<br />1 Electrical Power Plan 2 Electrical Lighting Plan
<br />Scale 1/8"=1'-0" Scale 1/8"=1'-0"
<br />POWER PLAN NOTES: LIGHTING PLAN NOTES:
<br />1O EXISTING J-BOX AND EMPTY 314" CONDUIT. EXTEND
<br />CONDUIT AS NEEDED AND RUN NEW WIRES TO NEW
<br />TENANT PANEL.
<br />O EXISTING 4 TON RTU. SHALL BE WIRED BACK TO NEW
<br />TENANT PANEL.
<br />O3 FOR POWER REQUIREMENTS TO RTU'S SEE MECHANICAL
<br />EQUIPMENT SCHEDULE ON M101 AND FOR WIRING SEE
<br />ELECTRICAL PANEL SCHEDULE ON THIS SHEET.
<br />O4 FACTORY INSTALLED POWERED CONVENIENCE OUTLET.
<br />INSTALLATION SHALL BE PER SECTION 210.63 OF THE NEC.
<br />COORDINATE WITH MECHANICAL.
<br />O5 NEW 200 AMP TENANT ELECTRICAL PANEL INSTALLED IN
<br />THE LOCATION OF THE EXISTING 2" CONDUIT STUB
<br />UP. WIRE PULLED FROM EXISTING 200 / 3 / 200
<br />DISCONNECT TO NEW PANEL VIA EXISTING CONDUIT.
<br />RUN 4#310, 1#6 GROUND IN EXISTING 2" CONDUIT.
<br />O6 EXISTING TELEPHONE CONDUIT STUB IN TO REMAIN AS IS.
<br />NO TTB OR RECEPTACLE REQ'D.
<br />O EXISTING DEDICATED RECEPTACLE FOR TTC TO REMAIN
<br />AS IS.
<br />O EXISTING HOUSE TTC TO REMAIN AS IS.
<br />O EXISTING ELEC. POWER RISER TO REMAIN AS IS.
<br />10 ALL FIRE ALARM EQUIPMENT ARE SHOWN AS REFERENCE
<br />PURPOSES ONLY. FIRE ALARM DESIGN DRAWINGS SHALL
<br />BE SUBMITTED BY TENANT BUILDOUT CONTRATOR,
<br />SIGNED AND SEALED BY STATE OF FLORIDA LICENSE AND
<br />REGISTERED ENGINEER.
<br />21 EXISTING DECORATIVE SCONCE FIXTURES SHALL REMAIN WIRED
<br />AS IS TO THE EXISTING HOUSE PANEL.
<br />22 EXISTING EXIT LIGHTS SHALL BE RE -WIRED FROM THE EXISTING
<br />HOUSE PANEL TO THE NEW TENANT PANEL.
<br />23 EXISTING REAR WALL MOUNTED LIGHT SHALL BE WIRED TO THE
<br />NEW TENANT PANEL VIA A NEW LIGHT SWITCH.
<br />LIGHTING NOTES
<br />1. VENDOR SHALL VERIFY ALL FIXTURE QUANTITIES.
<br />2. VERIFY FIXTURE LOCATION, SEE REFLECTED CEILING PLAN.
<br />3. MOUNTING HEIGHTS INDICATED ARE TO THE CENTER LINE OF DEVICE
<br />OR FIXTURE UNLESS OTHERWISE NOTED.
<br />4. ALL FIXTURES TO BE CENTERED ON 2X4 CEILING GRID U.O.N.
<br />5. ALL FIXTURES TO BE PROVIDED BY, RECEIVED, STORED & INSTALLED
<br />BY ELECTRICAL CONTRACTOR.
<br />6. ELECTRICAL CONTRACTOR SHALL SUPPLY 10% ADDITIONAL SPARE OF
<br />ALL LAMP TYPES TO BE LEFT AT JOB SITE AT END OF JOB.
<br />7. CIRCUIT BREAKERS USED AS SWITCHES IN 120V AND 277V
<br />FLUORESCENT LIGHTING CIRCUITS SHALL BE LISTED AND SHALL BE
<br />MARKED SWD OR HID.
<br />ELECTRICAL LEGEND
<br />MOUNTING HEIGHTS SHOWN ARE MAXIMUM/MINIMUM NOT ALL DEVICES SHOWN IN LEGEND ARE REQUIRED.
