<br />ELECTRICAL SPECIFICATIONS
<br />I. THE WORK SUBJECT TO THESE SPECIFICATIONS SHALL BE IN CONFORMANCE WITH THE LATEST
<br />EDITION OF THE NATIONAL ELECTRICAL CODE. THE INSTALLATION SHALL ALSO COMPLY WITH ALL
<br />APPLICABLE RULES AND REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES.
<br />2. ALL ELECTRICAL EQUIPMENT SHALL BE SPECIFICATION GRADE AND SHALL HAVE THE PROPER UL
<br />LABEL.
<br />3. POWER DISTRIBUTION HOUSE PANEL50ARD PROVIDE DEAD -FRONT,
<br />SAFETY -TYPE POWER DISTRIBUTION PANELBOARDS AS INDICATED WITH SWITCHING AND
<br />PROTECTIVE DEVICES IN QUANTITIES, RATINGS, TYPES, AND WITH ARRANGEMENT SHOWN. INCLUDE
<br />ANTI -TURN, SOLDERLESS PRESSURE TYPE MAIN LUG CONNECTORS APPROVED FOR USE WITH
<br />COPPER CONDUCTORS.
<br />4. HOUSE PANELBOARD IS EXISTING AND IS EQUAL TO SQUARE D TYPE "NQOD". VOLTAGE SHALL BE
<br />AS INDICATED. ACCEPTABLE MANUFACTURERS INCLUDE GENERAL ELECTRIC, SIEMENS AND
<br />CUTLER -HAMMER
<br />5. TENANT PANELBOARDS PROVIDE DEAD -FRONT SAFETY TYPE LIGHTING AND BRANCH CIRCUIT
<br />PANELBOARDS AS INDICATED WITH SWITCHING AND PROTECTIVE DEVICES- IN QUANTITIES, RATINGS,
<br />TYPES AND ARRANGEMENTS SHOWN. INCLUDE ANTI -TURN, SOLDERLESS PRESSURE TYPE LUG
<br />CONNECTORS APPROVED FOR USE WITH COPPER CONDUCTORS.
<br />6. TENANT PANELBOARDS SHALL BE SQUARE D TYPE =00s. PANEL50ARD BOXES SHALL BE FIVE
<br />AND THREE -FOURTHS INCHES (5-3/4") DEEP. VOLTAGE SHALL BE AS INDICATED.
<br />1. ALL PANEL50ARDS SHALL BE CONNECTED, DISTRIBUTED PHASE, WITH CIRCUIT NUMBERING AS
<br />INDICATED ON THE DRAWINGS. PANELBOARDS SHALL
<br />BE NUMBERED WITH ODD NUMBERS ON THE LEFT SIDE OF THE PANEL AND EVEN NUMBERS ON THE
<br />RIGHT SIDE OF THE PANEL..
<br />6. UNLESS OTHERWISE INDICATED, PROTECTIVE DEVICES SHALL BE MOUNTED WITH TOP OF CABINET
<br />OR ENCLOSURE 6'-b" ABOVE FINISHED FLOOR, SHALL BE PROPERLY ALIGNED, AND SHALL BE
<br />ADEQUATELY SUPPORTED INDEPENDENTLY OF THE CONNECTING RACEWAYS. ANY AND ALL STEEL
<br />FRAMING, SHAPES, ETC., NECESSARY FOR THE SUPPORT OF THE EQUIPMENT SHALL BE FURNISHED
<br />AND INSTALLED BY THE CONTRACTOR WHERE THE BUILDING STRUCTURE IS NOT SUITABLE FOR
<br />MOUNTING THE EQUIPMENT DIRECTLY THEREON. UNLESS OTHERWISE INDICATED, ALL BRANCH
<br />CIRCUIT PROTECTIVE DEVICE ENCLOSURES SHALL BE NEMA TYPE I, GENERAL PURPOSE TYPE.
<br />CIRCUIT PROTECTIVE DEVICES INSTALLED OUTDOORS OR EXPOSED TO THE WEATHER SHALL
<br />HAVE WEATHERPROOF ENCLOSURES, NEMA TYPE =3R= OR TYPE =4=.
