AIR CONDITIONING UNIT SCHEDULE
<br />ACU ACU
<br />ACU
<br />UNIT NO. T L
<br />0
<br />LOCATION
<br />ROOF
<br />ROOF
<br />ROOF
<br />SERVICE
<br />TELLER
<br />LOBBY
<br />OFFICE
<br />TOTAL COOLING - MIN MBH
<br />49
<br />44
<br />46
<br />SENSIBLE COOUNG - MIN MBH
<br />36
<br />31
<br />34
<br />SEER MIN
<br />13
<br />13
<br />13
<br />COIL EAT DB B
<br />78 66
<br />78 66
<br />76 65
<br />HEATING - MIN MBH
<br />21
<br />13
<br />18
<br />HEATER KW AT USTED VOLTAGE
<br />9
<br />9
<br />9
<br />HTR STEPS - MIN
<br />2
<br />2
<br />2
<br />TOTAL AIR CFM
<br />1,740
<br />1600
<br />11600
<br />OUTSIDE AIR CFM
<br />250
<br />250
<br />250
<br />ESP IN WG
<br />0.9
<br />0.9
<br />0.9
<br />RPM
<br />--
<br />--
<br />--
<br />BHP - MAX
<br />--
<br />--
<br />--
<br />MOTOR HP
<br />1
<br />1
<br />1
<br />ELECT FLA MCA MOCP
<br />49 59 60
<br />49 59 60
<br />49 59 60
<br />ELECT PH HZ
<br />208 3 60
<br />208 3 60
<br />208 3 60
<br />WEIGHT LBS
<br />850
<br />850
<br />850
<br />MANUFACTURER
<br />TRANE
<br />TRANE
<br />TRANE
<br />MODEL N0.
<br />WSC-048-E
<br />WSC-048-E
<br />WSC-048-E
<br />REMARKS
<br />1-14
<br />1-14
<br />1-14
<br />REMARK NUMBERS:
<br />1. NATIONAL SALES CONTRACT: WACHOVIA HAS ENTERED
<br />INTO A NATIONAL SALES CONTRACT WITH TRANE. THE
<br />GENERAL CONTRACTOR / HVAC SUB -CONTRACTORS
<br />SHALL CONTACT BARNEY HIGH, LEED, AP, TRANE
<br />NATIONAL ACCOUNT MANAGER AT (704) 529-3295
<br />(TELEPHONE) OR (704) 277-7126 (CELL PHONE) TO
<br />PURCHASE AIR CONDITIONING EQUIPMENT SHOWN ON
<br />THE DRAWINGS. NO SUBSTITUTIONS SHALL BE
<br />ACCEPTED.
<br />2. MINIMUM FILTER EFFICIENCIES PER ASHRAE STD. 52-76.
<br />3. PROVIDE SINGLE POINT POWER CONNECTION
<br />4. PROVIDE FACTORY FABRICATED ROOF CURB TO MATCH ROOF
<br />SLOPE. VERIFY ROOF SLOPE WITH ARCHITECTURAL DRAWINGS.
<br />5. PROVIDE THROUGH THE BASE ELECTRICAL WITH DISCONNECT
<br />AND FACTORY POWERED CONVENIENCE OUTLET (ONE PER PROJECT)
<br />ALL FINAL ELECTRICAL CONNECTIONS TO EQUIPMENT SHALL
<br />BE MADE BY MECHANICAL CONTRACTOR.
<br />6. PROVIDE MANUFACTURER'S 7-DAY PROGRAMMABLE,
<br />ELECTRONIC NIGHT SETBACK THERMOSTAT (TRANE BAYSTAT050A).
<br />7. R-41OA REFRIGERANT.
<br />8. FILTERS: 145 FPM FACE VELOCITY; AEROSTAR MERV 13 GREEN
<br />PLEAT,
<br />(2) 20 x 30 X 2 FILTERS, 0.1 IN. WG. AIR PRESSURE DROP (CLEAN);
<br />1.0 IN. WG AIR PRESSURE DROP (DIRTY), 0.24 IN WC AT 375 FPM (MAXIMUM).
<br />ACCEPTABLE MANUFACTURERS: FILTRATION GROUP INC. (OR APPROVED).
<br />9. EXTERNAL STATIC PRESSURES INCLUDES AN ALLOWANCE FOR DIRTY
<br />AIR FILTERS (0.5" ESP DUCTWORK + 0.12" FILTERS).