<br />HANDICAPPED ACCESSIBILITY STANDARDS - THEY SHALL REVIEW POWER & LIGHTING PLANS AND DETAILS FOR
<br />NOT BE ALTERED WITHOUT WRITTEN AUTHORIZATION. ITEMS WHICH APPLY TO THIS PROJECT.
<br />A®a - A®a
<br />FLUORESCENT LIGHT FIXTURE, LETTER INDICATES TYPE. SEE FIXTURE
<br />SCHEDULE. LOWER CASE SWITCH
<br />LETTER INDICATES (IF USED)
<br />At ---"a
<br />FLUORESCENT STRIP LIGHT, LETTER INDICATES TYPE. SEE FIXTURE
<br />SCHEDULE. LOWER CASE LETTER INDICATES SWITCH (IF USED)
<br />G an I=
<br />SURFACE MOUNTED LIGHT, LETTER INDICATES TYPE. SEE FIXTURE
<br />SCHEDULE. LOWER CASE LETTER INDICATES SWITCH (IF USED)
<br />0 B B
<br />INCANDESCENT OR HID LIGHT FIXTURE, LETTER INDICATES TYPE
<br />SEE LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING.
<br />Q C Q C
<br />WALL BRACKET LIGHT FIXTURE, LETTER INDICATES TYPE SEE
<br />LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING.
<br />NL
<br />NIGHT LIGHT FIXTURE (NL)
<br />® X
<br />EXIT LIGHT (SHADE AREA INDICATES DIRECTION) LETTER INDICATES TYPE
<br />SEE LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING.
<br />BATTERY POWERED EMERGENCY LIGHT
<br />.�
<br />TRACK LIGHTING AND TRACK. FOR INFORMATION ON TRACK SEE
<br />LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING.
<br />WALL WASHER FIXTURE. (SHADE AREA INDICATES DIRECTION) SEE
<br />LIGHT FIXTURE SCHEDULE TO CONFIRM TYPE AND MOUNTING.
<br />SINGLE POLE SWITCH, LOWER CASE LETTER INDICATES LIGHTS
<br />CONTROLLED. LETTER NOT SHOWN IF SELF EVIDENT. MOUNT
<br />a
<br />48" A.F.F. U.O.N.
<br />F
<br />SINGLE POLE SWITCH. FAN CONTROLLER, MOUNT 48" A.F.F. U.O.N.
<br />3
<br />3-WAY SWITCH, FOR CONTROLLING LIGHTS FROM TWO DIFFERENT POINTS.
<br />®
<br />TWO GANG FLOOR OUTLET BOX. ONE QUADPLEX ISOLATED GROUND
<br />RECEPTACLE AND ONE COMPUTER OUTLET.
<br />Q.
<br />WIREMOLD-WALKER INFLOOR SYSTEMS. RC4 FLUSH QUAD POKE
<br />THRU SERIES WITH FOUR MULTIMEDIA COMMUNICATION LOCATIONS
<br />Q�
<br />WIREMOLD WALLSOURCE MULTIPLE SERVICE BOX.
<br />Qi
<br />QUADPLEX FLOOR RECEPTACLE OUTLET.
<br />QUADPLEX RECEPTACLE OUTLET.
<br />QUADPLEX RECEPTACLE OUTLET MOUNTED ABOVE COUNTER TOP U.O.N.
<br />OO
<br />DUPLEX FLOOR RECEPTACLE OUTLET.
<br />DUPLEX RECEPTACLE, MOUNT 18"AFF LION
<br />@: DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER HEIGHT U.O.N.
<br />�GFI GROUND FAULT INTERRUPTER RECEPTACLE, LEVITON #6898-I, MOUNT
<br />ABOVE COUNTER HEIGHT U.O.N.
<br />I.G. DUPLEX RECEPTACLE, ISOLATED GROUND TYPE, LEVITON #5362-IGI
<br />MOUNTED ABOVE COUNTER HEIGHT. U.O.N.
<br />I.G.
<br />DUPLEX RECEPTACLE, ISOLATED GROUND TYPE, LEVITON #5362-IGI
<br />MOUNT AT 18" AFF UON
<br />DUPLEX RECEPTACLE, MOUNTED ABOVE STOREFRONT WINDOWS
<br />SINGLE RECEPTACLE, MOUNTED AT HEIGHT NOTED ON PLANS
<br />®
<br />SPECIAL PURPOSE RECEPTACLE OUTLET
<br />O
<br />JUNCTION BOX (FLUSH MOUNT IN FINISHED AREAS U.O.N.)
