AIR CONDITIONING UNIT SCHEDULE <br />ACU ACU <br />ACU <br />UNIT NO. T L <br />_ 0 <br />LOCATION ROOF ROOF <br />ROOF <br />SERVICE TELLER LOBBY <br />OFFICE <br />TOTAL COOLING - MIN (MBH) 44 47 <br />48 <br />SENSIBLE COOLING - MIN (MBH) 31- <br />35 <br />- - -34 - <br />SEER IN) 13 13 <br />13 <br />_ 8 66 <br />COIL EAT CDB/WB) 78%66 7--_ <br />- <br />78/66 - <br />HEATING - MIN (MBH) 14 15--- <br />19 _ <br />HEATER KW(AT LISTED VOLTAGE) 9 9 <br />9_ <br />HTR STEPS - MIN 2 2 <br />TOTAL AIR (CFM) 1,600 1,600 <br />1,800 4 <br />OUTSIDE AIR (CFM) 250 250 <br />250 <br />ESP IN WG) 0.9 0.9 <br />- 0.9 - -- <br />RPM -- -- <br />-- <br />BHP - MAX -- -- <br />- - <br />-- <br />- - <br />MOTOR HP 1 1 <br />1 <br />- - - 49/59 49 j9 j60 <br />ELECT <br />49/59/60 - <br />_(FLA/MCA/MOCP) _ <br />ELECT (V/PH/HZ) 208/3/60 208/3/60 <br />20813 60 <br />WEIGHT (LBS) 850 850 - <br />850 <br />MANUFACTURER TRANE TRANE _ <br />TRANE <br />MODEL NO. WSC-048-E WSC-048-E <br />WSC-048-E <br />REMARKS_- j 1-14_ 1--14 <br />-1-14 <br />REMARK NUMBERS: <br />1. NATIONAL SALES CONTRACT: WACHOVIA HAS ENTERED <br />INTO A NATIONAL SALES CONTRACT WITH TRANE. THE <br />GENERAL CONTRACTOR / HVAC SUB -CONTRACTORS <br />SHALL CONTACT BARNEY HIGH, LEED, AP, TRANE <br />NATIONAL ACCOUNT MANAGER AT (704) 529-3295 <br />(TELEPHONE) OR (704) 277-7126 (CELL PHONE) TO <br />PURCHASE AIR CONDITIONING EQUIPMENT SHOWN ON <br />THE DRAWINGS. NO SUBSTITUTIONS SHALL BE <br />ACCEPTED. <br />2. MINIMUM FILTER EFFICIENCIES PER ASHRAE STD. 52-76. <br />3. PROVIDE SINGLE POINT POWER CONNECTION <br />4. PROVIDE FACTORY FABRICATED ROOF CURB TO MATCH ROOF <br />SLOPE. VERIFY ROOF SLOPE WITH ARCHITECTURAL DRAWINGS. <br />5. PROVIDE THROUGH THE BASE ELECTRICAL WITH DICONNECT <br />AND FACTORY POWERED CONVENIENCE OUTLET (ONE PER PROJECT) <br />ALL FINAL ELECTRICAL CONNECTIONS TO EQUIPMENT SHALL <br />BE MADE BY MECHANICAL CONTRACTOR. <br />6. PROVIDE MANUFACTURER'S 7-DAY PROGRAMMABLE, <br />ELECTRONIC NIGHT SETBACK THERMOSTAT (TRANE BAYSTAT050A). <br />7. R-41OA REFRIGERANT. <br />8. FILTERS: 145 FPM FACE VELOCITY; AEROSTAR MERV 13 GREEN <br />PLEAT, <br />(2) 20 x 30 X 2 FILTERS, 0.1 IN. WG. AIR PRESSURE DROP (CLEAN); <br />1.0 IN. WG AIR PRESSURE DROP (DIRTY), 0.24 IN WC AT 375 FPM (MAXIMUM, <br />ACCEPTABLE MANUFACTURERS: FILTRATION GROUP INC. (OR APPROVED). <br />9. EXTERNAL STATIC PRESSURES INCLUDES AN ALLOWANCE FOR DIRTY <br />10. NOT USED. <br />11. NOT USED. <br />12. PRO <br />AIR DEVICE SCHEDULE <br />SYMBOL <br />TYPE <br />MOUNTING <br />FRAME <br />FACE <br />STYLE <br />DAMPER <br />FINISH <br />MANUFACTURER <br />MODEL NO. <br />REMARKS <br />SYMBOL <br />/ MOTORIZED DAMPER. <br />A <br />AIR OUTLET <br />CEILING <br />T-BAR <br />SQUARE PLAQUE <br />MODULAR 24 X 24 <br />OBD <br />OFF-WHITE <br />TITUS <br />OMNI <br />1,2,3 <br />n <br />COIL. <br />C <br />D <br />AIR OUTLET <br />AIR OUTLET <br />CEILING <br />SIDEWALL <br />T-BAR <br />SURFACE <br />TEAR (2) 3/4" SLOTS_ <br />ADJ. DOUBLE_ DEFL. <br />48" LONG W/BOOT <br />NOT MODULAR <br />OBD <br />OBD _ - <br />OFF-WHITE <br />OFF-WHITE_ _ <br />TITUS <br />TITUS <br />ML-38 <br />300FL <br />1,3,5 <br />1,3 <br />Is <br />0 <br />E <br />AIR OUTLET <br />CEILING <br />- - T-BAR <br />SQUARE PLAQUE <br />MODULAR 24 X 24 <br />INTEGRAL <br />OFF-WHITE_ <br />TITUS _ <br />TS3Q-4 <br />1,3,4 <br />TYPE <br />AIR INLET <br />AIR INLET <br />MOUNTING <br />CEILING <br />SIDEWALL <br />FRAME <br />T-BAR <br />SURFACE <br />FACE <br />SQUARE PLAQUE <br />BAR <br />STYLE <br />MODULAR 24 X 24 <br />NOT MODULAR <br />DAMPER <br />NONE <br />NONE <br />FINISH <br />OFF-WHITE <br />OFF-WHITE - - <br />MANUFACTURER <br />TITUS <br />TITUS - - - <br />MODEL NO. <br />OMNI <br />350FL <br />REMARKS <br />1,3 <br />1,3 <br />REMARK NUMBERS: <br />1. REFER TO DRAWING <br />FOR NECK SIZES. <br />2. FOUR WAY BLOW <br />UNLESS OTHERWISE INDICATED <br />ON DRAWING. PROVIDE INSULATED BACKPAN. <br />3. PROVIDE FLEXIBLE <br />DUCT CONNECTION SIZED AT <br />NECK SIZE OF AO. <br />4. SELF POWERED VAV DIFFUSER: COOLING SETPOINT 70 DEGREES, HEATING SETPOINT 72 DEGREES. <br />5. PROVIDE FACTORY <br />INSULATED PLENUM. <br />6. ACCEPTABLE MANUFACTURERS: TITUS, CARNES, KRUEGER, NAILER AND PRICE. <br />EXHAUST FAN SCHEDULE <br />EF <br />EF EF <br />EF <br />EF <br />UNIT NO. <br />M <br />W J <br />TF1 <br />TF2 <br />LOCATION <br />CEILING <br />CEILING CEILING <br />CEILING <br />CEILING <br />SERVICE <br />MEN <br />WOMEN JAN <br />ATM ROOM <br />_ <br />TELE/DATA <br />TOTAL AIR (CFM) <br />75 <br />90 75 <br />- <br />280 <br />580 <br />!ESP (IN WG) <br />0.25 <br />0.25 0.25 <br />0.25--__ <br />0.25 <br />;SOUND -MAX (BONES) <br />3 <br />3 3 <br />_ <br />3 <br />- <br />1.2 <br />RPM <br />1,200 <br />1,200 1,200 <br />- - <br />1,200 <br />-- <br />1,375 <br />'MOTOR HP OR WATTS <br />65W <br />65W 65W <br />172W <br />301 W <br />I ELECT (FLA/MCA/MOCP) <br />-- -- <br />- - <br />- <br />- <br />- <br />� ELECT (V/PH/HZ) <br />120/1 /60 <br />120/1 /60 120/1 /60 <br />120/1 /6-0 - <br />- <br />120/1_%60 <br />-40- <br />WEIGHT (LBS) <br />30 <br />30 30 <br />40 <br />MANUFACTURER <br />COOK <br />COOK COOK <br />COOK <br />COOK <br />MODEL NO. <br />GC-240 <br />GC-240 GC-240 <br />GC-520 <br />GC 720 <br />REMARKS <br />1,2,4 <br />1,2,4 1,4,5 <br />- <br />1,3,4 <br />1,3,4 <br />REMARK NUMBERS: <br />'1. CENTRIFUGAL IN -LINE CEILING FAN, DIRECT DRIVE, BACKDRAFT DAMPER, <br />PLUG-IN MOTOR SERVES AS DISCONNECT, ADJUSTABLE MOTOR SPEED <br />CONTROLLER (FOR T&B). <br />2. PROVIDE 365-DAY DIGITAL, PROGRAMMABLE TIME CLOCK, INTERMATIC MODEL ET70115C OR EQUAL. <br />3. PROVIDE WALL MOUNTED LINE VOLTAGE HIGH LIMIT COOLING THERMSTAT SET AT 80 DEGREES F. <br />14. ACCEPTABLE MANUFACTURERS: COOK, CARNES AND GREENHECK. <br />j5. PROVIDE 6 HR. MECHANICAL TIME (MARKTIME 93505) ADJACENT TO SPEED CONTROLLER <br />TO TURN FAN ON. <br />MECHANICAL (HVAC) NOTES: <br />1 A. REGULATORY REQUIREMENTS: PROVIDE ALL WORK TO MEET OR EXCEED MINIMUM <br />REGULATORY REQUIREMENTS INCLUDING: <br />FLORIDA BUILDING CODE: 2004 EDITION WITH 2O06 SUPPLEMENT <br />FLORIDA FIRE PREVENTION CODE: 2006 EDITION <br />ADVISE THE ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS THAT MAY BE <br />REQUIRED IN ORDER TO MEET CODE, PRIOR TO WORK (ORDERING, ROUGHING OR <br />INSTALLING). <br />B. COORDINATION: COORDINATE WITH OTHER WORK (INCLUDING ELECTRICAL, AND <br />ARCHITECTURAL) FOR AVAILABLE SPACE, SEQUENCE OF INSTALLATION, AND <br />INSTALLATION REQUIREMENTS, PRIOR TO COMMENCING CONSTRUCTION. ADVISE THE <br />ARCHITECT OF ANY CHANGES IN THE CONTRACT DOCUMENTS THAT MAY BE REQUIRED <br />FOR THE WORK TO BE PERFORMED. <br />C. EXISTING FIELD CONDITIONS: THE CONTRACT DOCUMENTS INDICATE THE DESIGN <br />INTENT USING AVAILABLE INFORMATION. THE CONTRACTOR IS TO ADVISE THE <br />ARCHITECT IF EXISTING CONDITIONS DIFFER FROM THOSE SHOWN. ALSO ADVISE THE <br />ARCHITECT IF CODE OR SAFETY CONFLICTS EXIST. THE CONTRACTOR IS REQUIRED TO <br />INSPECT THE SITE (PRIOR TO BID) TO BECOME FAMILIAR WITH CONDITIONS AND <br />INSTALLATION DETAILS THAT WILL AFFECT HIS WORK. CHANGES IN THE CONTRACT <br />SUM AND CONTRACT TIME WILL NOT BE ALLOWED FOR FAILURE TO INVESTIGATE FIELD <br />CONDITIONS. ALL WORK IS NEW, UNLESS NOTED OTHERWISE. <br />D. DEVICE LOCATIONS: REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF <br />AIR OUTLETS, AIR INLETS, AND OTHER CEILING ITEMS (TO AVOID CONFLICTS). LOCATE <br />ALL PIPING AND DUCTWORK IN FINISHED ROOMS OR SPACES WITHIN CONCEALED <br />LOCATIONS (FURRED CHASES OR SUSPENDED CEILINGS, AS AVAILABLE). DO NOT <br />LOCATE PIPING OR DUCTWORK ABOVE ELECTRICAL SWITCHBOARDS OR PANELBOARDS. <br />E. SIZES: WHEN A PIPE OR A DUCT SIZE IS NOT INDICATED, SIZE THAT PIPE OR DUCT <br />USING THE LARGER ADJACENT UPSTREAM SIZE, UNLESS A SMALLER SIZE IS APPROVED <br />BY THE ARCHITECT. PROVIDE 3/4 INCH MINIMUM PIPE SIZE, UNLESS SPECIFICALLY <br />NOTED OTHERWISE. FOR SIZES NOT INDICATED ON PLANS, REFER TO EQUIPMENT <br />DETAILS, FLOW DIAGRAMS, RISER DIAGRAMS, AND OTHER LOCATIONS IN THE CONTRACT <br />DOCUMENTS (DRAWINGS AND SPECIFICATIONS) FOR INFORMATION. <br />F. BASIS OF DESIGN: THE MECHANICAL CONTRACT DOCUMENTS HAVE BEEN PREPARED <br />USING THE FOLLOWING DATA IN THE CALCULATIONS (SIMPLIFIED FOR PRESENTATION <br />HERE): <br />INDOOR OUTDOOR <br />SUMMER 75 DB/50% RH 92 DB/79 WB <br />WINTER 72 DB 40 DB <br />G. PRIOR TO ROUGHING OR ORDERING, VERIFY ADEQUATE CLEARANCES FOR DUCTWORK, <br />OTHER WORK, ELECTRICAL CONDUITS AND LIGHTING. <br />2 SCOPE OF WORK: <br />A. PROVIDE NEW ROOFTOP UNITS, DUCTWORK, CEILING EXHAUST FANS AND ACCESSORIES. <br />B. PROVIDE NEW AHU'S, CU'S, EF'S, CEILING AIR DEVICES, AND ASSOCIATED DUCTWORK, <br />AS SHOWN. <br />C. T&B: <br />1) T&B NEW ACU, EF, DIFFUSERS, AND DAMPERS, AND PROVIDE FINAL T&B REPORT <br />3 PROVIDE ALL NECESSARY FEES AND PERMITS. REVIEW OPERATION OF EACH SYSTEM WITH <br />OWNER'S REPRESENTATIVE. PROVIDE ONE YEAR WARRANTY ON ENTIRE SYSTEM. PROVIDE <br />RECORD DRAWING (CONTRACTOR FURNISHED PRINT). SUBMITTALS: SUBMIT PRODUCT DATA <br />FOR EACH NEW MECHANICAL DEVICE AND TEST AND BALANCE REPORT. <br />5 ACCESS DOORS: PROVIDE 18 INCH X 18 INCH (MINIMUM) PAINTED, ALUMINUM ACCESS <br />DOOR (WITH FULL HINGE AND KEY) FOR ACCESS TO VALVES, EQUIPMENT, AND <br />ACCESSORIES IN PLASTER, DRYWALL, OR INACCESSIBLE CEILINGS OR IN WALLS. PROVIDE <br />INSULATED ACCESS DOORS (DO NOT SUBSTITUTE