ELECTRICAL SPECIFICATIONS
<br />Common Electrical Abbreviations
<br />ERIC J. SAFFRAN
<br />ARCHITECT
<br />GENERAL
<br />Before submitting a bid, the Contractor shall visit the site and familiarize himself
<br />with the existing conditions. The Contractor shall make such ac justments m work as
<br />required by the actual conditions and inform the Engineer ofRecord of any discrepancies
<br />between achral conditions and design documents.
<br />Coordination, Conflict and Changes: The Contractor shall coordinate his work with
<br />other trades, particularly in common areas such as mechanical moms, and chases where
<br />multiple trades will be working. In the event ofa coo ic; the Architect shall decide which
<br />equipment shall be relocated regardless of which was installed first: g during this
<br />coordination, it is discovered that necessary or desirable changes should be made, advise
<br />the Engineer and secure his approval in writing. Where- drawings appear to cou ict,
<br />provide the more expensive quality or quantity.
<br />The Contractor shall base his proposal on the materials specified herein and in the
<br />drawings. Reference to a particularptvduct by Manuficturw, trade name, or catalog
<br />number establishes the minimum standard ofmaterial and equipment required for this
<br />installation. It is not intended to exclude products of similar• design and equal quality.
<br />Where two or more standards are listed, the choice shall be by the Contractor. The
<br />Engineer reserves the sole right to decide the equality ofmateriais proposed for use in lieu
<br />of those specified: Permission to substitute shall be obtained prior to bid in accordance
<br />with the Architect's instructions.
<br />Warkk under this item of the Contract shall include providing all labor, material,
<br />equipment; supplies, and services necessary to install a complete and operational electrical
<br />system, both nitaw and exterior, as shown in these plans.
<br />All material shall be UL listed as approved and shall be new
<br />The Contractor shall comply with applicable local htws, the latest edition of the NEC
<br />where not in conflict with those laws, and the rules of the local utility company, Americans
<br />with Disabilities (ADA) Act, latest edition of the building code adopted by the Authority
<br />Having Jurisdiction over this work, NEMA standards, UL standards, ANSI standards, and
<br />the Manufacturer's recommendations regarding their product.
<br />The Contractor shall obtain and pay for all required permits. The Contractor shall
<br />pay all fees associated with the scope of work as outlined in these documrews. Auer
<br />completion of the work, the Contractor shall submit certificate of final inspection and
<br />approval from the local electrical inspector certifying that the installation complies with all
<br />applicable regulations governing same.
<br />The Contractor shall warrant the entire electrical system to be in proper working
<br />order Replace at no additional charge all work and/or material which may develop defects,
<br />excluding ordinary wear and tear and improper handling, for a period of one year from the
<br />date ofaccepmace.
<br />RACEWAYS
<br />Galvanized Rigid Conduit shall be hot -doped galvanized steel inside and outside
<br />including threaded cells. Where field cut and threaded, exposed surface shall be treated
<br />with a galvaniziaglaint. Conduit shall be manuAwtmed by Allied Tube, Wheatland,
<br />Pittsburgh Staorlarrd, Republic, or Triangle.
<br />Galvanized Rigid Coated Conduit shall be coated inside and outside with PVC coating
<br />and be ETL listed.
<br />Intermediiste Metal Conduit shall be hot galvanized steel with a corrosion resistant
<br />coating. Where field cut and breaded, exposed surface shall be treated with a galvanizing
<br />paint Conduit shall be manufactured by Allied Tube, Wheatland, Pittsburgh Steel, Republic,
<br />or Triangle. No Quick connect couplings are allowed
<br />Electrical Metallic Tubing shall be hot galvanized steel with a corrosion resistant
<br />coating. Conduit shall be msnufactu rd by Allied Tube, Wbestlam4 Pittsburgh Steel
<br />Republic, or Triangle. Fittings shall be set screw type fittings. No quick connect
<br />compression figs are allowed
<br />Rigid non metallic conduit (PVC) shall be heavy wall schedule 40 polyvinyl chloride
<br />as manufachred by Carlos. Condectm and fittings shall be by the same manufacturer:
<br />Liquid-tigbt ffe:nble metal conduct shall be type UA with writable fittings as
<br />manufactued by Anaconda.