<br />S. ALL SAFETY SWITCHES SHALL BE GENERAL DUTY TYPE. SWITCH MECHANISM SHALL BE
<br />QUICK -MAKE, QUICK -BREAK COVERS SHALL BE INTERLOCKED WITH
<br />MECHANISM TO PREVENT OPENING UNLESS SWITCH IS IN THE "OFF" POSITION. ALL ENCLOSURES
<br />SHALL BE PRIMED AND FINISHED TO RESIST RUSTING AND CORROSION. SWITCHES SHALL BE
<br />SQUARE-D, SIEMENS, GENERAL ELECTRIC OR CUTLER -HAMMER
<br />10. CIRCUIT BREAKERS FOR MOUNTING IN HOUSE PANELBOARD SHALL BE BOLT -ON TYPE, MOLDED
<br />PLASTIC CASE, AIR CIRCUIT BREAKER TYPE. BREAKERS SHALL HAVE THERMAL MAGNETIC TRIP
<br />UNITS AND MULTI -POLE BREAKERS SHALL HAVE A COMMON TRIP BAR SO THAT THE TRIPPING OF
<br />ONE POLE WILL AUTOMATICALLY TRIP ALL POLES OF THE BREAKER BREAKERS SHALL BE TRIP
<br />FREE AND TRIP INDICATING AND SHALL HAVE QUICK -MAKE, QUICK -BREAK CONTACTS.
<br />II. UPON COMPLETION OF WORK CORRECT ALL PANELBOARD CIRCUIT DIRECTORY CARDS TO
<br />REFLECT AS -BUILT CONDITIONS. PANELBOARD DIRECTORIES SHALL BE UPDATED WITH
<br />TYPEWRITTEN ACCURATE AND CURRENT INFORMATION BY THE CONTRACTOR AT THE END OF
<br />CONSTRUCTION. DIRECTORIES SHALL REFLECT RECORD CONDITIONS AND INCLUDE CIRCUIT
<br />NUMBER, TYPE AND LOCATION OF LOAD. A SET OF AS -BUILT DRAWINGS SHALL ALSO BE
<br />PREPARED AND TURNED OVER TO THE OWNER
<br />12. UNLESS SPECIFICALLY NOTED ON DRAWINGS, RACEWAYS SHALL COMPLY WITH THE FOLLOWING
<br />RACEWAYS EXPOSED TO THE WEATHER OR IN DAMP LOCATIONS
<br />SHALL BE GALVANIZED RIGID STEEL WITH THREADED CONNECTIONS.
<br />RACEWAYS SHALL BE SIZED FOR THE CONDUCTORS INSTALLED BUT A MINIMUM
<br />1/2". FULL SIZE MC CABLE IS ACCEPTABLE IN DRY LOCATIONS. HOMER INS TO
<br />PANELS SHALL BE IN CONDUIT.
<br />13. RACEWAYS RUN BELOW GRADE SHALL BE RIGID STEEL CONDUIT WITH A REDUNDANT GROUND
<br />PATH INCLUDED. RACEWAYS RUN EXPOSED ON BUILDING EXTERIOR SHALL BE RIGID STEEL
<br />CONDUIT.
<br />14. ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE AT ALL JOINTS
<br />AND AT ALL BOXES, CABINETS, FITTINGS, AND EQUIPMENT.
<br />15. ALL RACEWAYS SHALL BE SECURELY SUPPORTED FROM THE BUILDING STRUCTURE.
<br />16. ALL RACEWAYS SHALL BE PROVIDED WITH AN EQUIPMENT GROUND CONDUCTOR
<br />11. ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH SUITABLE SCREW
<br />FASTENED COVERS. OPEN KNOCK -OUTS OR HOLES IN BOXES SHALL BE PLUGGED WITH A
<br />SUITABLE BLANKING DEVICE.
<br />Ia. OUTLET BOXES FOR EXPOSED WALL MOUNTING AND OUTDOOR INSTALLATION SHALL BE CAST
<br />METAL TYPE "FS" OR 'TV" BOXES WITH SUITABLE GALVANIZED SHEET STEEL COVERS, OR CAST
<br />METAL WEATHERPROOF OR VAPOR TIGHT COVERS WHEN NOTED ON THE DRAWINGS.
<br />19. UNLESS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER NO. 12 AM. MINIMUM OR SIZE
<br />AS SHOWN ON DRAWINGS. CONDUCTORS SHALL HAVE TYPE "THHN/THWN' INSULATION.
<br />20. SPLICES, TAPS AND ATTACHMENT FITTINGS AND LUGS SHALL BE ELECTRICALLY AND
<br />MECHANICALLY SECURE AND SOLDERLESS FOR CONDUCTORS SIZES NO. 8 AUG AND LARGER
<br />THERE SHALL BE PLENTY OF SLACK CABLE IN BOXES, OUTLETS AND CABINETS TO INSURE THAT
<br />THERE IS NO BINDING AT T14E BUSHINGS. ALL LUGS SHALL BE OF THE CORRECT SIZE FOR THE
<br />CONDUCTORS INSTALLED AND IN NO CASE SHALL STRANDS BE CUT FROM A CONDUCTOR IN
<br />ORDER TO FIT THE CONDUCTOR INTO A LUG. TAPING OF JOINTS SHALL BE WITH VINYL PLASTIC
<br />ELECTRICAL TAPE TO INSURE INSULATION STRENGTH EQUAL TO THAT OF THE CONDUCTORS JOINED.