<br />10. PROVIDE CO2 SENSING OPTION WITH DUCT MOUNTED SENSOR.
<br />11. PROVIDE HINGED ACCESS PANELS.
<br />12. PROVIDE BLACK EPDXY PRE -COATED CONDENSER COIL
<br />13. PROVIDE FIELD SUPPUED HIGH STATIC DRIVE KIT.
<br />14. PROVIDE OA HOOD / DAMPER AND CONTROLS FOR CO2 OPERATION
<br />USING MAXIMUM OA CFM SHOWN.
<br />AIR DEVICE SCHEDULE
<br />A C D E
<br />SYMBOL
<br />TYPE
<br />AIR OUTLET
<br />AIR OUTLET
<br />AIR OUTLET
<br />AIR OUTLET
<br />MOUNTING
<br />CEIUNG
<br />CEIUNG
<br />SIDEWALL
<br />CEIUNG
<br />FRAME
<br />T-BAR
<br />T-BAR
<br />SURFACE
<br />T-BAR
<br />FACE
<br />SQUARE PLAQUE
<br />UNEAR 2 3 4" SLOTS
<br />ADJ. DOUBLE DEFL.
<br />SQUARE PLAQUE
<br />STYLE
<br />DAMPER
<br />MODULAR 24 X 24
<br />OBD
<br />48 LONG W BOOT
<br />OBD
<br />NOT MODULAR
<br />OBD
<br />MODULAR 24 X 24 1
<br />INTEGRAL
<br />FINISH
<br />OFF-WHITE
<br />OFF-WHITE
<br />OFF-WHITE
<br />OFF-WHITE
<br />MANUFACTURER
<br />TITUS
<br />TITUS
<br />TITUS
<br />_
<br />TITUS
<br />MODEL NO.
<br />OMNI
<br />ML-38
<br />300FL
<br />T2SQ-4
<br />REMARKS
<br />1,2,3
<br />1.3.5
<br />_
<br />1.3
<br />1,3.4
<br />_
<br />B F
<br />SYMBOL
<br />TYPE
<br />AIR INLET
<br />AIR INLET
<br />MOUNTING-
<br />CEIUNG
<br />SIDEWALL
<br />FRAME
<br />- _
<br />T-BAR
<br />SURFACE
<br />FACE
<br />SQUARE PLAQUE
<br />BAR
<br />STYLE
<br />MODULAR 24 X 24
<br />NOT MODULAR
<br />DAMPER
<br />NONE
<br />NONE
<br />FINISH
<br />OFF-WHITE
<br />OFF-WHITE ----
<br />- -- _ -
<br />MANUFACTURER_
<br />-
<br />TITUS
<br />_
<br />TITUS
<br />MODEL NO.
<br />OMNI
<br />REMARKS
<br />-- 1,3
<br />1,3
<br />_
<br />REMARK NUMBERS:
<br />1. REFER TO DRAWING FOR NECK SIZES.
<br />2. FOUR WAY BLOW UNLESS OTHERWISE INDICATED ON DRAWING. PROVIDE INSULATED BACKPAN.
<br />3. PROVIDE FLEXIBLE DUCT CONNECTION SIZED AT NECK SIZE OF AO.
<br />4. SELF POWERED VAV DIFFUSER: COOUNG SETPOINT 70 DEGREES, HEATING SETPOINT 72 DEGREES.
<br />5. PROVIDE FACTORY INSULATED PLENUM.
<br />6. ACCEPTABLE MANUFACTURERS: TITUS,-CARNES, KRUEGER, NAILER AND PRICE. - -�
<br />EXHAUST FAN SCHEDULE
<br />EF
<br />EF
<br />EF
<br />EF
<br />EF
<br />UNIT NO.