<br />Flexible metal conduit shall be used for final connection to vibrating machinery and
<br />finer junction box to ligh fixture. Run shall be as short as possible but no more than 72 ".
<br />Flexible metal conduit shall be as manufactured by AFC.
<br />Conduits shall be sized not smaller than as shown or in accordance with Table 1,
<br />Chapter 9 of the NEC, whichever is larger:
<br />Conduits shall be supported and substantially fastened to structural members at
<br />intervals of no more than 8 fret Supports and fasteners shall be of a type approved for the
<br />intended use and appropriate for the application Conduit shall be run concealed in the
<br />structue as mucb as practicable. When conduit must be exposed, the conduit shall be
<br />instilled with rums atfierparallel orperpendicular to structural members, walls, or vertical
<br />intersections. Right angles shall consist of cast metal fittings or symmetrical beads. Co ndurt
<br />shall be kept a minimum of 6" away from flues, hot water pipes, steam pipes, or other heat
<br />producing devices. Conduit which has been pushed or deformed due to improper bending or
<br />nushandim shall not be installed Conduit shall be pit square, threaded, reamed smooth,
<br />and drawn up 40L Conduit shall be securely ftstened to all abeet metal outlets, cabinets,
<br />junction and pull boxes with locknuts and bushings. Provide bushings at each end of the
<br />run. Where spare runs of conduit are mi icated, provide a pull wire in each raceway and cap
<br />each end to prevent the collection of debris. Conduit systems shall be installed complete
<br />prior to pulling conductors. Conduit shall be installed as follows:
<br />Underground - PVC with GRC sweep bends for the vertical turns
<br />Exposed Exterior -GRC, IMC
<br />Exposed Interior - GRC, )MC, EMT (only above 10' AFF )
<br />Concealed Interior - GRC, IMC, EMT, MC/AC Cable ( only if acceptable to
<br />heAHJ)
<br />No ENT ( "Sunuf tube') allowed.
<br />WIRE AND CABLE
<br />Conductors shall be soli drawn copper conforming to ASTM standards runless
<br />Ahmunum a specifically indicated on the plans. The maaufscture's name, wire size, and
<br />insulation type shall be permanently marked on the conductor jacket at regular intervals in a
<br />legible manner. All conductors; shall be labeled at each termination and in all junction boxes
<br />with cable tags. Conductors shall be as follows:
<br /># 12 AWG - #10 AWG TTHIN or THHW Stranded or solid
<br />#8 AWG TRW or TTHIW Stranded
<br />#6AWG and huger THW, THHW orXHHHW Stranded
<br />Riser General Notes:
<br />Conductors shall be color coded as follows:
<br />12012401Ph 1201209 or 1201240 3 Ph
<br />2771480 3 Ph
<br />Phase A
<br />Black Black
<br />Yellow
<br />Phase B
<br />Blue Blue
<br />Orange
<br />Phase C
<br />N/A Red
<br />Brawn
<br />Neutral
<br />White White
<br />White or Grey
<br />Ground
<br />Green Green
<br />Green
<br />Any "High Leg" Phase Shall Be Marked with Orange Tape.
<br />Wire and cable shall be as manufactured by Southwire, PWC, Carol, Triangle, Anaconda
<br />Splices shall be made only in approved locations as follows: #12 AWG - wirenuts
<br />#10AWG and larger - compression or camp type slices with insulating hest shrink
<br />gym&
<br />Fixture wires shall be SF-1 or SF-2 600V minimum #14A WG.
<br />AC and MC cables are acceptable where approved by the Authority Having
<br />Jurisdiction.
<br />BOXES
<br />Outlet boxes used in concealed work shall be galvanized or sheradized sheet steel
<br />boxes and be adequately sized to accommodate the devices and conductors to be installed
<br />(minion 1-112" deep ). Boxes dr tbeirplaster rings shallbe mounted Bush with the
<br />finished surface and square with the surfnee. Boxes shall be sized in accordance with
<br />NEC Article 314 and be appropriate for the environment in which installed Ceiling
<br />boxes shall be 4" octagonal boxes 1-1)2" deep minimum Boxes intended fen mounting
<br />ceiling fans shall be rated a minimum of 1001bs weight capacity. Boxes shallbe as
<br />manufacdnad by Appleton, Raco, or Steel City.
