F.F. <br />8 ALL REFRIGERANT LINES SHALL USE LONG RADIUS ELBOWS FOR TURNS, NO BENDS. <br />9 ALL NEW SA, RA, EA, MA, TA, AND OA DUCTWORK SHALL BE GALVANIZED STEEL WITH 2" <br />FIBERGLASS DUCT WRAP AND VAPOR BARRIER, OR R=6 FLEX DUCT (THERMAFLEX MKE, OR <br />AS APPROVED). USE ONLY METALLIC DUCTWORK FOR EXHAUST AIR (EA) DUCTS, PER THE <br />FBC. <br />10 PROVIDE TWO (2) SETS OF NEW FILTERS FOR AIR HANDLING UNITS, INSTALL ONE SET <br />INITIALLY AND ONE SET UPON COMPLETION OF CONSTRUCTION. <br />11 PROVIDE AND INSTALL TRANE MODEL BAYSTAT040 AUTOMATIC CHANGEOVER, PROGRAMMABLE <br />HEATING AND COOUNG THERMOSTAT. THE MECHANICAL CONTRACTOR SHALL PROGRAM ALL <br />THERMOSTATS IN ACCORDANCE WITH THE FOLLOWING SCHEDULE OR AS INSTRUCTED BY <br />OWNER. <br />D0Y I1NE COOLING SETPOINT HEATING SETPOINT <br />MONDAY 5:00 AM 74 DEGREES F 70 DEGREES F <br />6:00 PM 84 DEGREES F <br />TUESDAY <br />6:00 <br />AM <br />74 <br />DEGREES F <br />6:00 <br />PM <br />84 <br />DEGREES F <br />WEDNESDAY <br />6:00 <br />AM <br />74 <br />DEGREES F <br />6:00 <br />PM <br />84 <br />DEGREES F <br />THURSDAY <br />6:00 <br />AM <br />74 <br />DEGREES F <br />6:00 <br />PM <br />84 <br />DEGREES F <br />FRIDAY <br />6:00 <br />AM <br />74 <br />DEGREES F <br />7:00 <br />PM <br />84 <br />DEGREES F <br />SATURDAY 6:00 AM <br />74 <br />DEGREES F <br />7:00 PM <br />BRANCH BANKS SATURDAY <br />84 <br />DEGREES F <br />WITHOUT <br />OPERATION <br />DEGREES F <br />SATURDAY ALL DAY <br />84 <br />SUNDAY ALL DAY <br />84 <br />DEGREES F <br />62 DEGREES F <br />70 DEGREES F <br />62 DEGREES F <br />70 DEGREES F <br />62 DEGREES F <br />70 DEGREES F <br />62 DEGREES F <br />70 DEGREES F <br />62 DEGREES F <br />70 DEGREES F <br />62 DEGREES F <br />62 DEGREES F <br />62 DEGREES F <br />MECHANICAL LEGEND <br />SYMBOL <br />DESCRIPTION <br />® <br />POSITIVE PRESSURE DUCTWORK (SUPPLY AIR, RELIEF AIR) <br />NEGATIVE PRESSURE DUCTWORK (RETURN AIR, EXHAUST AIR, <br />OUTSIDE AIR INTAKE) <br />NEW DUCT OR DEVICES <br />\ \ \ \\ <br />/ / <br />FLEXIBLE DUCTWORK <br />T <br />THERMOSTAT (WALL MOUNTED AT 48" A.F.F.) <br />AIR FLOW: POSITIVE PRESSURE; NEGATIVE PRESSURE <br />BRANCH DUCT CONNECTION: WITH CONICAL CONNECTION AND DAMPER <br />OA <br />AIR OUTLET TYPE (A); 12" CONNECTION SIZE; AND 100 CFM <br />INDICATED. BRANCH DUCT SIZE MATCHES CONNECTION SIZE, <br />_ <br />12" <br />UNLESS NOTED OTHERWISE. THROW: 4 WAY, UNLESS NOTED <br />100 <br />OTHERWISE. <br />O <br />AIR INLET TYPE (N); CONNECTION SIZE; AND MAXIMUM CFM <br />INDICATED. BRANCH DUCT SIZE MATCHES CONNECTION SIZE, <br />UNLESS NOTED OTHERWISE. <br />- U <br />3/4" DOOR UNDERCUT- COORDINATE WITH ARCHITECTURAL WORK. <br />MANUAL VOLUME / BALANCING DAMPER <br />CO2 <br />DUCT MOUNTED CO2 SENSOR <br />DP <br />DIFFERENTIAL PRESSURE TRANSMITTER <br />eAIR <br />HANDLING UNIT TYPE <br />CU <br />0 <br />CONDENSING UNIT TYPE <br />EF <br />O <br />EXHAUST FAN TYPE <br />ODRAWING <br />NOTE: REFER TO NOTES ON EACH DRAWING <br />ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION <br />BTU BRITISH THERMAL UNIT <br />LAT LEAVING AIR TEMPERATURE <br />CFM CUBIC FEET PER MINUTE <br />LDB LEAVING DRY BULB <br />DB DRY <br />BULB <br />LWB LEAVING WET BULB <br />ESP EXTERNAL STATIC PRESSURE <br />MBH THOUSAND BTU PER HOUR <br />NP TYPICAL <br />RA RETURN AIR <br />WB WET <br />BULB <br />RH RELATIVE HUMIDITY <br />SP STATIC PRESSURE <br />SA SUPPLY