PANELS) IN DUCTWORK FOR ACCESS TO <br />DAMPERS AND OTHER OPERATING DEVICES (INCLUDING UPSTREAM OF ELECTRIC RESISTANCE <br />DUCT HEATERS AND AT DUCT MOUNTED SMOKE DETECTORS). GROUP DEVICES AT ON <br />LOCATION, AS AVAILABLE. <br />5 AIR DISTRIBUTION: <br />A. DUCTWORK: <br />1) TEST (BY FEEL OR TEMPERATURE CHANGE) EACH DUCTWORK SYSTEM FOR <br />LEAKS BEFORE INSULATING. RESEAL, AS REQUIRED. <br />2) DUCT DIMENSIONS INDICATE AIR FLOW SIZES. <br />3) AT CONTRACTOR'S OPTION, EQUAL AREA DUCTWORK HAVING A MAXIMUM 4 TO 1 <br />ASPECT RATIO MAY BE SUBSTITUTED FOR DUCT DIMENSIONS SHOWN. <br />4) FLEXIBLE DUCTWORK (USED TO CONNECT TO SUPPLY AIR OUTLETS: THERMAFLEX <br />TYPE M-KE (OR AS APPROVED). <br />5) BRANCH DUCT CONNECTIONS (POSITIVE AND NEGATIVE PRESSURE): ON <br />RECTANGULAR DUCTS, PROVIDE VOLUME EXTRACTORS OR 45 DEGREE ENTRIES; <br />ON CIRCULAR DUCTS, PROVIDE CONICAL TAPS (WITH DAMPERS). PROVIDE THESE <br />CONNECTIONS ON EACH BRANCH DUCT CONNECTION FOR EACH SYSTEM; DO NOT <br />SUBSTITUTE "T" CONNECTIONS. <br />6) INSTALL DUCTWORK AND ACCESSORIES IN ACCORDANCE WITH SMACNA HVAC DUCT <br />CONSTRUCTION STANDARDS - METAL AND FLEXIBLE. <br />6 ALL BRANCH TAKE -OFFS TO DIFFUSERS SHALL HAVE BALANCING DAMPERS. <br />7 MOUNT T'STATS 4'-0" A.F.F. <br />8 ALL REFRIGERANT LINES SHALL USE LONG RADIUS ELBOWS FOR TURNS, NO BENDS. <br />9 ALL NEW SA, RA, EA, MA, TA, AND OA DUCTWORK SHALL BE GALVANIZED STEEL WITH 2" <br />FIBERGLASS DUCT WRAP AND VAPOR BARRIER, OR R=6 FLEX DUCT (THERMAFLEX MKE, OR <br />AS APPROVED). USE ONLY METALLIC DUCTWORK FOR EXHAUST AIR (EA) DUCTS, PER THE <br />FBC.- <br />10 PROVIDE TWO (2) SETS OF NEW FILTERS FOR AIR HANDLING UNITS, INSTALL ONE SET <br />INITIALLY AND ONE SET UPON COMPLETION OF CONSTRUCTION. <br />11 PROVIDE AND INSTALL TRANE MODEL BAYSTAT040 AUTOMATIC CHANGEOVER, PROGRAMMABLE <br />HEATING AND COOLING THERMOSTAT. THE MECHANICAL CONTRACTOR SHALL PROGRAM ALL <br />THERMOSTATS IN ACCORDANCE WITH THE FOLLOWING SCHEDULE OR AS INSTRUCTED BY <br />OWNER. <br />DAY ilmE COOLING SETPOINT HEATING SETPOINT <br />MONDAY 5:00 AM 74 DEGREES F 70 DEGREES F <br />6:00 PM 84 DEGREES F 62 DEGREES F <br />TUESDAY 6:00 AM 74 DEGREES F 70 DEGREES F <br />6:00 PM 84 DEGREES F 62 DEGREES F <br />WEDNESDAY 6:00 AM 74 DEGREES F 70 DEGREES F <br />6:00 PM 84 DEGREES F 62 DEGREES F <br />THURSDAY 6:00 AM 74 DEGREES F 70 