<br />Exposed outlet boxes shall be Crouse -Hinds 7jjw FS or FD or equal.
<br />Sectional type boxes shall not be installed in masonry or concrete walls.
<br />L,71 1Z ► �
<br />Devices shall be as indicated in the Electrical Legend and as shown on the plans.
<br />Devices manufwan d by Arnow -Hart, Bryan; or Hubbell and listed in NEMA
<br />comparative lists as similar type and quality are approved Finish for devices and cover
<br />plates shall be as specified by the Architect.
<br />The plans slow apprroximate locations for devices only. The Cwhaictor shall
<br />familiarize himself with arrhitoctral and structural details and the rough -in requirements
<br />of the equipment to be installed to determine the device location. Devices shall be
<br />installed at umifurm heights throughout the installation. Devices installed above
<br />countertops shall be installed to avoid eouffict with the backsphusk cabinets, and/or
<br />equipment. The final location of devices shall be verified by the Architect.
<br />Pull boxes shall be installed in long runs of conduit: Pull boxes shall be
<br />galvanized sheet steel construction, sized aeeordilag to NEC Article 314, and installed in
<br />an aoecssible location.
<br />SAFETY SWITCI w
<br />Disconnect sanity switches shall be heavy dirty type 600V or 250V , fused or
<br />non -fused as indicated on the plans with the number ofpoles as indicated on the plans.
<br />NEMA enclosure type shall be as indicated on the pleas Switch mechanism shall b
<br />"quick make - quick break" type ooasbnrcbion
<br />The Contactx shall provide mounting frames for switches that can not be securely
<br />fastened to a solid structure. Frames shall consist ofgalvanized stool chi are/ set in
<br />concrete footings. Hardware (ours, bolts, washers, etc) shall be stainless steel.
<br />Switches installed as service entrance disconnects shall be labeled as such and be
<br />provided with all accessories and appurtenances required for a service entrance disconnect
<br />SERVICE
<br />Coordinate with Utility to provide a service as indicated on the plans. Provide all
<br />material and labor not supplied by the Utility in order to produce a complete to and operable
<br />electrical service complying with NEC and Utility Company regulations.
<br />Obtain metering equipment from Utility and install in compliance with Utility
<br />Companyregullstiorts.
<br />Unless Noted Otherwise, the transformer at the Service Entance will be provided
<br />by the Utility.
<br />GROUNDING
<br />The Contractor shall provide complete system and equipment pumidrng systems
<br />Iudbig coadhuctom o�Mm Brood rods, pound buusses, ink all etcfor the service
<br />entrance ground, groumcting ofelech ical equipme4 process egiq= n; building steel, or
<br />other itms indicated on the drawings. The grounding system shall be installed in
<br />accordance with NEC Article 250 and as detailed in the plans.
<br />Undiergnoumd connections and connections to building steel shall be exothermic
<br />weld. Exposed concoctions shall be irreversible crimp type connections.
<br />A green insulated ground conductor as indicated on the plans (nzimimurn size per
<br />NEC Table 250.122 ) shall be metalled in each raceway and with each cable.Isolated
<br />Ground conductors shall be green with yellow dace.
<br />DRY TYPE TRANSFORMERS
<br />Transformers of the size and type covered in UL 506 shall be so listed and labeled,
<br />ie. Transformers 600V up to and inchding 167 kVA single phase and 500 kVA three
<br />phase. Three phase transformers up to 9 kVA shall be Class 180 Insulation System with
<br />80 C Rise. Single Phase transformers and three phase transformers 15 kVA to 500 kVA
<br />shall be Class 220 kwiston System with 115 C rise. Cores shall be designed so dot
<br />maximum fiuur demsitim are substantially below saturation level. The core volume shall
<br />allow efficient operation at 109/9 above the highest tap voltage. All laminators shall be
<br />come pasted or annealed, fire of buns and firmly butted The core laminations must be
<br />tightly clamped and compressed to provide quiet operation. The entire core and coil
<br />assembly must be pedried by hen; napregnsted with silicome varnish, and cured at a
<br />minimum of350 F to reduce hotspots and seal out moisture. Coils must be protected with
<br />an outer layer ofg1m tape or similar insulation. Transformers 15kVA and larger shall
<br />have NEMA standard taps. All tandbimers shall be quiet type. Care and coil assemblies
<br />are to be mounted an rubber vibration isolators designed to specifically reduce 120 He
<br />sound and multiple harmonics. Enclosure temperature rise shall not exceed 40 C rise
<br />above ambient Windings shall be copper Transformers shall be miuuftcdmod by Square
<br />1) A fault current ofLsc-45,242A was obtained from the u duty.
