Laserfiche WebLink
ft <br />M Le <br />ELECTRICAL SPECIFICATIONS <br />I. THE WORK SUBJECT TO THESE SPECIFICATIONS SHALL BE IN CONFORMANCE WITH THE LATEST <br />EDITION OF THE NATIONAL ELECTRICAL CODE. THE INSTALLATION SHALL ALSO COMPLY WITH ALL <br />APPLICABLE RULES AND REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES. <br />2. ALL ELECTRICAL EQUIPMENT SHALL BE SPECIFICATION GRADE AND SHALL HAVE THE PROPER UL <br />LABEL. <br />3. POWER DISTRIBUTION HOUSE PANEL50ARD PROVIDE DEAD -FRONT, <br />SAFETY -TYPE POWER DISTRIBUTION PANELBOARDS AS INDICATED WITH SWITCHING AND <br />PROTECTIVE DEVICES IN QUANTITIES, RATINGS, TYPES, AND WITH ARRANGEMENT SHOWN. INCLUDE <br />ANTI -TURN, SOLDERLESS PRESSURE TYPE MAIN LUG CONNECTORS APPROVED FOR USE WITH <br />COPPER CONDUCTORS. <br />4. HOUSE PANELBOARD IS EXISTING AND IS EQUAL TO SQUARE D TYPE "NQOD". VOLTAGE SHALL BE <br />AS INDICATED. ACCEPTABLE MANUFACTURERS INCLUDE GENERAL ELECTRIC, SIEMENS AND <br />CUTLER -HAMMER <br />5. TENANT PANELBOARDS PROVIDE DEAD -FRONT SAFETY TYPE LIGHTING AND BRANCH CIRCUIT <br />PANELBOARDS AS INDICATED WITH SWITCHING AND PROTECTIVE DEVICES- IN QUANTITIES, RATINGS, <br />TYPES AND ARRANGEMENTS SHOWN. INCLUDE ANTI -TURN, SOLDERLESS PRESSURE TYPE LUG <br />CONNECTORS APPROVED FOR USE WITH COPPER CONDUCTORS. <br />6. TENANT PANELBOARDS SHALL BE SQUARE D TYPE =00s. PANEL50ARD BOXES SHALL BE FIVE <br />AND THREE -FOURTHS INCHES (5-3/4") DEEP. VOLTAGE SHALL BE AS INDICATED. <br />1. ALL PANEL50ARDS SHALL BE CONNECTED, DISTRIBUTED PHASE, WITH CIRCUIT NUMBERING AS <br />INDICATED ON THE DRAWINGS. PANELBOARDS SHALL <br />BE NUMBERED WITH ODD NUMBERS ON THE LEFT SIDE OF THE PANEL AND EVEN NUMBERS ON THE <br />RIGHT SIDE OF THE PANEL.. <br />6. UNLESS OTHERWISE INDICATED, PROTECTIVE DEVICES SHALL BE MOUNTED WITH TOP OF CABINET <br />OR ENCLOSURE 6'-b" ABOVE FINISHED FLOOR, SHALL BE PROPERLY ALIGNED, AND SHALL BE <br />ADEQUATELY SUPPORTED INDEPENDENTLY OF THE CONNECTING RACEWAYS. ANY AND ALL STEEL <br />FRAMING, SHAPES, ETC., NECESSARY FOR THE SUPPORT OF THE EQUIPMENT SHALL BE FURNISHED <br />AND INSTALLED BY THE CONTRACTOR WHERE THE BUILDING STRUCTURE IS NOT SUITABLE FOR <br />MOUNTING THE EQUIPMENT DIRECTLY THEREON. UNLESS OTHERWISE INDICATED, ALL BRANCH <br />CIRCUIT PROTECTIVE DEVICE ENCLOSURES SHALL BE NEMA TYPE I, GENERAL PURPOSE TYPE. <br />CIRCUIT PROTECTIVE DEVICES INSTALLED OUTDOORS OR EXPOSED TO THE WEATHER SHALL <br />HAVE WEATHERPROOF ENCLOSURES, NEMA TYPE =3R= OR TYPE =4=. <br />S. ALL SAFETY SWITCHES SHALL BE GENERAL DUTY TYPE. SWITCH MECHANISM SHALL BE <br />QUICK -MAKE, QUICK -BREAK COVERS SHALL BE INTERLOCKED WITH <br />MECHANISM TO PREVENT OPENING UNLESS SWITCH IS IN THE "OFF" POSITION. ALL ENCLOSURES <br />SHALL BE PRIMED AND FINISHED TO RESIST RUSTING AND CORROSION. SWITCHES SHALL BE <br />SQUARE-D, SIEMENS, GENERAL ELECTRIC OR CUTLER -HAMMER <br />10. CIRCUIT BREAKERS FOR MOUNTING IN HOUSE PANELBOARD SHALL BE BOLT -ON TYPE, MOLDED <br />PLASTIC CASE, AIR CIRCUIT BREAKER TYPE. BREAKERS SHALL HAVE THERMAL MAGNETIC TRIP <br />UNITS AND MULTI -POLE BREAKERS SHALL HAVE A COMMON TRIP BAR SO THAT THE TRIPPING OF <br />ONE POLE WILL AUTOMATICALLY TRIP ALL POLES OF THE BREAKER BREAKERS SHALL BE TRIP <br />FREE AND TRIP INDICATING AND SHALL HAVE QUICK -MAKE, QUICK -BREAK CONTACTS. <br />II. UPON COMPLETION OF WORK CORRECT ALL PANELBOARD CIRCUIT DIRECTORY CARDS TO <br />REFLECT AS -BUILT CONDITIONS. PANELBOARD DIRECTORIES SHALL BE UPDATED WITH <br />TYPEWRITTEN ACCURATE AND CURRENT INFORMATION BY THE CONTRACTOR AT THE END OF <br />CONSTRUCTION. DIRECTORIES SHALL REFLECT RECORD CONDITIONS AND INCLUDE CIRCUIT <br />NUMBER, TYPE AND LOCATION OF LOAD. A SET OF AS -BUILT DRAWINGS SHALL ALSO BE <br />PREPARED AND TURNED OVER TO THE OWNER <br />12. UNLESS SPECIFICALLY NOTED ON DRAWINGS, RACEWAYS SHALL COMPLY WITH THE FOLLOWING <br />RACEWAYS EXPOSED TO THE WEATHER OR IN DAMP LOCATIONS <br />SHALL BE GALVANIZED RIGID STEEL WITH THREADED CONNECTIONS. <br />RACEWAYS SHALL BE SIZED FOR THE CONDUCTORS INSTALLED BUT A MINIMUM <br />1/2". FULL SIZE MC CABLE IS ACCEPTABLE IN DRY LOCATIONS. HOMER INS TO <br />PANELS SHALL BE IN CONDUIT. <br />13. RACEWAYS RUN BELOW GRADE SHALL BE RIGID STEEL CONDUIT WITH A REDUNDANT GROUND <br />PATH INCLUDED. RACEWAYS RUN EXPOSED ON BUILDING EXTERIOR SHALL BE RIGID STEEL <br />CONDUIT. <br />14. ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE AT ALL JOINTS <br />AND AT ALL BOXES, CABINETS, FITTINGS, AND EQUIPMENT. <br />15. ALL RACEWAYS SHALL BE SECURELY SUPPORTED FROM THE BUILDING STRUCTURE. <br />16. ALL RACEWAYS SHALL BE PROVIDED WITH AN EQUIPMENT GROUND CONDUCTOR <br />11. ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH SUITABLE SCREW <br />FASTENED COVERS. OPEN KNOCK -OUTS OR HOLES IN BOXES SHALL BE PLUGGED WITH A <br />SUITABLE BLANKING DEVICE. <br />Ia. OUTLET BOXES FOR EXPOSED WALL MOUNTING AND OUTDOOR INSTALLATION SHALL BE CAST <br />METAL TYPE "FS" OR 'TV" BOXES WITH SUITABLE GALVANIZED SHEET STEEL COVERS, OR CAST <br />METAL WEATHERPROOF OR VAPOR TIGHT COVERS WHEN NOTED ON THE DRAWINGS. <br />19. UNLESS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER NO. 12 AM. MINIMUM OR SIZE <br />AS SHOWN ON DRAWINGS. CONDUCTORS SHALL HAVE TYPE "THHN/THWN' INSULATION. <br />20. SPLICES, TAPS AND ATTACHMENT FITTINGS AND LUGS SHALL BE ELECTRICALLY AND <br />MECHANICALLY SECURE AND SOLDERLESS FOR CONDUCTORS SIZES NO. 8 AUG AND LARGER <br />THERE SHALL BE PLENTY OF SLACK CABLE IN BOXES, OUTLETS AND CABINETS TO INSURE THAT <br />THERE IS NO BINDING AT T14E BUSHINGS. ALL LUGS SHALL BE OF THE CORRECT SIZE FOR THE <br />CONDUCTORS INSTALLED AND IN NO CASE SHALL STRANDS BE CUT FROM A CONDUCTOR IN <br />ORDER TO FIT THE CONDUCTOR INTO A LUG. TAPING OF JOINTS SHALL BE WITH VINYL PLASTIC <br />ELECTRICAL TAPE TO INSURE INSULATION STRENGTH EQUAL TO THAT OF THE CONDUCTORS JOINED. <br />21. THE INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS <br />REQUIRED BY THE NEC AND AS SPECIFIED HEREINAFTER <br />22. CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS. <br />23. THE CONTRACTOR SHALL VERIFY ALL LOCATIONS WITH THE OWNER PRIOR TO INSTALLATION. THEY <br />SHALL NOT BE CHARSED FOR MINOR LOCATION CHANGES PRIOR TO INSTALLATIONS. LOCATIONS <br />ARE APPROXIMATE. (DO NOT SCALE DRAWINGS). <br />24, THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL ELECTRICAL LAYOUTS FOR BIDDING <br />PURPOSES ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PREPARE DETAILED SHOP <br />DRAWINGS AND CONFIRM SPACE ALLOCATIONS. <br />25. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES <br />FOR ELECTRICAL CONDUIT ROUTING AND EQUIPMENT PLACEMENT. AVOID INTERFERENCE WITH <br />ARCHITECTURAL AND STRUCTURAL FEATURES SUCH AN BEAMS, FOOTINGS, WINDOWS, ETC. NOTIFY <br />ARCHITECT IMMEDIATELY OF ANY CONFLICTS. <br />26. THE ELECTRICAL CONTRACTOR, THE HVAC FOREMAN AND THE GENERAL CONTRACTOR PROJECT <br />MANAGER SHALL INSPECT AND REVIEW THE CONDITIONS, AND SHALL COORDINATE THEIR WORK <br />SO AS TO PROVIDE ADEQUATE SPACE ALLOWANCE ABOVE CEILING FOR ALL TRADES. <br />21. THE PLANS SHOW THE LOCATION OF ALL FIXTURES