<br />21. THE INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS
<br />REQUIRED BY THE NEC AND AS SPECIFIED HEREINAFTER
<br />22. CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS.
<br />23. THE CONTRACTOR SHALL VERIFY ALL LOCATIONS WITH THE OWNER PRIOR TO INSTALLATION. THEY
<br />SHALL NOT BE CHARSED FOR MINOR LOCATION CHANGES PRIOR TO INSTALLATIONS. LOCATIONS
<br />ARE APPROXIMATE. (DO NOT SCALE DRAWINGS).
<br />24, THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL ELECTRICAL LAYOUTS FOR BIDDING
<br />PURPOSES ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PREPARE DETAILED SHOP
<br />DRAWINGS AND CONFIRM SPACE ALLOCATIONS.
<br />25. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES
<br />FOR ELECTRICAL CONDUIT ROUTING AND EQUIPMENT PLACEMENT. AVOID INTERFERENCE WITH
<br />ARCHITECTURAL AND STRUCTURAL FEATURES SUCH AN BEAMS, FOOTINGS, WINDOWS, ETC. NOTIFY
<br />ARCHITECT IMMEDIATELY OF ANY CONFLICTS.
<br />26. THE ELECTRICAL CONTRACTOR, THE HVAC FOREMAN AND THE GENERAL CONTRACTOR PROJECT
<br />MANAGER SHALL INSPECT AND REVIEW THE CONDITIONS, AND SHALL COORDINATE THEIR WORK
<br />SO AS TO PROVIDE ADEQUATE SPACE ALLOWANCE ABOVE CEILING FOR ALL TRADES.
<br />21. THE PLANS SHOW THE LOCATION OF ALL FIXTURES AND EQUIPMENT AND ARE INTENDED TO
<br />DEPICT THE GENERAL INTENT OF THE WORK IN SCOPE, LAYOUT AND QUALITY OF WORKMANSHIP.
<br />THEY ARE NOT INTENDED TO SHOW IN MINUTE DETAIL EVERY AND ALL ACCESSORY INTENDED FOR
<br />THE PURPOSE OF EXECUTION OF THE WORK, BUT SHALL BE UNDERSTOOD THAT SUCH DETAILS WILL
<br />BE PART OF THIS WORK
<br />26, THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE
<br />AND FUNCTIONAL ELECTRICAL SYSTEM INCLUDING CONTROLS AND CONNECTIONS TO NEW
<br />SERVICES, SUPPORTS, AND HARDWARE REQUIRED FOR THE SATISFACTORY OPERATION OF THE
<br />SYSTEM, WHETHER SPECIFICALLY SHOWN OR NOT ON THE DRAWINGS.
<br />N
<br />N
<br />SYMBOL LIST
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />®
<br />1'x4' FLOORESCENT FIXTURE
<br />SEE FIXTURE
<br />SCHEDULE
<br />2'x4' FLOORESCENT FIXTURE
<br />SEE FIXTURE
<br />SCHEDULE
<br />SHADED FIXTURES CONTAIN
<br />SEE FIXTURE
<br />BATTERY PACK
<br />SCHEDULE
<br />F0-1
<br />FLUORESCENT STRIP FIXTURE
<br />SEE FIXTURE
<br />SCHEDULE
<br />LIGHT FIXTURE, WALL BRACKET
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />®LIGHT
<br />FIXTURE, CEILING TYPE
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />® B
<br />EXIT FIXTURE, SHADING INDICATES
<br />SEE FIXTURE
<br />SINGLE OR DOUBLE FACE
<br />SCHEDULE
<br />4p
<br />EXIT LIGHT WITH EMERGENCY
<br />SEE FIXTURE
<br />I�
<br />LIGHTS
<br />SCHEDULE
<br />EMERGENCY BATTERY UNIT
<br />SEE FIXTURE
<br />SCHEDULE
<br />S
<br />SWITCH, SINGLE POLE -LETTER
<br />46" AFF TO CL
<br />INDICATES LIGHTS CONTROLLED
<br />OR AS NOTED
<br />SWITCH, THREE WAY
<br />4a" AFF TO CIL
<br />$
<br />OR AS NOTED
<br />DIGITAL SWITCH OR AS
<br />+48" AFF OR AS
<br />NOTED
<br />NOTED
<br />0
<br />WALL -MOUNTED OCCUPANCY
<br />+48" AFF OR AS
<br />SENSOR
<br />NOTED
<br />®CEILING
<br />MOUNTED OCCUPANCY
<br />SURFACE MOUNT
<br />SENSOR
<br />TO CEILING
<br />INSTALL CONCEALED
<br />LR
<br />LIGHTING RELAY
<br />IN AN ACCESSIBLE
<br />AREA ABOVE CEILING
<br />INSTALL CONCEALED
<br />Ea
<br />POWER PACK