<br />IT size or fault current is differen4 notify Architect immediately for resolution
<br />2) Notify Architect Immediately to obtain a resolution ifany discrepancy between field condlitidmns and conduction documents that impacts installation is discovered.
<br />3) Seal Penetrations to Insmre Integrity ofBudding Envelope. Coordinate with Architect
<br />NOTICE TO CONTRACTORS:
<br />ALL CONTRACTORS PRIOR TO BID SUBMISSION PROCESS SHALL VISIT
<br />PROPOSED WORK SITE AND FIELD VERIFY ALL EXISTING CONDITIONS.
<br />ANY CONDITIONS THAT DIFFER FROM THAT SHOWN ON THESE PLANS
<br />SHALL BE REPORTED TO ARCHITECT/ENGINEER SO THAT NEW AND
<br />REVISED BID DRAWINGS OR INFORMATION MAY BE ISSUED. MODIFICATIONS
<br />TO SCOPE OF WORK WHICH RESULTS FROM CONTRACTORS NEGLECT
<br />TO VISIT THE SITE PRIOR TO SUBMITTING BID, SHALL BE THE CONTRACTORS
<br />SOLE RESPONSIBILITY.
<br />E r I
<br />MOTORS
<br />Motors installed under this section shall be TEFC premium efficiency motors
<br />suitable for duty in the environment in which they are installed
<br />The Contractor shall verify the correct rotation of all motors in the prvjec; whether
<br />installed under this section or another
<br />PANHXOARDS
<br />Paaelboards shall have the number ofphases and wires as indicated on the
<br />panel acbedule. The NEMA enclosure type shall be as noted on the panel schedule.
<br />Pandboards shall have copper buss, 100% rated neutral with set screw connections,
<br />and grand buss with set screw connection The panel box shall not be less than 20
<br />inches wide and be Abritated from galvanized orgalvannea[ed steel. Boxes shall be
<br />constivctad with minimum wire bending and gutter dimensions as required by UL and
<br />NEC. Tire Box shall have a separate UL label. All miencis willbe factory
<br />assembled and braced fora symmetrical fault current as indicated on the panel
<br />schedule C'fmuit breakers shall be replaceable without disdubing adjacent units, and
<br />without drifting or tapping. All circuit breakkerconnections shall be m a hole tapped
<br />by the manufacturer. Circuit breakers shall have common tie trip handles where
<br />required. Field ties are not acceptable. Circuit breakers shall have visible trip
<br />indication. PAndboards shall be famished with legible, typed panel directories
<br />acemaidy identifying the load each circuit breaker saver. Panelboards shall be as
<br />manufactured by Square D, Siemens, GE, or Cuder Hammer
<br />LIGHT FIXTURES
<br />Furnish and install fixduts as indicatod in the Light Fixture Schedule. Catalog
<br />numbers indicate base unit: 77w Contra shall fumish all escutcheon plates, p!asw
<br />rings, and plates, hanging chains, stems, and other appurtenances necessary for a
<br />cOmpklae installation. The Contractor shall match the voltage of the fixture to the
<br />voltage of the desigaatod circuit
<br />The Engineer reserves the sole right to determine the quality of any fixture
<br />proposed for use in lieu of those specified
<br />]matures shall be supported from structure Where installed in lay in acoustic
<br />tile ceiling, fixtures shall be supported from structure by two diametrically opposed
<br />cornerx
<br />Lamps shall be as manukwhu ed by Sylvania, Phillips, or GE.
<br />Fluorescent lamps shall be cool whit; unless noted otherwise.
<br />Fluorescent ballast shall be high efficiency, low temperature electronic ballasts with
<br />less than 10% T HD unless noted otherwise. Ballasts shall be manufactured by Sylvania,
<br />Advaoae, or GE. Emergency ballasts shall be manufactured by Bodine.