AND EQUIPMENT AND ARE INTENDED TO <br />DEPICT THE GENERAL INTENT OF THE WORK IN SCOPE, LAYOUT AND QUALITY OF WORKMANSHIP. <br />THEY ARE NOT INTENDED TO SHOW IN MINUTE DETAIL EVERY AND ALL ACCESSORY INTENDED FOR <br />THE PURPOSE OF EXECUTION OF THE WORK, BUT SHALL BE UNDERSTOOD THAT SUCH DETAILS WILL <br />BE PART OF THIS WORK <br />26, THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE <br />AND FUNCTIONAL ELECTRICAL SYSTEM INCLUDING CONTROLS AND CONNECTIONS TO NEW <br />SERVICES, SUPPORTS, AND HARDWARE REQUIRED FOR THE SATISFACTORY OPERATION OF THE <br />SYSTEM, WHETHER SPECIFICALLY SHOWN OR NOT ON THE DRAWINGS. <br />N <br />N <br />SYMBOL LIST <br />SYMBOL <br />DESCRIPTION <br />MOUNTING <br />® <br />1'x4' FLOORESCENT FIXTURE <br />SEE FIXTURE <br />SCHEDULE <br />2'x4' FLOORESCENT FIXTURE <br />SEE FIXTURE <br />SCHEDULE <br />SHADED FIXTURES CONTAIN <br />SEE FIXTURE <br />BATTERY PACK <br />SCHEDULE <br />F0-1 <br />FLUORESCENT STRIP FIXTURE <br />SEE FIXTURE <br />SCHEDULE <br />LIGHT FIXTURE, WALL BRACKET <br />SEE FIXTURE <br />LETTER INDICATES TYPE <br />SCHEDULE <br />®LIGHT <br />FIXTURE, CEILING TYPE <br />SEE FIXTURE <br />LETTER INDICATES TYPE <br />SCHEDULE <br />® B <br />EXIT FIXTURE, SHADING INDICATES <br />SEE FIXTURE <br />SINGLE OR DOUBLE FACE <br />SCHEDULE <br />4p <br />EXIT LIGHT WITH EMERGENCY <br />SEE FIXTURE <br />I� <br />LIGHTS <br />SCHEDULE <br />EMERGENCY BATTERY UNIT <br />SEE FIXTURE <br />SCHEDULE <br />S <br />SWITCH, SINGLE POLE -LETTER <br />46" AFF TO CL <br />INDICATES LIGHTS CONTROLLED <br />OR AS NOTED <br />SWITCH, THREE WAY <br />4a" AFF TO CIL <br />$ <br />OR AS NOTED <br />DIGITAL SWITCH OR AS <br />+48" AFF OR AS <br />NOTED <br />NOTED <br />0 <br />WALL -MOUNTED OCCUPANCY <br />+48" AFF OR AS <br />SENSOR <br />NOTED <br />®CEILING <br />MOUNTED OCCUPANCY <br />SURFACE MOUNT <br />SENSOR <br />TO CEILING <br />INSTALL CONCEALED <br />LR <br />LIGHTING RELAY <br />IN AN ACCESSIBLE <br />AREA ABOVE CEILING <br />INSTALL CONCEALED <br />Ea <br />POWER PACK <br />IN AN ACCESSIBLE <br />AREA ABOVE CEILING <br />® <br />PHOTOCELL <br />SURFACE MOUNT <br />TO CEILING <br />IG� <br />DUPLEX RECEPTACLE, 125V, 20A <br />15" AM TO CL <br />WITH ISOLATED GROUND <br />OR AS NOTED <br />DUPLEX RECEPTACLE, 125V, 15A <br />IS" AFF OR AS <br />NOTED <br />DUPLEX RECEPTACLE, 125V, 15A <br />44" AFF OR 6" <br />ABOVE COUNTER <br />GFI� <br />DUPLEX RECEPTACLE, 125V, 15A <br />18" AFF OR AS <br />GROUND FAULT <br />NOTED <br />GF I� <br />DUPLEX RECEPTACLE, 125V, 15A <br />44" AFF OR 6 <br />ABOVE COUNTER <br />DUPLEX RECEPTACLE, 125V, 15A <br />INFLUSH FLOOR <br />QUADRAPLEX RECEPTACLE, 125V, 15A <br />16" AFF OR AS <br />NOTED <br />QUADRAPLEX RECEPTACLE, 125V, 15A <br />44" AFF OR 6" <br />ABOVE COUNTER <br />m <br />TELEPHONE/DATA OUTLET. SEE <br />18" AFF OR AS <br />PLANS FOR WIRING CONFIGURATION <br />NOTED <br />FH <br />TELEVISION OUTLET <br />16" AFF OR <br />AS NOTED <br />PANEL50ARD 1201206V <br />SEE PANEL <br />- <br />OR 120/240V <br />SCHEDULE <br />Sn <br />MOTOR STARTER SWITCH WITH <br />AS NOTED <br />OVERLOAD RELAYS AS REQUIRED <br />MOTOR <br />AS NOTED <br />LO 60 3 <br />DISCONNECT SWITCH <br />TOP 60" AFF <br />40 <br />SIZE/ FUSE/ M OF POLES <br />OR AS NOTED <br />CONDUIT CONCEALED IN CEILING <br />NUMBER OF WIRES <br />SPACE OR WALL <br />INDICATED AS FOLLOWS <br />�-- <br />CONDUIT IN FLOOR SLAB, CEILING <br />TWO WIRES <br />� <br />SLAB OR UNDERGROUND <br />THREE WIRES <br />HOME RUN TO PANEL (HASH MARKS <br />FOUR WIRES <br />INDICATE