<br />M
<br />W
<br />J
<br />TF1
<br />TF2
<br />LOCATION
<br />CEIUNG
<br />CEIUNG
<br />CEIUNG
<br />CEIUNG
<br />CEIUNG
<br />SERVICE
<br />MEN
<br />WOMEN
<br />JAN
<br />ATM ROOM
<br />TELE DATA
<br />TOTAL AIR CFM
<br />75
<br />90
<br />75
<br />280
<br />580
<br />ESP IN WG
<br />0.25
<br />0.25
<br />0.25
<br />0.25
<br />0.25
<br />SOUND - MAX (SONES)
<br />3
<br />3
<br />3
<br />3
<br />1.2
<br />RPM
<br />1,200
<br />1,200
<br />1,200
<br />1.200
<br />1,375
<br />MOTOR HP OR WATTS
<br />65W
<br />65W
<br />65W
<br />172W
<br />301W
<br />ELECT MCA MOCP
<br />--
<br />--
<br />--
<br />--
<br />--
<br />ELECT PH HZ
<br />120 1 60
<br />120 1 60
<br />120 1 60
<br />120 1 60
<br />120 1 60
<br />WEIGHT LBS
<br />30
<br />30
<br />30
<br />40
<br />40
<br />MANUFACTURER
<br />COOK
<br />COOK
<br />COOK
<br />COOK
<br />COOK
<br />MODEL NO.
<br />GC-240
<br />GC-240
<br />GC-240
<br />GC-520
<br />GC-720
<br />REMARKS
<br />1.2,4
<br />1.2,4
<br />1.4,5
<br />1.3.4
<br />1,3,4
<br />REMARK NUMBERS:
<br />1. CENTRIFUGAL IN-UNE CEIUNG FAN,
<br />DIRECT DRIVE, BACKDRAFT DAMPER,
<br />PLUG-IN MOTOR SERVES AS
<br />DISCONNECT, ADJUSTABLE MOTOR SPEED
<br />CONTROLLER (FOR T&B).
<br />2. PROVIDE 365-DAY DIGITAL.PROGRAMMABLE
<br />TIME CLOCK,
<br />INTERMATIC MODEL
<br />E770115C OR
<br />EQUAL
<br />3. PROVIDE WALL MOUNTED
<br />UNE VOLTAGE HIGH UMIT COOLING THERMSTAT SET AT 80 DEGREES F.
<br />4. ACCEPTABLE MANUFACTURERS: COOK, CARNES AND GREENHECK.
<br />5. PROVIDE 6 HR. MECHANICAL TIME
<br />(MARKTIME 93505)
<br />ADJACENT TO SPEED CONTROLLER
<br />TO TURN FAN ON.
<br />MECHANICAL (HVAC) NOTES:
<br />1 A. REGULATORY REQUIREMENTS: PROVIDE ALL WORK TO MEET OR EXCEED MINIMUM
<br />REGULATORY REQUIREMENTS INCLUDING:
<br />FLORIDA BUILDING CODE: 2004 EDITION WITH 2O06 SUPPLEMENT
<br />FLORIDA FIRE PREVENTION CODE: 2006 EDITION
<br />ADVISE THE ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS THAT MAY BE
<br />REQUIRED IN ORDER TO MEET CODE, PRIOR TO WORK (ORDERING, ROUGHING OR
<br />INSTALLING).
<br />B. COORDINATION: COORDINATE WITH OTHER WORK (INCLUDING ELECTRICAL, AND
<br />ARCHITECTURAL) FOR AVAILABLE SPACE, SEQUENCE OF INSTALLATION, AND
<br />INSTALLATION REQUIREMENTS, PRIOR TO COMMENCING CONSTRUCTION. ADVISE THE
<br />ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS THAT MAY BE REQUIRED
<br />FOR THE WORK TO BE PERFORMED.
<br />C. EXISTING FIELD CONDITIONS: THE CONTRACT DOCUMENTS INDICATE THE DESIGN
<br />INTENT USING AVAILABLE INFORMATION. THE CONTRACTOR IS TO ADVISE THE
<br />ARCHITECT IF EXISTING CONDITIONS DIFFER FROM THOSE SHOWN. ALSO ADVISE THE
<br />ARCHITECT IF CODE OR SAFETY CONFLICTS EXIST. THE CONTRACTOR IS REQUIRED TO
<br />INSPECT THE SITE (PRIOR TO BID) TO BECOME FAMILIAR WITH CONDITIONS AND
<br />INSTALLATION DETAILS THAT WILL AFFECT HIS WORK. CHANGES IN THE CONTRACT
<br />SUM AND CONTRACT TIME WILL NOT BE ALLOWED FOR FAILURE TO INVESTIGATE FIELD
<br />CONDITIONS. ALL WORK IS NEW, UNLESS NOTED OTHERWISE.