<br />IN AN ACCESSIBLE
<br />AREA ABOVE CEILING
<br />®
<br />PHOTOCELL
<br />SURFACE MOUNT
<br />TO CEILING
<br />IG�
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />15" AM TO CL
<br />WITH ISOLATED GROUND
<br />OR AS NOTED
<br />DUPLEX RECEPTACLE, 125V, 15A
<br />IS" AFF OR AS
<br />NOTED
<br />DUPLEX RECEPTACLE, 125V, 15A
<br />44" AFF OR 6"
<br />ABOVE COUNTER
<br />GFI�
<br />DUPLEX RECEPTACLE, 125V, 15A
<br />18" AFF OR AS
<br />GROUND FAULT
<br />NOTED
<br />GF I�
<br />DUPLEX RECEPTACLE, 125V, 15A
<br />44" AFF OR 6
<br />ABOVE COUNTER
<br />DUPLEX RECEPTACLE, 125V, 15A
<br />INFLUSH FLOOR
<br />QUADRAPLEX RECEPTACLE, 125V, 15A
<br />16" AFF OR AS
<br />NOTED
<br />QUADRAPLEX RECEPTACLE, 125V, 15A
<br />44" AFF OR 6"
<br />ABOVE COUNTER
<br />m
<br />TELEPHONE/DATA OUTLET. SEE
<br />18" AFF OR AS
<br />PLANS FOR WIRING CONFIGURATION
<br />NOTED
<br />FH
<br />TELEVISION OUTLET
<br />16" AFF OR
<br />AS NOTED
<br />PANEL50ARD 1201206V
<br />SEE PANEL
<br />-
<br />OR 120/240V
<br />SCHEDULE
<br />Sn
<br />MOTOR STARTER SWITCH WITH
<br />AS NOTED
<br />OVERLOAD RELAYS AS REQUIRED
<br />MOTOR
<br />AS NOTED
<br />LO 60 3
<br />DISCONNECT SWITCH
<br />TOP 60" AFF
<br />40
<br />SIZE/ FUSE/ M OF POLES
<br />OR AS NOTED
<br />CONDUIT CONCEALED IN CEILING
<br />NUMBER OF WIRES
<br />SPACE OR WALL
<br />INDICATED AS FOLLOWS
<br />�--
<br />CONDUIT IN FLOOR SLAB, CEILING
<br />TWO WIRES
<br />�
<br />SLAB OR UNDERGROUND
<br />THREE WIRES
<br />HOME RUN TO PANEL (HASH MARKS
<br />FOUR WIRES
<br />INDICATE NUMBER OF WIRES)
<br />CONDUIT RUN EXPOSED
<br />WIREMOLD
<br />AS NOTED
<br />®
<br />Q
<br />TEMPERATURE SENSOR
<br />AS NOTED
<br />MECHANICAL PLANS
<br />Q
<br />JUNCTION BOX
<br />AS NOTED
<br />m
<br />FIRE ALARM MANUAL
<br />46" AFF OR AS
<br />PULL STATION
<br />NOTED
<br />FIRE ALARM CHIME/FLASHING
<br />80" AFF OR
<br />LIGHT COMBINATION SIGNAL
<br />SEE NOTE BELOW
<br />gH
<br />FIRE ALARM FLASHING
<br />80" AFF OR
<br />LIGHT SIGNAL
<br />I SEE NOTE BELOW
<br />®
<br />FIRE ALARM SMOKE DETECTOR
<br />ON CEILING OR
<br />AS NOTED
<br />WALL MOUNTED
<br />6" BELOW THE CEILING TO
<br />SMOKE DETECTOR
<br />THE TOP OF THE DETECTOR
<br />®
<br />RELAY
<br />AS NOTED
<br />FRCP
<br />FIRE ALARM CONTROL PANEL
<br />60" AFF TO TOP
<br />i�
<br />"FAA" - FIRE ALARM ANNUNCIATOR
<br />OR AS NOTED
<br />O O 3❑ Q O
<br />1 REFER TO LIKE NUMBERED NOTES
<br />ALL MOUNTING HEIGHTS SHOWN ARE TO THE CENTERLINE OF THE
<br />DEVICE UNLESS NOTED OTHERWISE
<br />NOTE - THE DEVICE SHALL BE PLACED 80 INCHES ABOVE THE HIGHEST
<br />FLOOR LEVEL WITHIN THE SPACE OR 6 INCHES BELOW THE CEILING,
<br />WHICHEVER IS LOWER
<br />System No. C-AJ-1079
<br />F Ratings - 3 and 4 Hr (See Item 3C)
<br />T Ratings - 0, 1/4, 1/2 and 3/4 Hr (See Item 2)
<br />L Rating At Ambient - Less Than 1 CFM/sq ft
<br />L Rating At 400 F - Less Than 1 CFM/sq ft
<br />A
<br />A �J
<br />Section A -A
<br />1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Floor may
<br />also be constructed of any min 6 in. thick UL Classified hollow -core Precast Concrete Units*. Wall may also be constructed of
<br />any UL Classified Concrete Blocks*. Max diam of opening is 28 in. Max diam of opening in floor constructed of hollow -core
<br />precast concrete units is 7 in.