<br />Match the fixture tin to the surface nVon which the fixture is installed
<br />Recessed fixtures shall be IC noted fixtures unless noted otherwise Recessed
<br />fixtures installed in fire rated assemblies shall be provided with a UL listed method of
<br />instillidom to maintain the foe rating of the assembly as designated in the Architectural
<br />Plans.
<br />Recessed f xtums installed in the building envelope shall be provided with an
<br />approved method of installation toprevent air migration through the opening or fixture m
<br />accordance with the latest version of the Energy Code.
<br />LABELLING
<br />Provide engraved phenolic labels white 112" high letters on black background for
<br />each pnoelboard>, loadexmter, disconnect switch, service main, etcto identify the
<br />equipment served by the device or equipment
<br />FIRE RATED SEALS
<br />Provide a UL approved fine seal for each and everypenetration of a fire rated
<br />assembly ( wal), ceiling; and/or Door) in order to maintain the fire rating of the assembly
<br />as indicated in the AmIth ectural plans. Do not install devices within 6" of each other
<br />back to back in any fire rated assembly.
<br />TELEPHONE
<br />Contractor shall coordinate with local utility for exact telephone service
<br />roquirameats. The Contractor shall provide a Telephhone Termination Cabin; sized as
<br />indicated on the plans, for mounting telephone equipment Provide a #6 A WG ground
<br />fain the backboard to the main service ground. Leave s minimmn 6ofslack at the
<br />board for termination.
<br />CATV
<br />Contra shall coordinate with local utility for exact cable television service
<br />requirements. The Czatrntor shall provide an AC grade plywood backboard, sized as
<br />indicated on the plans, treated with fine retardant paint fur mounting cable television
<br />equipment Provide a #6 AWG ground firm the backboard to the main service ground.
<br />Leave a minimum 6' of slack at the board for termination
<br />A, Amp
<br />Amperes
<br />EQ
<br />Equal, Equipment
<br />SBC
<br />Standard Building Code
<br />AC
<br />Alternating Curren; Armored Cable
<br />EQUIP
<br />Equipment
<br />SH
<br />Sheet
<br />ACT
<br />Above Counter Top
<br />EX
<br />Existing
<br />SW
<br />switch
<br />ADA
<br />American's with Disabilities Act
<br />FA
<br />Fire Alarm
<br />TEL
<br />Telephone
<br />AF
<br />Amp Fuse
<br />FAAP
<br />Fine Alarm Annuciatvr Panel
<br />UG
<br />Undwgroumd
<br />AFF
<br />Above Finished Floor
<br />FRCP
<br />Fine Alarm Cembrol Pawl
<br />UL
<br />Underwriters Laboratory
<br />AFG
<br />Above Finished Grade
<br />FIX
<br />Fixture
<br />UNO
<br />Unless Noted Otherwise
<br />AHU
<br />Air Handling Unit
<br />FL
<br />Floor
<br />V
<br />Volt
<br />AFC[
<br />Arc Fault Circuit Inie7rupter
<br />FU
<br />Fused
<br />W
<br />Wire
<br />Al
<br />Aluminum
<br />GFCI
<br />Ground Fault Circuit Interrupter
<br />WP
<br />Weatherproof
<br />ANSI
<br />American National Standards Institute
<br />GFI
<br />Ground Fault (Circuit] Inoetrupter
<br />)0;11M
<br />Transformer
<br />Approx
<br />Approximately
<br />GRC
<br />Galvanized Rigid Steel Conduit
<br />Arch
<br />Architect
<br />HP
<br />Horsepower, House Panel
<br />ASHRAE
<br />American Society ofHeating, Refrigeration and Air -Conditioning Engineers
<br />HZ
<br />Hertz
<br />AWG
<br />American Wire Gauge
<br />IAW
<br />In Accordance With
<br />BD