<br />D. DEVICE LOCATIONS: REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF
<br />AIR OUTLETS, AIR INLETS, AND OTHER CEIUNG ITEMS (TO AVOID CONFLICTS). LOCATE
<br />ALL PIPING AND DUCTWORK IN FINISHED ROOMS OR SPACES WITHIN CONCEALED
<br />LOCATIONS (FURRED CHASES OR SUSPENDED CEIUNGS, AS AVAILABLE). DO NOT
<br />LOCATE PIPING OR DUCTWORK ABOVE ELECTRICAL SWITCHBOARDS OR PANELBOARDS.
<br />E. SIZES: WHEN A PIPE OR A DUCT SIZE IS NOT INDICATED, SIZE THAT PIPE OR DUCT
<br />USING THE LARGER ADJACENT UPSTREAM SIZE, UNLESS A SMALLER SIZE IS APPROVED
<br />BY THE ARCHITECT. PROVIDE 3/4 INCH MINIMUM PIPE SIZE, UNLESS SPECIFICALLY
<br />NOTED OTHERWISE. FOR SIZES NOT INDICATED ON PLANS, REFER TO EQUIPMENT
<br />DETAILS, FLOW DIAGRAMS, RISER DIAGRAMS, AND OTHER LOCATIONS IN THE CONTRACT
<br />DOCUMENTS (DRAWINGS AND SPECIFICATIONS) FOR INFORMATION.
<br />F. BASIS OF DESIGN: THE MECHANICAL CONTRACT DOCUMENTS HAVE BEEN PREPARED
<br />USING THE FOLLOWING DATA IN THE CALCULATIONS (SIMPLIFIED FOR PRESENTATION
<br />HERE):
<br />INDOOR OUTDOOR
<br />SUMMER 75 DB/50% RH 92 DB/79 WB
<br />WINTER 72 DB 40 DB
<br />G. PRIOR TO ROUGHING OR ORDERING, VERIFY ADEQUATE CLEARANCES FOR DUCTWORK,
<br />OTHER WORK, ELECTRICAL CONDUITS AND LIGHTING.
<br />2 SCOPE OF WORK:
<br />A. PROVIDE NEW ROOFTOP UNITS, DUCTWORK, CEIUNG EXHAUST FANS AND ACCESSORIES.
<br />B. PROVIDE NEW AHU'S, CU'S, EF'S, CEILING AIR DEVICES, AND ASSOCIATED DUCTWORK,
<br />AS SHOWN.
<br />C. T&B:
<br />1) T&B NEW ACU, EF, DIFFUSERS, AND DAMPERS, AND PROVIDE FINAL T&B REPORT
<br />3 PROVIDE ALL NECESSARY FEES AND PERMITS. REVIEW OPERATION OF EACH SYSTEM WITH
<br />OWNER'S REPRESENTATIVE. PROVIDE ONE YEAR WARRANTY ON ENTIRE SYSTEM. PROVIDE
<br />RECORD DRAWING (CONTRACTOR FURNISHED PRINT). SUBMITTALS: SUBMIT PRODUCT DATA
<br />FOR EACH NEW MECHANICAL DEVICE AND TEST AND BALANCE REPORT.
<br />5 ACCESS DOORS: PROVIDE 18 INCH X 18 INCH (MINIMUM) PAINTED, ALUMINUM ACCESS
<br />DOOR (WITH FULL HINGE AND KEY) FOR ACCESS TO VALVES, EQUIPMENT, AND
<br />ACCESSORIES IN PLASTER, DRYWALL, OR INACCESSIBLE CEILINGS OR IN WALLS. PROVIDE
<br />INSULATED ACCESS DOORS (DO NOT SUBSTITUTE PANELS) IN DUCTWORK FOR ACCESS TO
<br />DAMPERS AND OTHER OPERATING DEVICES (INCLUDING UPSTREAM OF ELECTRIC RESISTANCE
<br />DUCT HEATERS AND AT DUCT MOUNTED SMOKE DETECTORS). GROUP DEVICES AT ON
<br />LOCATION, AS AVAILABLE.
<br />5 AIR DISTRIBUTION:
<br />A. DUCTWORK:
<br />1) TEST (BY FEEL OR TEMPERATURE CHANGE) EACH DUCTWORK SYSTEM FOR
<br />LEAKS BEFORE INSULATING. RESEAL, AS REQUIRED.