<br />See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of
<br />manufacturers.
<br />2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the
<br />firestop system. The annular space between the pipe, conduit or tubing and the periphery of the opening shall be min 0 in.
<br />(point contact) to a max 4 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The
<br />following types and sizes of metallic pipes, conduits or tubing may be used:
<br />A. Steel Pipe - Nom 24 in diam (or smaller) Schedule 5 (or heavier) steel pipe.
<br />B. Iron Pipe - Nom 24 in. diam (or smaller) cast or ductile iron pipe.
<br />C. Conduit - Nom 4 in. diam (or smaller) electrical metallic tubing or nom 6 in. diam (or smaller) steel conduit or nom 1 in.
<br />diam (or smaller) flexible steel conduit.
<br />D. Copper Tubing - Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
<br />E. Copper Pipe - Nom 6 in. diam (or smaller) Regular or heavier copper pipe.
<br />Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876
<br />Reproduced courtesy of Underwriters Laboratories Inc.
<br />STI Created or Revised: October 09, 2069 C ®` U
<br />-AJ-1079
<br />(800)992-1180 • (908)526-8000 - FAX (908)231-8415 - E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 2
<br />System No. C-AJ-1259
<br />F Rating - 3 Hr
<br />T Rating - 0 Hr
<br />I A
<br />A
<br />Section A -A
<br />1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Floor may
<br />also be constructed of any min 6 in. thick UL Classified hollow -core Precast Concrete Units*. Wall may also be constructed of
<br />any UL Classified Concrete Blocks*. Max diam of opening is 7 in.
<br />See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of
<br />manufacturers.
<br />2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the
<br />firestop system. The annular space between the pipe, conduit or tubing and the periphery of the opening shall be a min of 0 in.
<br />(point contact) to a max of 3 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The
<br />following types and sizes of metallic pipes, conduit or tubing may be used:
<br />A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
<br />B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe.
<br />C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit.
<br />D. Copper Tube - Nom 4 in. diam (or smaller) Type L (or heavier) copper tube.
<br />3. Forming Material - (Optional, Not Shown) - Mineral wool batt packing material or polyurethane backer rod friction fitted
<br />into opening and recessed from floor or wall surfaces as required to accommodate required thickness of fill material.
<br />4. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. thickness of fill material applied within the annulus, flush with both
<br />surfaces of floor or wall. At the point contact location between penetrating item and concrete, a min 114 in. thick bead of fill
<br />material shall be applied at the concrete/penetrating item interface on both sides of floor or wall.
<br />SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant
<br />*Bearing the UL Classification Mark
<br />Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876
<br />Reproduced courtesy of Underwriters Laboratories, Inc.
<br />STI Created or Revised: October 09, 2009 C ®� U S
<br />(800)992-1180 - (908)526-8000 - FAX (908)231-8415 • E-Mail:techserv@stifirestop.com - Website:www.stifirestop.com AGE 11OF�1
<br />A55REVIATION6
<br />AFC
<br />- AVAILABLE FAULT CURRENT
<br />LW -
<br />LIGHT WHITE
<br />AFF
<br />- ABOVE FINISHED FLOOR
<br />HP -
<br />HORSEPOWER, HEAT PUMP
<br />AHU
<br />- AIR HANDLING UNIT
<br />HVAC -
<br />HEATING, VENTILATING, AIR CONDITIONING
<br />BFG
<br />- BELOW FINISHED GRADE
<br />JB -
<br />JUNCTION BOX
<br />C
<br />- CONDUIT
<br />LRA -
<br />LOCKED ROTOR AMPERES
<br />CW
<br />- COOL WHITE
<br />MCB -
<br />MAIN CIRCUIT BREAKER
<br />DACT
<br />- DIGITAL ALARM COMMUNICATOR TRANSMITTER
<br />MLO -
<br />MAIN LUGS ONLY
<br />DACP
<br />- DOOR ALARM CONTROL PANEL
<br />N -
<br />NEUTRAL