NUMBER OF WIRES) <br />CONDUIT RUN EXPOSED <br />WIREMOLD <br />AS NOTED <br />® <br />Q <br />TEMPERATURE SENSOR <br />AS NOTED <br />MECHANICAL PLANS <br />Q <br />JUNCTION BOX <br />AS NOTED <br />m <br />FIRE ALARM MANUAL <br />46" AFF OR AS <br />PULL STATION <br />NOTED <br />FIRE ALARM CHIME/FLASHING <br />80" AFF OR <br />LIGHT COMBINATION SIGNAL <br />SEE NOTE BELOW <br />gH <br />FIRE ALARM FLASHING <br />80" AFF OR <br />LIGHT SIGNAL <br />I SEE NOTE BELOW <br />® <br />FIRE ALARM SMOKE DETECTOR <br />ON CEILING OR <br />AS NOTED <br />WALL MOUNTED <br />6" BELOW THE CEILING TO <br />SMOKE DETECTOR <br />THE TOP OF THE DETECTOR <br />® <br />RELAY <br />AS NOTED <br />FRCP <br />FIRE ALARM CONTROL PANEL <br />60" AFF TO TOP <br />i� <br />"FAA" - FIRE ALARM ANNUNCIATOR <br />OR AS NOTED <br />O O 3❑ Q O <br />1 REFER TO LIKE NUMBERED NOTES <br />ALL MOUNTING HEIGHTS SHOWN ARE TO THE CENTERLINE OF THE <br />DEVICE UNLESS NOTED OTHERWISE <br />NOTE - THE DEVICE SHALL BE PLACED 80 INCHES ABOVE THE HIGHEST <br />FLOOR LEVEL WITHIN THE SPACE OR 6 INCHES BELOW THE CEILING, <br />WHICHEVER IS LOWER <br />System No. C-AJ-1079 <br />F Ratings - 3 and 4 Hr (See Item 3C) <br />T Ratings - 0, 1/4, 1/2 and 3/4 Hr (See Item 2) <br />L Rating At Ambient - Less Than 1 CFM/sq ft <br />L Rating At 400 F - Less Than 1 CFM/sq ft <br />A <br />A �J <br />Section A -A <br />1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Floor may <br />also be constructed of any min 6 in. thick UL Classified hollow -core Precast Concrete Units*. Wall may also be constructed of <br />any UL Classified Concrete Blocks*. Max diam of opening is 28 in. Max diam of opening in floor constructed of hollow -core <br />precast concrete units is 7 in. <br />See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of <br />manufacturers. <br />2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the <br />firestop system. The annular space between the pipe, conduit or tubing and the periphery of the opening shall be min 0 in. <br />(point contact) to a max 4 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The <br />following types and sizes of metallic pipes, conduits or tubing may be used: <br />A. Steel Pipe - Nom 24 in diam (or smaller) Schedule 5 (or heavier) steel pipe. <br />B. Iron Pipe - Nom 24 in. diam (or smaller) cast or ductile iron pipe. <br />C. Conduit - Nom 4 in. diam (or smaller) electrical metallic tubing or nom 6 in. diam (or smaller) steel conduit or nom 1 in. <br />diam (or smaller) flexible steel conduit. <br />D. Copper Tubing - Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing. <br />E. Copper Pipe - Nom 6 in. diam (or smaller) Regular or heavier copper pipe. <br />Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876 <br />Reproduced courtesy of Underwriters Laboratories Inc. <br />STI Created or Revised: October 09, 2069 C ®` U <br />-AJ-1079 <br />(800)992-1180 • (908)526-8000 - FAX (908)231-8415 - E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com PAGE 1 OF 2 <br />System No. C-AJ-1259 <br />F Rating - 3 Hr <br />T Rating - 0 Hr <br />I A <br />A <br />Section A -A <br />1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Floor may <br />also be constructed of any min 6 in. thick UL Classified hollow -core Precast Concrete Units*. Wall may also be constructed of <br />any UL Classified Concrete Blocks*. Max diam of opening is 7 in. <br />See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of <br />manufacturers. <br />2. Through Penetrants -One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the <br />firestop system. The annular space between the pipe, conduit or tubing and the periphery of the opening shall be a min of 0 in. <br />(point contact) to a max of 3 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The <br />following types and sizes of metallic pipes, conduit or tubing may be used: <br />A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. <br />B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe. <br />C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. <br />D. Copper Tube - Nom 4 in. diam (or smaller) Type L (or heavier) copper tube. <br />3. Forming Material - (Optional, Not Shown) - Mineral wool batt packing material or polyurethane backer rod friction fitted <br />into opening and recessed from floor or wall surfaces as required to accommodate required thickness of fill material. <br />4. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. thickness of fill material applied within the annulus, flush with both <br />surfaces of floor or wall. At the point contact location between penetrating item and concrete, a min 114 in. thick bead of fill <br />material shall be applied at the concrete/penetrating item interface on both sides of floor or wall. <br />SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant <br />*Bearing the UL Classification Mark <br />Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876 <br />Reproduced courtesy of Underwriters Laboratories, Inc. <br />STI Created or Revised: October 09, 2009 C ®� U S <br />(800)992-1180 - (908)526-8000 - FAX (908)231-8415 • E-Mail:techserv@stifirestop.com - Website:www.stifirestop.com AGE 11OF�1 <br />A55REVIATION6 <br />AFC <br />- AVAILABLE FAULT CURRENT <br />LW - <br />LIGHT WHITE <br />AFF <br />- ABOVE FINISHED FLOOR <br />HP - <br />HORSEPOWER, HEAT PUMP <br />AHU <br />- AIR HANDLING UNIT <br />HVAC - <br />HEATING, VENTILATING, AIR CONDITIONING <br />BFG <br />- BELOW FINISHED GRADE <br />JB - <br />JUNCTION BOX <br />C <br />- CONDUIT <br />LRA - <br />LOCKED ROTOR AMPERES <br />CW <br />- COOL WHITE <br />MCB - <br />MAIN CIRCUIT BREAKER <br />DACT <br />- DIGITAL ALARM COMMUNICATOR TRANSMITTER <br />MLO - <br />MAIN LUGS ONLY <br />DACP <br />- DOOR ALARM CONTROL PANEL <br />N - <br />NEUTRAL <br />DN <br />- DOWN <br />NL - <br />NIGHT LIGHT <br />EF <br />- EXHAUST FAN <br />OB - <br />OUTLET BOX <br />EG <br />- EQUIPMENT GROUND <br />PB - <br />PULL BOX, PUSHBUTTON <br />ENCL <br />- ENCLOSURE <br />RECEPT- <br />RECEPTACLE <br />EWC <br />- ELECTRIC WATER COOLER <br />RLC - <br />RELOCATE <br />EWH <br />- ELECTRIC WATER HEATER <br />WV - <br />REMOVE <br />ETR <br />- EXISTING TO REMAIN <br />RWD - <br />REWIRE <br />EX <br />- EXISTING <br />SF - <br />SUPPLY FAN <br />FRCP <br />- FIRE ALARM CONTROL PANEL <br />SPEC - <br />SPECIFICATIONS <br />FAA <br />- FIRE ALARM ANNUNCIATOR <br />TL - <br />TWISTLOCK <br />FCU <br />- FAN COIL UNIT <br />TTB - <br />TELEPHONE TERMINAL BOARD <br />FHP <br />- FRACTIONAL HORSE POWER <br />TVT5 - <br />TELEVISION TERMINAL BOARD <br />FLA <br />- FULL LOAD AMPERES <br />UNO - <br />UNLESS NOTED OTHERWISE <br />G <br />- GROUND <br />VERT - <br />VERTICAL <br />GFI <br />- GROUND FAULT INTERRUPTER <br />UP - <br />WEATHERPROOF <br />HID <br />- HIGH INTENSISTY DISCHARGE <br />WW - <br />WARM WHITE <br />HORIZ <br />- HORIZONTAL <br />XFMR - <br />TRANSFORMER <br />IG <br />- ISOLATED GROUND <br />Type of Metallic Penetrant <br />Max Diam of Metallic Penetrant in. <br />T Rating Hr <br />Steel or Iron Pipe, Conduit <br />24 <br />0 <br />Copper