<br />LIGHTING, POWER, FACP PANELBOARD OR TELE. TERM. CABINET.
<br />MSBIMDP
<br />MAIN SWITCHBOARD OR MAIN DISTRIBUTION PANEL
<br />CONDUIT CONCEALED IN WALL, BELOW SLAB, OR ABOVE CEILING.
<br />CONDUIT EXPOSED ON WALL OR CEILING.
<br />LIGHT FIXTURE SCHEDULE
<br />TYPE
<br />MANUFACTURER
<br />CATALOG NO.
<br />VOLT
<br />LAMPS
<br />MOUNTING & OPTION
<br />NOTE
<br />A
<br />DAYBRITE
<br />2TG8-3-32-01-UNV-1/3-EB
<br />120
<br />(3) 32W T8
<br />GRID MOUNTED
<br />1-3,5.6
<br />C
<br />NITE BRITES
<br />WCR-050-M-MT
<br />120
<br />-
<br />EXISTING TO REMAIN
<br />EM
<br />BEGHELLI
<br />XLPS1
<br />120
<br />-
<br />WALL MTD 9-0"AFF
<br />2,4-6
<br />X
<br />BEGHELLI
<br />VA4-RSA
<br />EXISTING TO REMAIN
<br />ALTERNATE FIXTURES SHALL BE BY "COOPER INDUSTRY", "LITHONIW, "GENLYTE", "HUBBELL" AND "THOMAS INDUSTRY'.
<br />ALL FIXTURE SUBSTITUTIONS MUST BE EQUAL OR BETTER AND MUST BE SUBMITTED FOR APPROVAL (SEE GENERAL FIXTURE NOTES).
<br />GENERAL FIXTURE NOTES: 4. ALL EMERGENCY, EXIT AND NIGHT LIGHT FIXTURES SHALL
<br />BE CONNECTED AHEAD OF LOCAL SWITCHES. UNLESS
<br />1. ALL FLUORESCENT LIGHTING FIXTURES SHALL HAVE ENERGY OTHERWISE NOTED.
<br />SAVING LAMPS AND ELECTRONIC BALLASTS.
<br />2. PROVIDE NECESSARY MOUNTING HARDWARE AND ACCESSORIES 5. ALL ALTERNATE FIXTURES SHALL BE SUBMITTED FOR
<br />PRIOR APPROVAL, SEE SPECIFICATIONS.
<br />FOR ALL FIXTURES.
<br />3. PROVIDE .125 MIN. THICK LENSES FOR FLUORESCENT FIXTURES. 6. CONTACT SESCO LIGHTING (407) 629-6100 DAN SCHULMAN
<br />FLEXIBLE CONDUIT NOT TO EXCEED 6 FEET IN LENGTH
<br />A•1,3 CONDUIT RUN CONCEALED IN WALLS BELOW SLAB, OR CEILING SPACES.
<br />ARROWS INDICATE HOMERUN. SMALL HASHMARKS INDICATE NUMBER OF
<br />HOT CONDUCTORS, AND LARGE HASHMARK INDICATES NEUTRAL.
<br />SUBSCRIPT INDICATES PANEL AND CIRCUIT NUMBERS. GROUND
<br />CONDUCTOR REQUIRED IN ALL CONDUITS BUT NOT INDICATED.
<br />A-37:39:41 SUBSCRIPT INDICATES PANEL -AND NUMBERS WITH COLONS
<br />INDICATE 2 OR 3 POLE CIRCUITS.
<br />MANUFACTURER: SQUARE Q'NO'
<br />MAIN BREAKER:
<br />MAIN LUGS: 200A
<br />K.A.I.C.:
<br />MOUNTED: SURFACE
<br />Lo
<br />DISCONNECT SWITCH
<br />100/3/60
<br />DISCONNECT DESIGNATION (SIZE/POLESIFUSE) "NF" INDICATES
<br />NON -FUSED; "DE" INDICATES DUAL ELEMENT FUSES.
<br />EF
<br />MOTOR PERMANENTLY CONNECTED WITH FLEXIBLE CONDUIT
<br />(HORSEPOWER OR EQUIPMENT INDICATED)
<br />THERMOSTAT. PROVIDE SINGLE GANG BOX WITH 1/2" C. STUBBED
<br />OT
<br />INTO CEILING SPACE, MOUNT 60" A.F.F. U.O.N. (COORDINATE WITH
<br />MECHANICAL DRAWINGS PRIOR TO ROUGH -IN)
<br />TELEPHONE WALL OUTLET, PROVIDE SINGLE GANG BOX WITH 3/4"
<br />CONDUIT WITH PULL WIRE AND INSULATING BUSHING STUBBED INTO
<br />CEILING SPACE. MOUNT BOX 18" A.F.F. U.O.N.