<br />DN
<br />- DOWN
<br />NL -
<br />NIGHT LIGHT
<br />EF
<br />- EXHAUST FAN
<br />OB -
<br />OUTLET BOX
<br />EG
<br />- EQUIPMENT GROUND
<br />PB -
<br />PULL BOX, PUSHBUTTON
<br />ENCL
<br />- ENCLOSURE
<br />RECEPT-
<br />RECEPTACLE
<br />EWC
<br />- ELECTRIC WATER COOLER
<br />RLC -
<br />RELOCATE
<br />EWH
<br />- ELECTRIC WATER HEATER
<br />WV -
<br />REMOVE
<br />ETR
<br />- EXISTING TO REMAIN
<br />RWD -
<br />REWIRE
<br />EX
<br />- EXISTING
<br />SF -
<br />SUPPLY FAN
<br />FRCP
<br />- FIRE ALARM CONTROL PANEL
<br />SPEC -
<br />SPECIFICATIONS
<br />FAA
<br />- FIRE ALARM ANNUNCIATOR
<br />TL -
<br />TWISTLOCK
<br />FCU
<br />- FAN COIL UNIT
<br />TTB -
<br />TELEPHONE TERMINAL BOARD
<br />FHP
<br />- FRACTIONAL HORSE POWER
<br />TVT5 -
<br />TELEVISION TERMINAL BOARD
<br />FLA
<br />- FULL LOAD AMPERES
<br />UNO -
<br />UNLESS NOTED OTHERWISE
<br />G
<br />- GROUND
<br />VERT -
<br />VERTICAL
<br />GFI
<br />- GROUND FAULT INTERRUPTER
<br />UP -
<br />WEATHERPROOF
<br />HID
<br />- HIGH INTENSISTY DISCHARGE
<br />WW -
<br />WARM WHITE
<br />HORIZ
<br />- HORIZONTAL
<br />XFMR -
<br />TRANSFORMER
<br />IG
<br />- ISOLATED GROUND
<br />Type of Metallic Penetrant
<br />Max Diam of Metallic Penetrant in.
<br />T Rating Hr
<br />Steel or Iron Pipe, Conduit
<br />24
<br />0
<br />Copper Pipe or Tube
<br />6
<br />0
<br />Steel or Iron Pipe, Conduit or EMT
<br />4
<br />1/4
<br />Steel or Iron Pipe, Conduit or EMT
<br />2
<br />1/2
<br />Steel or Iron Pipe, Conduit or EMT
<br />F 1
<br />3/4
<br />3. Firestop System -The firestop system shall consist of the following:
<br />A. Packing Material - Min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material
<br />to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of
<br />fill material. When floor is constructed of hollow -core precast concrete units, packing material is to be recessed from both
<br />surfaces of floor to accommodate the required thickness of fill material.
<br />The thickness of the packing material is dependent upon the type and diam of the through penetrant (Item 2) as tabulated
<br />below:
<br />Thought Penetrant
<br />Max Throught-Penetrant Diam In.
<br />Min Mineral Wool Insulation Thkns In.
<br />Steel Pipe, Conduit Or Iron Pipe
<br />6
<br />1-1/2++
<br />Steel Pipe, Conduit Or Iron Pipe
<br />24
<br />3
<br />Copper Tube Or Copper Pipe
<br />6
<br />3
<br />++When annular space exceeds 2 in., packing material thickness to be min 3 in.
<br />B. Fill, Void or Cavity Material* - Caulk - Min 1/2 in. thickness of fill material applied within the annulus, flush with top
<br />surface of floor or with both surfaces of wall. When floor is constructed of hollow -core precast concrete units, fill material is
<br />to be installed symmetrically on both sides of floor, flush with floor surfaces. At the point contact location between
<br />penetrating item and concrete, a min 3/8 in. thick bead of fill material shall be applied at the concrete penetrating item
<br />interface on top surface of floor and both surfaces of wall or hollow -core precast concrete floor.
<br />SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant
<br />C. Steel Cover Plate - (Not Shown) - Min 0.014 in. (No. 28 gauge) galv steel cut to fit the contour of the through -penetrant
<br />assembly around the perimeter of the
<br />(Item 2) with a min 2 in. lap on the top surface of floor and both surfaces of wall asse y p
<br />through -opening. Seams of steel cover plate shall overlap a min 1/2 in. Steel cover plate secured to top surface of floor and
<br />both surfaces of wall assembly by means of 114 in, diam by 1-3/4 in. long steel concrete anchors in conjunction with 1/4 in.
<br />by 1-1A in. diam steel fender washers spaced a max 6 in. OC.
<br />The hourly F Rating of the firestop system is dependent upon the use of the steel cover plate. If the steel cover plate is
<br />used , the F Rating of the firestop system is 4 hr. If the steel cover plate is omitted, the F Rating of the firestop system is 3
<br />hr.