Pipe or Tube <br />6 <br />0 <br />Steel or Iron Pipe, Conduit or EMT <br />4 <br />1/4 <br />Steel or Iron Pipe, Conduit or EMT <br />2 <br />1/2 <br />Steel or Iron Pipe, Conduit or EMT <br />F 1 <br />3/4 <br />3. Firestop System -The firestop system shall consist of the following: <br />A. Packing Material - Min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material <br />to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of <br />fill material. When floor is constructed of hollow -core precast concrete units, packing material is to be recessed from both <br />surfaces of floor to accommodate the required thickness of fill material. <br />The thickness of the packing material is dependent upon the type and diam of the through penetrant (Item 2) as tabulated <br />below: <br />Thought Penetrant <br />Max Throught-Penetrant Diam In. <br />Min Mineral Wool Insulation Thkns In. <br />Steel Pipe, Conduit Or Iron Pipe <br />6 <br />1-1/2++ <br />Steel Pipe, Conduit Or Iron Pipe <br />24 <br />3 <br />Copper Tube Or Copper Pipe <br />6 <br />3 <br />++When annular space exceeds 2 in., packing material thickness to be min 3 in. <br />B. Fill, Void or Cavity Material* - Caulk - Min 1/2 in. thickness of fill material applied within the annulus, flush with top <br />surface of floor or with both surfaces of wall. When floor is constructed of hollow -core precast concrete units, fill material is <br />to be installed symmetrically on both sides of floor, flush with floor surfaces. At the point contact location between <br />penetrating item and concrete, a min 3/8 in. thick bead of fill material shall be applied at the concrete penetrating item <br />interface on top surface of floor and both surfaces of wall or hollow -core precast concrete floor. <br />SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant <br />C. Steel Cover Plate - (Not Shown) - Min 0.014 in. (No. 28 gauge) galv steel cut to fit the contour of the through -penetrant <br />assembly around the perimeter of the <br />(Item 2) with a min 2 in. lap on the top surface of floor and both surfaces of wall asse y p <br />through -opening. Seams of steel cover plate shall overlap a min 1/2 in. Steel cover plate secured to top surface of floor and <br />both surfaces of wall assembly by means of 114 in, diam by 1-3/4 in. long steel concrete anchors in conjunction with 1/4 in. <br />by 1-1A in. diam steel fender washers spaced a max 6 in. OC. <br />The hourly F Rating of the firestop system is dependent upon the use of the steel cover plate. If the steel cover plate is <br />used , the F Rating of the firestop system is 4 hr. If the steel cover plate is omitted, the F Rating of the firestop system is 3 <br />hr. <br />*Bearing the UL Classification Mark <br />TV Specified Technologies Inc. 200 Evans Way Somerville, NJ 08876 <br />Reproduced courtesy of Underwriters Laboratories Inc. u <br />STI Created or Revised: October 09, 20b9 C ®` U <br />-AJ-1079 <br />(800)992-1180 - (908)526-8000 - FAX (908)231-8415 • E-Mail:techserv@stifirestop.com - Website:www.stifirestop.com PAGE 2OF 2 <br />GENERAL PROJECT AND DEMOLITION NOTES <br />I. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING <br />CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF THE WORK <br />THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN <br />MADE. LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED, OR FOR <br />DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN <br />EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. <br />2. ALL EXISTING CIRCUITS TO REMAIN SHALL BE RECONNECTED WHETHER INDICATED OR <br />NOT ON PROJECT DOCUMENTS. <br />3. NEW AND EXISTING CIRCUIT DESIGNATIONS MAY NOT REPRESENT ACTUAL FIELD <br />CONDITIONS. FIELD VERIFY WHERE REQUIRED AND INDICATE ACTUAL CIRCUIT USED ON <br />THE AS -BUILT DRAWINGS. <br />4. COORDINATE WITH OTHER TRADES FOR ITEMS IN THEIR SCOPE OF WORK WHICH WOULD <br />REQUIRE ELECTRICAL WORK DISCONNECTION, RECONNECTION, ETC. AND ARE NOT <br />INDICATED ON THE ELECTRICAL PLANS. <br />5. WHERE EXISTING PARTITIONS OR WALLS ARE SHOWN TO BE REMOVED, CONTRACTOR <br />SHALL REMOVE DEVICES TO THE NEAREST SOURCE JUNCTION BOX AND SHALL MAINTAIN <br />SERVICE TO REMAINING DOWNSTREAM ELECTRICAL OUTLETS. COORDINATE THE <br />DEMOLITION OF THE EXISTING WALLS WITH ARCHITECTURAL DRAWINGS. <br />6. PROTECT EXISTING ELECTRICAL EQUIPMENT AND INSTALLATIONS NECESSARY TO <br />REMAIN. IF EXISTING EQUIPMENT IS DAMAGED OR DISTURBED IN THE COURSE OF THE <br />WORK, REMOVE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL <br />CAPACITY, QUALITY, AND FUNCTIONALITY. <br />-1, REMOVE ELECTRICAL EQUIPMENT AND INSTALLATIONS INDICATED TO BE DEMOLISHED <br />IN THEIR ENTIRETY. WHERE THE EXISTING EQUIPMENT INDICATED TO BE DEMOLISHED <br />CONTAINS BRANCH CIRCUITRY SERVING OUTLETS THAT ARE EXISTING TO REMAIN, <br />RELOCATE THE BRANCH CIRCUIT TO AN ALTERNATE PANEL AND INDICATE THE CHANGE <br />ON THE AS -BUILT DRAWINGS. <br />8. ABANDONED WORK CUT OR REMOVE RACEWAY SLEEVES AND WIRING INDICATED TO BE <br />ABANDONED IN PLACE BELOW THE SURFACE OF ADJACENT CONSTRUCTION. CAP <br />RACEWAYS AND PATCH SURFACE TO MATCH EXISTING FINISH. <br />9, COMPLETELY REMOVE ALL EXISTING FLOOR BOX BRANCH CIRCUITS BACK TO PANEL. <br />REMOVE FLOOR DATA WIRING COMPLETELY BACK TO SOURCE. REMOVE FLOOR BOX <br />COVERS AND FLANGES AND GRIND FLOOR BOX TO BELOW FINISHED SLAB TO PREPARE <br />FOR CONCRETE FINISH WORK COORDINATE WITH GENERAL CONTRACTOR, <br />10, THE CONTRACTOR SHALL INCLUDE WITHIN THE BID ALL REQUIRED OFF HOUR, OVERTIME, <br />AND NON -BUSINESS HOUR WORK AS REQUIRED TO PERT-ORM THE DEMOLITION WITHOUT <br />DISRUPTING THE BUILDING TENANTS NORMAL BUSINESS OPERATIONS. <br />II. REMOVE ALL DATA WIRING AND EQUIPMENT RACKS THAT WILL NOT BE RE -USED. <br />RELOCATE TELEPHONE DEMARC CONDUIT TO NEW LOCATION AS REQUIRED. <br />12. ALL DEMOLISHED EQUIPMENT AND WIRING SHALL BE REMOVED FROM SITE AND <br />PROPERLY DISPOSED OF OR TURNED OVER TO THE OWNER AT THE OWNER'S SOLE <br />OPTION. <br />Wall Opening Protective Materials <br />SPECIFIED TECHNOLOGIES INC R14288 SUITE 2 200 EVANS WAY SOMERVILLE, NJ 08616 USA <br />SpecSeal Putty Paris, for use with max 4-II/16 by 4-I1/16 in. flush device UL Listed metallic outlet boxes Installed with steel cover plates In i <br />and 2 h fire rated gypsum board wall assemblies framed with min 3-1/2 In. deep wood or steel studs and constructed of the materials and in <br />the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs In the Fire Resistance Directory. Installation to <br />comply with the National Electrical Code (NFPA 10). Min 3/16 in. thick moldable putty pads are to be installed to completely cover the <br />exterior surfaces of the outlet box (except for the side of the outlet box against the stud) and completely seal against the stud within the <br />stud cavity. An additional 3/16 in. thickness of putty to be formed around the connector securing the end of each electrical metallic tube or <br />conduit to the box. When used with metallic outlet boxes larger than 4 by 4 In., a ball of putty is to be installed to plug the open end of <br />each electrical metallic tube or conduit within the outlet box. When max 4 by 4 In. metallic outlet boxes are used, the ball of putty in the open <br />end of each electrical metallic tube or conduit within the outlet box is optional. 