AIR <br />12 THE MECHANICAL <br />CONTRACTOR <br />SHALL PROGRAM THE WALL - MOUNTED TIME CLOCKS IN <br />ACCORDANCE WITH THE <br />FOLLOWING SCHEDULE OR AS INSTRUCTED BY OWNER. <br />DAY <br />IlME <br />MONDAY <br />8:00 <br />AM <br />ON <br />5:00 <br />PM <br />OFF <br />TUESDAY <br />8:00 <br />AM <br />ON <br />5:00 <br />PM <br />OFF <br />WEDNESDAY <br />8:00 <br />AM <br />ON <br />5:00 <br />PM <br />OFF <br />THURSDAY <br />8:00 <br />AM <br />ON <br />5:00 <br />PM <br />OFF <br />FRIDAY <br />8:00 <br />AM <br />ON <br />BRANCH WITH SATURDAY <br />6:00 <br />PM <br />OPERATION <br />OFF <br />SATURDAY <br />8:00 <br />AM <br />ON <br />BRANCH <br />5:00 <br />PM <br />OFF <br />BANKS <br />SATURDAY <br />WITHOUT <br />SATURDAY <br />OPERATION <br />OFF <br />SUNDAY <br />OFF <br />HOLIDAYS <br />OFF <br />13 ALL DUCT SIZES ARE ACTUAL SHEET METAL DIMENSIONS. <br />14 - 59 NOT USED. <br />60 ROUTE THE SUPPLY AND RETURN DUCT UP TO THE ROOF MOUNTED ACU. REFER TO <br />DRAWING M1.2. <br />61 ROUTE THE 12 INCH EXHAUST DUCT UP TO ROOF CAP. REFER TO "EXHAUST FAN <br />DISCHARGE DETAIL" ON DRAWING M1.2. <br />62 ROUTE THE 8 INCH EXHAUST DUCT UP TO ROOF CAP. REFER TO "EXHAUST FAN <br />DISCHARGE DETAIL" ON DRAWING M1.2. <br />63 PROVIDE A CURB MOUNTED ROOF CAP FOR EF-J. PROVIDE COOK MODEL PR-8. <br />PROVIDE A MINIMUM OF 10 FEET FROM OUTSIDE AIR INTAKES OF ROOFTOP UNITS. <br />PROVIDE BACKDRAFT DAMPER (LOW PRESSURE LOSS TYPE) IN NECK AT ROOF CAP. <br />64 ROUTE A 4 X 12 SUPPLY AIR DUCT DOWN TO OPENING IN VAULT. BALANCE AIRFLOW <br />TO 100 CFM. TRANSITION TO AN INTERIOR OPENING IN VAULT AND ROUTE TO CEILING <br />DIFFUSER. COORDINATE WITH ARCHITECTURAL PLANS. COORDINATE THE VAULT DUCT <br />CONNECTION SIZE AND LOCATION WITH THE VAULT SUPPLIER. TRANSITION, AS REQUIRED. <br />COORDINATE THE DUCTING WITHIN THE VAULT TO MAINTAIN MAXIMUM CEILING HEIGHT <br />(TRANSITION, AS REQUIRED). <br />®5 PROVIDE A CURB MOUNTED ROOF CAP FOR EF W AND M. PROVIDE COOK MODEL PR-12. <br />PROVIDE A MINIMUM OF 10 FEET FROM OUTSIDE AIR INTAKES OF ROOFTOP UNITS. <br />PROVIDE BACKDRAFT DAMPER (LOW PRESSURE LOSS TYPE) IN NECK AT ROOF CAP. <br />66 NOT USED. <br />67 NOT USED. <br />6® PROVIDE A ROOF MOUNTED ACU. REFER TO "ROOFTOP UNIT DETAIL" ON DRAWING M1.2. <br />69 PROVIDE 1 INCH CONDENSATE PIPING. PROVIDE MIRO INDUSTRIES MODEL 1.5 PIPE <br />SUPPORTS. PROVIDE 4'-0" MAXIMUM SPACING. <br />OO TERMINATE CONDENSATE DRAINS INTO THE ROOF DRAIN. <br />MECHANICAL -LEGEND, NOTES, SCHEDULES <br />SCALE: NONE <br />Notes: <br />Revisions: <br />Seal: <br />jil AY /r1(�y <br />Consultants: <br />0 <br />ARCHITECTURAL ENGINEERING INCORPORATE <br />3442 EAST LAKE ROAD, PALM HARBOR, FL 3461 <br />CONSULTING ENGINEERS (727) 784-14. <br />CERTIFICATE OF AUTHORIZATION: FL 3W <br />W. RONALD MCILVEEN FL PE 3027 <br />�9 <br />r`• <br />WP- r <br />I� A <br />4 <br />40 <br />�Ir� IR • <br />E L E M E N T S <br />ARCHITECTS -INTERIOR DESIGNERS <br />Tampa Office <br />The Edgewater Building <br />600 South Magnolia Avenue <br />Suite 150 <br />Tampa, Florida 33606 <br />Phone (813) 251-0565 <br />Pax (813) 251-0567 <br />Mial n1 Offi -_e <br />1699 Coral Way suite 503 <br />Miami, Florida 33145 <br />Phone (305) 858-5858 <br />Pax (305) 858-5850 <br />�i.. 7777y, <br />WACHOVIA <br />COAST• s <br />Fa <br />. . <br />HERNANDO COUNTY <br />�A <br />► _7"-2z = <br />NECHANCAL <br />LEGEND,NOTES,SCW-DULES <br />