<br />*Bearing the UL Classification Mark
<br />TV Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876
<br />Reproduced courtesy of Underwriters Laboratories Inc. u
<br />STI Created or Revised: October 09, 20b9 C ®` U
<br />-AJ-1079
<br />(800)992-1180 - (908)526-8000 - FAX (908)231-8415 • E-Mail:techserv@stifirestop.com - Website:www.stifirestop.com PAGE 2OF 2
<br />GENERAL PROJECT AND DEMOLITION NOTES
<br />I. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING
<br />CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF THE WORK
<br />THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN
<br />MADE. LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED, OR FOR
<br />DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN
<br />EXAMINATION BEEN MADE, WILL NOT BE ALLOWED.
<br />2. ALL EXISTING CIRCUITS TO REMAIN SHALL BE RECONNECTED WHETHER INDICATED OR
<br />NOT ON PROJECT DOCUMENTS.
<br />3. NEW AND EXISTING CIRCUIT DESIGNATIONS MAY NOT REPRESENT ACTUAL FIELD
<br />CONDITIONS. FIELD VERIFY WHERE REQUIRED AND INDICATE ACTUAL CIRCUIT USED ON
<br />THE AS -BUILT DRAWINGS.
<br />4. COORDINATE WITH OTHER TRADES FOR ITEMS IN THEIR SCOPE OF WORK WHICH WOULD
<br />REQUIRE ELECTRICAL WORK DISCONNECTION, RECONNECTION, ETC. AND ARE NOT
<br />INDICATED ON THE ELECTRICAL PLANS.
<br />5. WHERE EXISTING PARTITIONS OR WALLS ARE SHOWN TO BE REMOVED, CONTRACTOR
<br />SHALL REMOVE DEVICES TO THE NEAREST SOURCE JUNCTION BOX AND SHALL MAINTAIN
<br />SERVICE TO REMAINING DOWNSTREAM ELECTRICAL OUTLETS. COORDINATE THE
<br />DEMOLITION OF THE EXISTING WALLS WITH ARCHITECTURAL DRAWINGS.
<br />6. PROTECT EXISTING ELECTRICAL EQUIPMENT AND INSTALLATIONS NECESSARY TO
<br />REMAIN. IF EXISTING EQUIPMENT IS DAMAGED OR DISTURBED IN THE COURSE OF THE
<br />WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL
<br />CAPACITY, QUALITY, AND FUNCTIONALITY.
<br />-1, REMOVE ELECTRICAL EQUIPMENT AND INSTALLATIONS INDICATED TO BE DEMOLISHED
<br />IN THEIR ENTIRETY. WHERE THE EXISTING EQUIPMENT INDICATED TO BE DEMOLISHED
<br />CONTAINS BRANCH CIRCUITRY SERVING OUTLETS THAT ARE EXISTING TO REMAIN,
<br />RELOCATE THE BRANCH CIRCUIT TO AN ALTERNATE PANEL AND INDICATE THE CHANGE
<br />ON THE AS -BUILT DRAWINGS.
<br />8. ABANDONED WORK CUT OR REMOVE RACEWAY SLEEVES AND WIRING INDICATED TO BE
<br />ABANDONED IN PLACE BELOW THE SURFACE OF ADJACENT CONSTRUCTION. CAP
<br />RACEWAYS AND PATCH SURFACE TO MATCH EXISTING FINISH.
<br />9, COMPLETELY REMOVE ALL EXISTING FLOOR BOX BRANCH CIRCUITS BACK TO PANEL.
<br />REMOVE FLOOR DATA WIRING COMPLETELY BACK TO SOURCE. REMOVE FLOOR BOX
<br />COVERS AND FLANGES AND GRIND FLOOR BOX TO BELOW FINISHED SLAB TO PREPARE
<br />FOR CONCRETE FINISH WORK COORDINATE WITH GENERAL CONTRACTOR,
<br />10, THE CONTRACTOR SHALL INCLUDE WITHIN THE BID ALL REQUIRED OFF HOUR, OVERTIME,
<br />AND NON -BUSINESS HOUR WORK AS REQUIRED TO PERT-ORM THE DEMOLITION WITHOUT
<br />DISRUPTING THE BUILDING TENANTS NORMAL BUSINESS OPERATIONS.
<br />II. REMOVE ALL DATA WIRING AND EQUIPMENT RACKS THAT WILL NOT BE RE -USED.
<br />RELOCATE TELEPHONE DEMARC CONDUIT TO NEW LOCATION AS REQUIRED.
<br />12. ALL DEMOLISHED EQUIPMENT AND WIRING SHALL BE REMOVED FROM SITE AND
<br />PROPERLY DISPOSED OF OR TURNED OVER TO THE OWNER AT THE OWNER'S SOLE
<br />OPTION.