11kien moldable putty pad outlet box protective material is <br />used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on the opposite sides of the wall may be <br />less than 24 in. provided that the boxes are not installed back-to-back <br />SpecSeal Putty Pads for use with max 4 by 3-3/4 by 3 In. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carlon Electrical <br />Products and made from polyvinyl chloride, max 4 by 3-3/4 by 3 in, deep UL Listed Nonmetallic Outlet Boxes manufactured by Allied Moulded <br />Products Inc. and made from fiber -reinforced thermosetting plastic or max 4-1/16 by 3-5/6 by 3-1/8 in. deep UL Listed Nonmetallic Outlet <br />Boxes manufactured by Thomas 4 Betts Corp. and made from fiber -reinforced thermosetting plastic. Boxes shall also bear a 2 h rating under <br />the "Outlet Boxes and Fittings Classified for Fire Resistance" category in the Fire Resistance Directory. Installation to comply with the <br />National Electrical Code (NFPA 10). Boxes installed with steel or plastic cover plates. Putty pads and boxes for use in 1 and 2 h fire rated <br />gypsum board/wood stud wall assemblies constructed of the materials and in the manner specified in the Individual U300 Series Wall and <br />Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of two nailing tabs in conjunction with nails <br />supplied with the outlet box. Min 3/16 in. thick moldable putty pads are to be Installed to completely cover the exterior surfaces of the <br />outlet box (except for the side of the outlet box against the stud) including nailing tabs and completely seal against the stud within the <br />stud cavity. An additional 3/16 in. thickness of putty to be formed around the end of each nonmetallic sheathed cable at its connection to <br />the box and to extend a minimum of 1 in. from the box onto the nonmetallic sheathed cable within the stud cavity. When moldable putty pad <br />outlet box protective material is used on boxes on both sides of wall as directed, the horizontal separation between outlet boxes on <br />opposite sides of the wall may be less than 24 in, provided that the boxes are not installed back-to-back <br />FI���TIONDET,41LS�T��IC��SDETAILS�T�LIC��S <br />NOT TO SCALE <br />O 1 ELECTimICAL Si�CIFICATION5 <br />SCALE: NOT TO SCALE <br />00 <br />m N <br />o 0 o <br />N cd [� U <br />5 Z <br />N in cxd *U. <br />NCd <br />G p., 4- <br />CD• U <br />C)in c'-d <br />N t <br />ti 10 <br />o <br />~ 00 3 <br />r- <br />3ti 3 <br />O x N <br />G <br />ti o <br />tia <br />cm <br />0 <br />. <br />6 <br />• "it fLd <br />ti <br />• <br />-- 0) <br />�`' <br />• <br />D,.: <br />U) <br />L0 1 i► �= rb Ch <br />o <br />`drat <br />••� .••� _c_ca <br />•, <br />ss <br />� ..�5 <br />L <br />m <br />t <br />c <br />m <br />i <br />I) <br />-a <br />tf) <br />3 <br />LI_ <br />r <br />L- <br />M <br />O <br />O <br />75 <br />J <br />.=1 <br />(� <br />t^ <br />N <br />O <br />m <br />LL <br />m <br />W <br />- <br />N <br />ti <br />0 <br />L <br />.0 <br />F- <br />E <br />OCO:) <br />s <br />Q <br />U <br />CO <br />N <br />m <br />C <br />L <br />N <br />t <br />a <br />m <br />N <br />Date: 02. 06. 14 <br />Scale: <br />AS NOTED <br />Project <br />Mgr: MPS <br />Drawn: <br />MW <br />Job: <br />12-194 <br />Sheet <br />El <br />