<br />2) DUCT DIMENSIONS INDICATE AIR FLOW SIZES.
<br />3) AT CONTRACTOR'S OPTION, EQUAL AREA DUCTWORK HAVING A MAXIMUM 4 TO 1
<br />ASPECT RATIO MAY BE SUBSTITUTED FOR DUCT DIMENSIONS SHOWN.
<br />4) FLEXIBLE DUCTWORK (USED TO CONNECT TO SUPPLY AIR OUTLETS: THERMAFLEX
<br />TYPE M-KE (OR AS APPROVED).
<br />5) BRANCH DUCT CONNECTIONS (POSITIVE AND NEGATIVE PRESSURE): ON
<br />RECTANGULAR DUCTS, PROVIDE VOLUME EXTRACTORS OR 45 DEGREE ENTRIES;
<br />ON CIRCULAR DUCTS, PROVIDE CONICAL TAPS (WITH DAMPERS). PROVIDE THESE
<br />CONNECTIONS ON EACH BRANCH DUCT CONNECTION FOR EACH SYSTEM; DO NOT
<br />SUBSTITUTE "T" CONNECTIONS.
<br />6) INSTALL DUCTWORK AND ACCESSORIES IN ACCORDANCE WITH SMACNA HVAC DUCT
<br />CONSTRUCTION STANDARDS - METAL AND FLEXIBLE.
<br />6 ALL BRANCH TAKE -OFFS TO DIFFUSERS SHALL HAVE BALANCING DAMPERS.
<br />7 MOUNT T'STATS 4'-0" A.F.F.
<br />8 ALL REFRIGERANT LINES SHALL USE LONG RADIUS ELBOWS FOR TURNS, NO BENDS.
<br />9 ALL NEW SA, RA, EA, MA, TA, AND OA DUCTWORK SHALL BE GALVANIZED STEEL WITH 2"
<br />FIBERGLASS DUCT WRAP AND VAPOR BARRIER, OR R=6 FLEX DUCT (THERMAFLEX MKE, OR
<br />AS APPROVED). USE ONLY METALLIC DUCTWORK FOR EXHAUST AIR (EA) DUCTS, PER THE
<br />FBC.
<br />10 PROVIDE TWO (2) SETS OF NEW FILTERS FOR AIR HANDLING UNITS, INSTALL ONE SET
<br />INITIALLY AND ONE SET UPON COMPLETION OF CONSTRUCTION.
<br />11 PROVIDE AND INSTALL TRANE MODEL BAYSTAT040 AUTOMATIC CHANGEOVER, PROGRAMMABLE
<br />HEATING AND COOUNG THERMOSTAT. THE MECHANICAL CONTRACTOR SHALL PROGRAM ALL
<br />THERMOSTATS IN ACCORDANCE WITH THE FOLLOWING SCHEDULE OR AS INSTRUCTED BY
<br />OWNER.
<br />D0Y I1NE COOLING SETPOINT HEATING SETPOINT
<br />MONDAY 5:00 AM 74 DEGREES F 70 DEGREES F
<br />6:00 PM 84 DEGREES F
<br />TUESDAY
<br />6:00
<br />AM
<br />74
<br />DEGREES F
<br />6:00
<br />PM
<br />84
<br />DEGREES F
<br />WEDNESDAY
<br />6:00
<br />AM
<br />74
<br />DEGREES F
<br />6:00
<br />PM
<br />84
<br />DEGREES F
<br />THURSDAY
<br />6:00
<br />AM
<br />74
<br />DEGREES F
<br />6:00
<br />PM
<br />84
<br />DEGREES F
<br />FRIDAY
<br />6:00
<br />AM
<br />74
<br />DEGREES F
<br />7:00
<br />PM
<br />84
<br />DEGREES F
<br />SATURDAY 6:00 AM
<br />74
<br />DEGREES F
<br />7:00 PM
<br />BRANCH BANKS SATURDAY
<br />84
<br />DEGREES F
<br />WITHOUT
<br />OPERATION
<br />DEGREES F
<br />SATURDAY ALL DAY
<br />84
<br />SUNDAY ALL DAY
<br />84
<br />DEGREES F
<br />62 DEGREES F
<br />70 DEGREES F
<br />62 DEGREES F
<br />70 DEGREES F
<br />62 DEGREES F
<br />70 DEGREES F
<br />62 DEGREES F
<br />70 DEGREES F
<br />62 DEGREES F
<br />70 DEGREES F
<br />62 DEGREES F
<br />62 DEGREES F
<br />62 DEGREES F
<br />MECHANICAL LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />®
<br />POSITIVE PRESSURE DUCTWORK (SUPPLY AIR, RELIEF AIR)
<br />NEGATIVE PRESSURE DUCTWORK (RETURN AIR, EXHAUST AIR,
<br />OUTSIDE AIR INTAKE)
<br />NEW DUCT OR DEVICES
<br />\ \ \ \\
<br />/ /
<br />FLEXIBLE DUCTWORK
<br />T
<br />THERMOSTAT (WALL MOUNTED AT 48" A.F.F.)