<br />Wall Opening Protective Materials
<br />SPECIFIED TECHNOLOGIES INC R14288 SUITE 2 200 EVANS WAY SOMERVILLE, NJ 08616 USA
<br />SpecSeal Putty Paris, for use with max 4-II/16 by 4-I1/16 in. flush device UL Listed metallic outlet boxes Installed with steel cover plates In i
<br />and 2 h fire rated gypsum board wall assemblies framed with min 3-1/2 In. deep wood or steel studs and constructed of the materials and in
<br />the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs In the Fire Resistance Directory. Installation to
<br />comply with the National Electrical Code (NFPA 10). Min 3/16 in. thick moldable putty pads are to be installed to completely cover the
<br />exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and completely seal against the stud within the
<br />stud cavity. An additional 3/16 in. thickness of putty to be formed around the connector securing the end of each electrical metallic tube or
<br />conduit to the box. When used with metallic outlet boxes larger than 4 by 4 In., a ball of putty is to be installed to plug the open end of
<br />each electrical metallic tube or conduit within the outlet box. When max 4 by 4 In. metallic outlet boxes are used, the ball of putty in the open
<br />end of each electrical metallic tube or conduit within the outlet box is optional. 11kien moldable putty pad outlet box protective material is
<br />used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on the opposite sides of the wall may be
<br />less than 24 in. provided that the boxes are not installed back-to-back
<br />SpecSeal Putty Pads for use with max 4 by 3-3/4 by 3 In. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon Electrical
<br />Products and made from polyvinyl chloride, max 4 by 3-3/4 by 3 in, deep UL Listed Nonmetallic Outlet Boxes manufactured by Allied Moulded
<br />Products Inc. and made from fiber -reinforced thermosetting plastic or max 4-1/16 by 3-5/6 by 3-1/8 in. deep UL Listed Nonmetallic Outlet
<br />Boxes manufactured by Thomas 4 Betts Corp. and made from fiber -reinforced thermosetting plastic. Boxes shall also bear a 2 h rating under
<br />the "Outlet Boxes and Fittings Classified for Fire Resistance" category in the Fire Resistance Directory. Installation to comply with the
<br />National Electrical Code (NFPA 10). Boxes installed with steel or plastic cover plates. Putty pads and boxes for use in 1 and 2 h fire rated
<br />gypsum board/wood stud wall assemblies constructed of the materials and in the manner specified in the Individual U300 Series Wall and
<br />Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs in conjunction with nails
<br />supplied with the outlet box. Min 3/16 in. thick moldable putty pads are to be Installed to completely cover the exterior surfaces of the
<br />outlet box (except for the side of the outlet box against the stud) including nailing tabs and completely seal against the stud within the
<br />stud cavity. An additional 3/16 in. thickness of putty to be formed around the end of each nonmetallic sheathed cable at its connection to
<br />the box and to extend a minimum of 1 in. from the box onto the nonmetallic sheathed cable within the stud cavity. When moldable putty pad
<br />outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on
<br />opposite sides of the wall may be less than 24 in, provided that the boxes are not installed back-to-back
<br />FI���TIONDET,41LS�T��IC��SDETAILS�T�LIC��S
<br />NOT TO SCALE
<br />O 1 ELECTimICAL Si�CIFICATION5
<br />SCALE: NOT TO SCALE
<br />00
<br />m N
<br />o 0 o
<br />N cd [� U
<br />5 Z
<br />N in cxd *U.
<br />NCd
<br />G p., 4-
<br />CD• U
<br />C)in c'-d
<br />N t
<br />ti 10
<br />o
<br />~ 00 3
<br />r-
<br />3ti 3
<br />O x N
<br />G
<br />ti o
<br />tia
<br />cm
<br />0
<br />.
<br />6
<br />• "it fLd
<br />ti
<br />•
<br />-- 0)
<br />�`'
<br />•
<br />D,.:
<br />U)
<br />L0 1 i► �= rb Ch
<br />o
<br />`drat
<br />••� .••� _c_ca
<br />•,
<br />ss
<br />� ..�5
<br />L
<br />m
<br />t
<br />c
<br />m
<br />i
<br />I)
<br />-a
<br />tf)
<br />3
<br />LI_
<br />r
<br />L-
<br />M
<br />O
<br />O
<br />75
<br />J
<br />.=1
<br />(�
<br />t^
<br />N
<br />O
<br />m
<br />LL
<br />m
<br />W
<br />-
<br />N
<br />ti
<br />0
<br />L
<br />.0
<br />F-
<br />E
<br />OCO:)
<br />s
<br />Q
<br />U
<br />CO
<br />N
<br />m
<br />C
<br />L
<br />N
<br />t
<br />a
<br />m
<br />N
<br />Date: 02. 06. 14
<br />Scale:
<br />AS NOTED
<br />Project
<br />Mgr: MPS
<br />Drawn:
<br />MW
<br />Job:
<br />12-194
<br />Sheet
<br />El
<br />
|