DEGREES F <br />6:00 PM 84 DEGREES F 62 DEGREES F <br />FRIDAY 6:00 AM 74 DEGREES F 70 DEGREES F <br />7:00 PM 84 DEGREES F 62 DEGREES F <br />BRANCH WITH SATURDAY OPERATION <br />SATURDAY 6:00 AM 74 DEGREES F 70 DEGREES F <br />7:00 PM 84 DEGREES F 62 DEGREES F <br />BRANCH BANKS WITHOUT SATURDAY OPERATION <br />SATURDAY ALL DAY 84 DEGREES F 62 DEGREES F <br />SUNDAY ALL DAY 84 DEGREES F 62 DEGREES F <br />MECHANICAL LEGEND <br />SYMBOL <br />DESCRIPTION <br />® <br />POSITIVE PRESSURE DUCTWORK (SUPPLY AIR, RELIEF AIR) <br />NEGATIVE PRESSURE DUCTWORK (RETURN AIR, EXHAUST AIR, <br />OUTSIDE AIR INTAKE) <br />NEW DUCT OR DEVICES <br />\\\\ \ <br />/ <br />FLEXIBLE DUCTWORK <br />T <br />THERMOSTAT (WALL MOUNTED AT 48" A.F.F.) <br />�► <br />AIR FLOW: POSITIVE PRESSURE; NEGATIVE PRESSURE <br />BRANCH DUCT CONNECTION: WITH CONICAL CONNECTION AND DAMPER <br />O <br />AIR OUTLET TYPE (A); 12" CONNECTION SIZE; AND 100 CFM <br />INDICATED. BRANCH DUCT SIZE MATCHES CONNECTION SIZE, <br />AL� 12" <br />UNLESS NOTED OTHERWISE. THROW: 4 WAY, UNLESS NOTED <br />100 <br />OTHERWISE. <br />O <br />AIR INLET TYPE (N); CONNECTION SIZE; AND MAXIMUM CFM <br />INDICATED. BRANCH DUCT SIZE MATCHES CONNECTION SIZE, <br />UNLESS NOTED OTHERWISE. <br />- U -- <br />3/4" DOOR UNDERCUT- COORDINATE WITH ARCHITECTURAL WORK. <br />MANUAL VOLUME / BALANCING DAMPER <br />CO2 <br />DUCT MOUNTED CO2 SENSOR <br />DP <br />DIFFERENTIAL PRESSURE TRANSMITTER <br />AC <br />0 <br />AIR CONDITIONING UNIT TYPE <br />EF <br />0 <br />EXHAUST FAN TYPE <br />ODRAWING <br />NOTE: REFER TO NOTES ON EACH DRAWING <br />ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION <br />BTU BRITISH <br />THERMAL UNIT <br />LAT LEAVING AIR TEMPERATURE <br />CFM CUBIC <br />FEET PER MINUTE <br />LDB LEAVING DRY BULB <br />DB DRY BULB <br />LWB LEAVING WET BULB <br />ESP EXTERNAL STATIC PRESSURE <br />MBH THOUSAND BTU PER HOUR <br />TYP TYPICAL <br />RA RETURN AIR <br />WB WET BULB <br />RH RELATIVE HUMIDITY <br />SP STATIC <br />PRESSURE <br />SA SUPPLY AIR <br />12 <br />THE MECHANICAL CONTRACTOR <br />SHALL PROGRAM THE WALL - MOUNTED TIME CLOCKS IN <br />ACCORDANCE <br />WITH THE FOLLOWING SCHEDULE OR AS INSTRUCTED BY OWNER. <br />DAY <br />IlbM.E <br />MONDAY <br />8:00 AM <br />ON <br />5:00 PM <br />OFF <br />TUESDAY <br />8:00 AM <br />ON <br />5:00 PM <br />OFF <br />WEDNESDAY <br />8:00 AM <br />ON <br />5:00 PM <br />OFF <br />THURSDAY <br />8:00 AM <br />ON <br />5:00 PM <br />OFF <br />FRIDAY <br />8:00 AM <br />ON <br />BRANCH <br />6:00 PM <br />SATURDAY <br />OFF <br />WITH <br />SATURDAY <br />OPERATION <br />8:00 AM <br />ON <br />5:00 PM <br />OFF <br />BRANCH BANKS <br />WITHOUT SATURDAY <br />OPERATION <br />SATURDAY <br />OFF <br />SUNDAY <br />OFF <br />HOLIDAYS OFF <br />13 <br />ALL DUCT SIZES ARE ACTUAL <br />SHEET METAL DIMENSIONS. <br />14 <br />- 59 <br />NOT USED. <br />60 <br />ROUTE THE <br />SUPPLY AND RETURN DUCT UP TO THE ROOF MOUNTED ACU. REFER TO <br />DRAWING M 1.2. <br />61 <br />ROUTE THE <br />12 INCH EXHAUST <br />DUCT UP TO ROOF CAP. REFER TO "EXHAUST FAN <br />DISCHARGE <br />DETAIL" ON DRAWING M 1.2. <br />62 <br />ROUTE THE <br />8 INCH EXHAUST <br />DUCT UP TO ROOF CAP. REFER TO "EXHAUST FAN <br />DISCHARGE <br />DETAIL" ON DRAWING M 1.2. <br />63 <br />PROVIDE A <br />CURB MOUNTED ROOF CAP FOR EF-J. PROVIDE COOK MODEL PR-8. <br />PROVIDE A <br />MINIMUM OF 10 FEET FROM OUTSIDE AIR INTAKES OF ROOFTOP UNITS. <br />PROVIDE BACKDRAFT DAMPER <br />(LOW PRESSURE LOSS TYPE) IN NECK AT ROOF CAP. <br />NOT USED. <br />/ <br />L <br />65 PROVIDE A CURB MOUNTED ROOF CAP FOR EF W AND M. PROVIDE COOK MODEL PR-12. <br />PROVIDE A MINIMUM OF 10 FEET FROM OUTSIDE AIR INTAKES OF ROOFTOP UNITS. <br />PROVIDE BACKDRAFT DAMPER (LOW PRESSURE LOSS TYPE) IN NECK AT ROOF CAP. <br />66 NOT USED. <br />67 NOT USED. <br />PROVIDE A ROOF MOUNTED ACU. REFER TO "ROOFTOP UNIT DETAIL" ON DRAWING M 1.2. <br />69 PROVIDE 1 INCH CONDENSATE PIPING. PROVIDE MIRO INDUSTRIES MODEL 1.5 PIPE <br />SUPPORTS. PROVIDE 4'-0" MAXIMUM SPACING. <br />O TERMINATE CONDENSATE DRAINS INTO THE ROOF DRAIN. <br />OWNER <br />REVISIONS <br />07/17/09 <br />® <br />OWNER <br />REVISIONS <br />08/10/09 <br />ARCHITECTURAL ENGINEERING INCORPORATED <br />3442 EAST LAKE ROAD, PALM HARBOR, FL 34685 <br />CONSULTING ENGINEERS (727) 784-1472 <br />CERTIFICATE OF AUTHORIZATION: FL 3886 <br />W. RONALD MCILVEEN FL PE 30270 <br />ELEMENTS State License #, AAC),0023,41 <br />WACHOVIA --- ZEPHYR COIMIVO �S <br />PAA� CEL 6 <br />UIS RO�JTE 301 <br />ZEPHYRHiLLS, FLORIDA <br />Dro inn No/`Dlotee 02053,09 <br />m� <br />Drawing :i': w:e tr� � SCole 'Drawn by THr,�., <br />MECHANICAi <br />LECEND,N0TE'S,SC ED) U L'S <br />SCALE": NONE <br />