<br />AIR FLOW: POSITIVE PRESSURE; NEGATIVE PRESSURE
<br />BRANCH DUCT CONNECTION: WITH CONICAL CONNECTION AND DAMPER
<br />OA
<br />AIR OUTLET TYPE (A); 12" CONNECTION SIZE; AND 100 CFM
<br />INDICATED. BRANCH DUCT SIZE MATCHES CONNECTION SIZE,
<br />_
<br />12"
<br />UNLESS NOTED OTHERWISE. THROW: 4 WAY, UNLESS NOTED
<br />100
<br />OTHERWISE.
<br />O
<br />AIR INLET TYPE (N); CONNECTION SIZE; AND MAXIMUM CFM
<br />INDICATED. BRANCH DUCT SIZE MATCHES CONNECTION SIZE,
<br />UNLESS NOTED OTHERWISE.
<br />- U
<br />3/4" DOOR UNDERCUT- COORDINATE WITH ARCHITECTURAL WORK.
<br />MANUAL VOLUME / BALANCING DAMPER
<br />CO2
<br />DUCT MOUNTED CO2 SENSOR
<br />DP
<br />DIFFERENTIAL PRESSURE TRANSMITTER
<br />eAIR
<br />HANDLING UNIT TYPE
<br />CU
<br />0
<br />CONDENSING UNIT TYPE
<br />EF
<br />O
<br />EXHAUST FAN TYPE
<br />ODRAWING
<br />NOTE: REFER TO NOTES ON EACH DRAWING
<br />ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION
<br />BTU BRITISH THERMAL UNIT
<br />LAT LEAVING AIR TEMPERATURE
<br />CFM CUBIC FEET PER MINUTE
<br />LDB LEAVING DRY BULB
<br />DB DRY
<br />BULB
<br />LWB LEAVING WET BULB
<br />ESP EXTERNAL STATIC PRESSURE
<br />MBH THOUSAND BTU PER HOUR
<br />NP TYPICAL
<br />RA RETURN AIR
<br />WB WET
<br />BULB
<br />RH RELATIVE HUMIDITY
<br />SP STATIC PRESSURE
<br />SA SUPPLY AIR
<br />12 THE MECHANICAL
<br />CONTRACTOR
<br />SHALL PROGRAM THE WALL - MOUNTED TIME CLOCKS IN
<br />ACCORDANCE WITH THE
<br />FOLLOWING SCHEDULE OR AS INSTRUCTED BY OWNER.
<br />DAY
<br />IlME
<br />MONDAY
<br />8:00
<br />AM
<br />ON
<br />5:00
<br />PM
<br />OFF
<br />TUESDAY
<br />8:00
<br />AM
<br />ON
<br />5:00
<br />PM
<br />OFF
<br />WEDNESDAY
<br />8:00
<br />AM
<br />ON
<br />5:00
<br />PM
<br />OFF
<br />THURSDAY
<br />8:00
<br />AM
<br />ON
<br />5:00
<br />PM
<br />OFF
<br />FRIDAY
<br />8:00
<br />AM
<br />ON
<br />BRANCH WITH SATURDAY
<br />6:00
<br />PM
<br />OPERATION
<br />OFF
<br />SATURDAY
<br />8:00
<br />AM
<br />ON
<br />BRANCH
<br />5:00
<br />PM
<br />OFF
<br />BANKS
<br />SATURDAY
<br />WITHOUT
<br />SATURDAY
<br />OPERATION
<br />OFF
<br />SUNDAY
<br />OFF
<br />HOLIDAYS
<br />OFF
<br />13 ALL DUCT SIZES ARE ACTUAL SHEET METAL DIMENSIONS.