<br />Board
<br />IBC
<br />Intemadacal Building Code
<br />BLDG
<br />Building
<br />IEEE
<br />Institute of Electrical and Mecironies Engineers
<br />C
<br />Condui; Centigrade, Celsius
<br />IMC
<br />Intermediate Metallic Conduit
<br />C&P
<br />Corp dt Plug
<br />ISA
<br />Instrument Society ofAmerica
<br />C/L
<br />Cemteriine
<br />JB
<br />Junction Box
<br />CAB
<br />Cabinet
<br />KAIC
<br />Kilo-Ampew Iotemnrpting Capacity
<br />CAP
<br />Capacity
<br />KVA
<br />Kilo Volt Ampere
<br />CB
<br />Circuit Breaker
<br />KVAR
<br />Kilo Volt -Ampere Reactive
<br />CKT
<br />Circuit
<br />KW
<br />Kilo Watt
<br />CLG
<br />Ceiling
<br />KWH
<br />Kilo Wan Hour
<br />COL
<br />Colulmn
<br />MC
<br />Metallic Cable
<br />Cond
<br />Conduit
<br />MCB
<br />Main Circuit Breaker
<br />CONN
<br />Connection
<br />MECH
<br />Mechanical
<br />CONT
<br />Continua, Continuation
<br />MISC
<br />Miscellaneous
<br />CPT
<br />Control Power Transformer
<br />Mw
<br />Man Lug Only
<br />CT
<br />Current Transformer
<br />AM
<br />Motor Rated Switch
<br />Cu
<br />Copper
<br />MT O
<br />Mounted
<br />DIC
<br />Disconnect Switch
<br />MTR
<br />Mom
<br />DET
<br />Detail
<br />NC
<br />Nn maily Closed
<br />DF
<br />Drinking Fountain
<br />NEC
<br />National Electric Code
<br />DN
<br />Down
<br />NEMA
<br />National Electrical Mmufacdrar's Association
<br />DWG
<br />Drawing
<br />NF
<br />Nam -Fused
<br />EA
<br />Each
<br />NFPA
<br />National Fire Protection Association
<br />EC
<br />Empty Conduit; Electrical Contractor
<br />NMC
<br />NonMetallic Cable, NonMegsllic Conduit
<br />EDF
<br />Electric Drinking Fountain
<br />NO
<br />Number, Normally Open
<br />EF
<br />Exhaust Fan
<br />NTS
<br />Not To Scale
<br />ELEC
<br />Electric, Electrical
<br />OH
<br />Overhead
<br />EMT
<br />ElectroMetallic Conduit
<br />Ph
<br />Phase
<br />PNL
<br />Panel
<br />PVC
<br />PolyVi TKWaride Conduit
<br />RTU
<br />Roof Top Uri; Radio Telemetry Unit
<br />Riser Diagram Keyed Notes:
<br />01 Existing Wkmmy to Remain ( 8WA ). Field Verify.
<br />© Existing Ground To Remain.
<br />® Existing House Panel Discomnect To Remain.
<br />Existing Tenant Disconnect To Remain.
<br />Currently Vacant
<br />© jaxisimir 200A Conductors and Conduit to Remain Field Vey
<br />Instan t) ##2IG Continuous to Isolated Ground Buss in Pawl LB.
<br />43 g 200A Safety Disconnect for Tenant Use.
<br />Field Verify Fuses Are Class J and 200A.
<br />© Existing 200A Conductors and Conduit to Remain. Field Verify.
<br />® Panel LA.
<br />0 (4) #6, (1) #10G, (1) #2IG, 1 "C.
<br />® Panel LB
<br />Install (1) #2 IG Continuous firm Main Service Ground to
<br />Isolated Ground Buss in Panel.
<br />® Panel LA2.
<br />© Lighting Contactor for Exterior Sign(s)/ Lights.
<br />30A EOEff 4 Pole Coniacton(s) in NEMA 1 Enclosure.
<br />Square D Class 8903 Type S or Equal.
<br />Tirawlock for Control of Exterior Sign(s).
<br />Seven Day Skip A Day Astronomic wi Battery Backup, Taxf or
<br />Equal.
<br />® Provide Permanently Affixed Label
<br />"Five Guys Disconnect 112"
<br />® Provide Pemiatiently Affixed Label
<br />"Five Guys Disconnect Z2"
<br />® Provide Permanently Affixed Label
<br />'Fed From Five Guys Disconnect 112"
<br />© Provide Permanently Affixed Label
<br />"Fed From Five Guys Disconnect 212"
<br />PROJECT GENERAL NOTES:
<br />1. Routing sbown a diagrammatic ably. Field verify exact routing of oarduit and coadutcbors.