<br />0
<br />COMPUTER OUTLET. MOUNT BOX @ 18' A.F.F. U.O.N.
<br />O
<br />CEILING SPEAKERS MTD. AND WIRED PER AEI MUSIC NETWORK,
<br />INC. (800-274-9298)
<br />OD
<br />CEILING MTD. SENSOR DEVICE
<br />❑F
<br />FIRE ALARM PULL STATION: EDWARDS #SIGA-270
<br />HORN/STROBE: EDWARDS #692-BA -HSW
<br />OSMOKE
<br />DETECTOR: EDWARDS MSIGA-PS
<br />OHEAT
<br />DETECTOR: EDWARDS #SIGH HRS
<br />FACP PANEL: SIEMEN CYRBURUS MODEL #PXL
<br />EF BATH ROOM FAN LIGHT (BROAN S150L)
<br />ABBREVIATIONS
<br />ACC-CU
<br />CONDENSING UNIT
<br />NF
<br />NON -FUSED
<br />AFF
<br />ABOVE FINISH FLOOR
<br />NIC
<br />NOT IN CONTRACT
<br />AFG
<br />ABOVE FINISH GRADE
<br />NL
<br />NIGHT LIGHT
<br />A/H-AHU
<br />AIR HANDLING UNIT
<br />NTS
<br />NOT TO SCALE
<br />C/T
<br />CURRENT TRANSFORMER
<br />OS
<br />OCCUPANCY SENSORS
<br />DE
<br />DUAL ELEMENT FUSE
<br />PC
<br />PULL CHAIN
<br />EC
<br />EMPTY CONDUIT
<br />RTU
<br />ROOF TOP UNIT
<br />E/F-EF
<br />EXHAUST FAN
<br />TTB
<br />TELEPHONE TERMINAL BOARD
<br />EG
<br />EQUIPMENT GROUND
<br />TTC
<br />TELEPHONE TERMINAL CABINET
<br />EM
<br />EMERGENCY LIGHT
<br />TYP
<br />TYPICAL
<br />EWC
<br />ELECTRIC WATER COOLER
<br />UON
<br />UNLESS OTHERWISE NOTED
<br />EWH
<br />ELECTRIC WATER HEATER
<br />VTC
<br />VIA TIME CLOCK
<br />EX
<br />EXISTING DEVICE TO REMAIN
<br />WP
<br />WEATHERPROOF
<br />FACP
<br />FIRE ALARM CONTROL PANEL
<br />X
<br />EXIT LIGHT
<br />GFI
<br />GROUND FAULT INTERRUPTER
<br />IG
<br />ISOLATED GROUND
<br />LB
<br />LOCK BREAKER
<br />NOTE: MOUNTING HEIGHTS NOTED ARE TO BOTTOM OF DEVICE SHOWN UON
<br />NAME: PANEL'W
<br />3 PHASE
<br />4 WIRE PROJECT NAME: ZEPHYR COMMONS
<br />120/208 VOLTS PROJECT NUMBER: 206319
<br />FED FROM: EXISTING WIREWAY
<br />0
<br />E
<br />S
<br />CKT
<br />NO
<br />IDENTIFICATION
<br />WIRE/COND
<br />C
<br />O
<br />D
<br />E
<br />LOAD/PHASE (KVA) CIRCUIT BREAKER
<br />C
<br />LOAD/PHASE (KVA) 0
<br />D
<br />E
<br />WIRE/COND
<br />IDENTIFICATION
<br />CKT
<br />NO
<br />0
<br />E
<br />S
<br />A B C TRIP
<br />P
<br />P
<br />TRIP
<br />A B C
<br />1
<br />1
<br />EMER. & NIGHT LGTS
<br />2#12, 1#12G, 3/4"C
<br />L
<br />0.22 20
<br />1
<br />1
<br />20
<br />1.25 L
<br />2012, 1#12G, 3/4"C
<br />TENANTSIGNAGE
<br />2
<br />3
<br />3
<br />EXT. REAR LGT
<br />2#12, 1#12G, 3/4"C
<br />L
<br />0.05 20
<br />1
<br />1
<br />20
<br />1.27 R
<br />2#12, 1#12G, 3/4"C
<br />SHOW WINDOW
<br />4
<br />4
<br />5
<br />2x4 LGTS
<br />2#12, 1#12G, 3/4"C
<br />L
<br />1.14 20
<br />1
<br />1