<br />14 - 59 NOT USED.
<br />60 ROUTE THE SUPPLY AND RETURN DUCT UP TO THE ROOF MOUNTED ACU. REFER TO
<br />DRAWING M1.2.
<br />61 ROUTE THE 12 INCH EXHAUST DUCT UP TO ROOF CAP. REFER TO "EXHAUST FAN
<br />DISCHARGE DETAIL" ON DRAWING M1.2.
<br />62 ROUTE THE 8 INCH EXHAUST DUCT UP TO ROOF CAP. REFER TO "EXHAUST FAN
<br />DISCHARGE DETAIL" ON DRAWING M1.2.
<br />63 PROVIDE A CURB MOUNTED ROOF CAP FOR EF-J. PROVIDE COOK MODEL PR-8.
<br />PROVIDE A MINIMUM OF 10 FEET FROM OUTSIDE AIR INTAKES OF ROOFTOP UNITS.
<br />PROVIDE BACKDRAFT DAMPER (LOW PRESSURE LOSS TYPE) IN NECK AT ROOF CAP.
<br />64 ROUTE A 4 X 12 SUPPLY AIR DUCT DOWN TO OPENING IN VAULT. BALANCE AIRFLOW
<br />TO 100 CFM. TRANSITION TO AN INTERIOR OPENING IN VAULT AND ROUTE TO CEILING
<br />DIFFUSER. COORDINATE WITH ARCHITECTURAL PLANS. COORDINATE THE VAULT DUCT
<br />CONNECTION SIZE AND LOCATION WITH THE VAULT SUPPLIER. TRANSITION, AS REQUIRED.
<br />COORDINATE THE DUCTING WITHIN THE VAULT TO MAINTAIN MAXIMUM CEILING HEIGHT
<br />(TRANSITION, AS REQUIRED).
<br />®5 PROVIDE A CURB MOUNTED ROOF CAP FOR EF W AND M. PROVIDE COOK MODEL PR-12.
<br />PROVIDE A MINIMUM OF 10 FEET FROM OUTSIDE AIR INTAKES OF ROOFTOP UNITS.
<br />PROVIDE BACKDRAFT DAMPER (LOW PRESSURE LOSS TYPE) IN NECK AT ROOF CAP.
<br />66 NOT USED.
<br />67 NOT USED.
<br />6® PROVIDE A ROOF MOUNTED ACU. REFER TO "ROOFTOP UNIT DETAIL" ON DRAWING M1.2.
<br />69 PROVIDE 1 INCH CONDENSATE PIPING. PROVIDE MIRO INDUSTRIES MODEL 1.5 PIPE
<br />SUPPORTS. PROVIDE 4'-0" MAXIMUM SPACING.
<br />OO TERMINATE CONDENSATE DRAINS INTO THE ROOF DRAIN.
<br />MECHANICAL -LEGEND, NOTES, SCHEDULES
<br />SCALE: NONE
<br />Notes:
<br />Revisions:
<br />Seal:
<br />jil AY /r1(�y
<br />Consultants:
<br />0
<br />ARCHITECTURAL ENGINEERING INCORPORATE
<br />3442 EAST LAKE ROAD, PALM HARBOR, FL 3461
<br />CONSULTING ENGINEERS (727) 784-14.
<br />CERTIFICATE OF AUTHORIZATION: FL 3W
<br />W. RONALD MCILVEEN FL PE 3027
<br />�9
<br />r`•
<br />WP- r
<br />I� A
<br />4
<br />40
<br />�Ir� IR •
<br />E L E M E N T S
<br />ARCHITECTS -INTERIOR DESIGNERS
<br />Tampa Office
<br />The Edgewater Building
<br />600 South Magnolia Avenue
<br />Suite 150
<br />Tampa, Florida 33606
<br />Phone (813) 251-0565
<br />Pax (813) 251-0567
<br />Mial n1 Offi -_e
<br />1699 Coral Way suite 503
<br />Miami, Florida 33145
<br />Phone (305) 858-5858
<br />Pax (305) 858-5850
<br />�i.. 7777y,
<br />WACHOVIA
<br />COAST• s
<br />Fa
<br />. .
<br />HERNANDO COUNTY
<br />�A
<br />► _7"-2z =
<br />NECHANCAL
<br />LEGEND,NOTES,SCW-DULES
<br />
|