<br />2. Contractor shall verify do" swings prior to installing light switches.
<br />3. Lay m light fixtures shall be shad on opposite corners from stuct m.
<br />4. No oombuatble material shall be installed m a plenum sp wo Verify Plcenm Spaces with Architectural and Mechanical.
<br />5. Cover plates shall be installed fax• all dmces. Where merle than one device is indicated is the same location, the devices shall be ganged
<br />under a common plate
<br />6. No devices shall be mounted within 24" of another device on opposite sides ofa fine rated wall.
<br />7. The Branch Circuit feeding the emergency ligliftWexit signs shall be the saw as that serving the normal lighting to the am and connected
<br />ahead of any local switches
<br />8. All wire shall be Capper.
<br />9. Any flexible coodult shall NOT exceed 5'-0" in hngth.
<br />10. Coordinate Mounting Heights for Kitchen Equipment with Kitchen Equipment Supplier, Architectural Plans, and General Contractor Prior to
<br />Rougb-In.
<br />11. Device Cove.rph tes Shall Be Stainless Steel. All Devices Shari Be WHITE in Color. Provide Blank Coveiplates Where Devices Are Not
<br />Installed
<br />12. All Devices New UNO.
<br />EX - Existing to Remain
<br />EX R - Existing Shown in Relocated Position.
<br />13. Information contained in these plans regarding existing equipment was supplied by a third party. The Contrator shall field verify exact
<br />requirements of the existing equipment. Where that are discrepancies between the design documents and the actual installatiom, the Contractor
<br />shall inform the Architect immediately for a resolution.
<br />James E. Tremel ling, PE
<br />4838 Campground Road
<br />Alexander City, Alabama 35010
<br />r (250 329-3557 F/aidr PEW. Pmjact P
<br />P: (2-%) 329-3" 58973 2010022
<br />Preston Ridge Commons
<br />3155 North Point Parkway
<br />Building E - Suite 200
<br />Alpharetta, Georgia 30005
<br />Tel 770 619 5916
<br />Fax 770 619 5919
<br />``�elalulrr)
<br />��g�' T•REMcc��'.
<br />r
<br />-� 0 G)51 cc
<br />-
<br />-
<br />.4 .4
<br />li
<br />H
<br />Z
<br />W
<br />M
<br />LU
<br />ZQQ
<br />aC
<br />"LL I
<br />:D-0
<br />LL
<br />O J DC
<br />==O
<br />O0 tv
<br />H O _5
<br />Hm Li-
<br />L
<br />z
<br />Q Q J
<br />WV—
<br />a
<br />Joe
<br />1:� o=C
<br />00
<br />��_
<br />^LU
<br />@M100011
<br />m
<br />ac W
<br />N
<br />uWLU
<br />3:
<br />N
<br />REVISIONS
<br />NO.
<br />DATE
<br />REVISION
<br />IfQX3MNtFlCATM CLAUSE
<br />THE OWNER SHALL RELEASE, HOLD
<br />HARMLESS, AND INDEMNIFY THE
<br />ARCHITECT WITH RESPECT TO: ANY
<br />CHANGES MADE TO THE CONSTRUCTION
<br />DOCUMENTS BY ANYONE OTHER THAN
<br />THE ARCHITECT, OR CHANGES IN ANY
<br />ASPECT OF THE WORK OR FAILURE BY
<br />THE CONTRACTOR TO BUILD IN
<br />ACCORDANCE WITH THESE
<br />CONSTRUCTION DOCUMENTS
<br />ERIC 11. SAFFRAW
<br />AifCHITKT
<br />THIS DRAWING IS THE PROPERTY OF
<br />ERIC 1. SAFFRANI ARCHITECT
<br />AND IS NOT To BE REPRODUCED OR
<br />COPIED IN WHOLE OR IN PART.
<br />UNAUTHORIZED USE OF ANY KIND,
<br />INCLUDING USE ON ANY OTHER
<br />WPR ECT ISPROHIBITED. IT IS TO BE
<br />RNED UPON REQUEST.
<br />L
<br />SPECIFICATIONS &
<br />RISER DIAGRAM