<br />20
<br />1.27 R
<br />2#12, 1#12G, 3/4"C
<br />SHOW WINDOW
<br />6
<br />7
<br />1
<br />1
<br />20
<br />0.75 R
<br />2#12, 1#12G, 3/4"C
<br />EWC
<br />a
<br />9
<br />1
<br />20
<br />0.54 R
<br />2#12, 1#12G, 314"C
<br />RECEPTACLES
<br />10
<br />11
<br />1
<br />20
<br />0.72 R
<br />2#12, 1#12G, 3/4"C
<br />RECEPTACLES
<br />12
<br />13
<br />14
<br />15
<br />16
<br />17
<br />18
<br />19
<br />20
<br />21
<br />22
<br />23
<br />24
<br />25
<br />28
<br />27
<br />28
<br />29
<br />30
<br />31
<br />32
<br />33
<br />34
<br />35
<br />36
<br />37
<br />3
<br />35
<br />3.02
<br />3,02 C
<br />3.02
<br />408, 1010G, 1"C
<br />4 TON RTU
<br />38
<br />2
<br />39
<br />q0
<br />41
<br />42
<br />1 U.c 1 U. -1 1 -1. -1 1
<br />TOTAL KVA PHASE A: 5.24
<br />TOTAL KVA PHASE B: 4.88
<br />TOTAL KVA PHASE C: 6.15
<br />LIGHTING (L;
<br />RECEPTACLES (R;
<br />A/C HEATING (Ff,
<br />A/C COOLING (C,
<br />KITCHEN EQUIPENT (K;
<br />LARGEST MOTOR (M;
<br />OTHER (0;
<br />COW LOAD
<br />(KVA)
<br />DI M4N7
<br />FACTOR
<br />ND
<br />QAD
<br />(KVA)
<br />2.66
<br />1.25
<br />3.325
<br />4.55
<br />NEC
<br />4.55
<br />0
<br />1.00
<br />0
<br />3.02
<br />1.00
<br />3.02
<br />0
<br />—RE _C
<br />0
<br />0
<br />1.25
<br />0
<br />0
<br />1.00
<br />0
<br />1 a.0 1 4.a I mu 1
<br />TOTAL CONNECTED KVA: 16.27
<br />TOTAL CONNECTED AMPS: 45.16
<br />TOTAL DEMAND KVA: 10.90
<br />TOTAL DEMAND AMPS: 30.24
<br />GENERAL
<br />SQUARE FOOT: LIGHTING LOAD: VAISF
<br />" LIGHTING DEMAND LOAD IS BASED ON THE LARGER OF THE TWO
<br />(CONNECTED VS. TABLE 220.3a, NEC 2002.)
<br />"LARGER A/C LOAD: 3.02 KVA
<br />(TL) LENGTH 0 KVA
<br />U
<br />c
<br />w
<br />c
<br />0
<br />Q_
<br />O
<br />�L_
<br />�/ W
<br />�ZO
<br />VQM
<br />._V��
<br />�0LL
<br />w Ema
<br />'L°;�
<br />w �MH
<br />I
<br />V
<br />cn
<br />c
<br />0
<br />E
<br />E
<br />0
<br />U
<br />L
<br />i
<br />Q
<br />Nm
<br />Co
<br />J
<br />cn m
<br />V Q
<br />0 u-
<br />♦♦cu
<br />VJJJ
<br />00 J
<br />w
<br />�Q1:
<br />Cox
<br />W N
<br />��N
<br />a
<br />cu
<br />•
<br />J
<br />c
<br />cu
<br />L
<br />0
<br />a-
<br />vi
<br />V
<br />U)
<br />cD
<br />c
<br />0)
<br />J
<br />cu
<br />V
<br />� V
<br />w
<br />CD
<br />rn
<br />0
<br />0
<br />=
<br />N
<br />nppt
<br />�
<br />� N
<br />0
<br />'� a
<br />�LL
<br />ru
<br />w
<br />N
<br />J
<br />N
<br />zuj
<br />rn�
<br />N
<br />S
<br /><
<br />w
<br />0
<br />uj
<br />E101
<br />tCUIT BREAKER 3) VIA TENANT TIME CLOCK 4) NFPA 70-M 240.83(D) COMPLIANT