Laserfiche WebLink
FOR ASPHALT SHINGLE ROOF, USE MIN 7/16' STRUCTURAL <br />SHEATHING EXP 1(24/16) or 15/32" STRUCTURAL SHEATHING EXP 1 <br />(32/16), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE 15/32" <br />STRUCTURAL SHEATHING EXP 1 (32/16) .(SEE TABLE FOR FIELD AND <br />EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE SO RING SHANK GUN <br />NAILS 0 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' <br />OF GABLE END. <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL REQUIREMENTS <br />SIZE <br />HEAD <br />LENGTH <br />DIA. <br />TENSILE STR. <br />SHANK <br />ASTM <br />SO <br />RING SHANK, <br />2 SAT' <br />0.113 <br />170,000 <br />RING <br />G RINGS <br />F16" <br />SCREW SHANK <br />PER INCH) <br />RSRS-01 <br />8d <br />RING SHANK, <br />PNEUMATIC <br />23/8 <br />0.113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 1/2" COX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT <br />4" O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6' O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16' ZIP SHEATHING SYSTEM <br />(INSTALLED PER MANUR SPECS.) SEE DETAIL <br />RQOF SHEATHING ATTACHEME:N78PAGNG <br />20NE 1: 8d NAILS 4" O.C. ON EDGE AND 6' O.C. IN FIELD <br />ZONE 2e, 2n, 2r: ed NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r: 8d NAILS C 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />8d RING SHANK GUN NAILS 0 4" O.C. <br />TOP & BOTTOM EDGES . <br />a <br />OC <br />TYP. EXT. SHEATHING ATTACHMENT <br />WI -TER <br />ROOF SHEATHING <br />.--_—I 11 <br />mmmEN 11 <br />Z = <br />9° <br />m <br />BUILDING LENGTH <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING 0 <br />16"0.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP <br />BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />Sd RING SHANK GUN NAILS <br />SEE"ROOF SHEATHING ATTACHMENT' <br />TABLE FOR FIELD SPACING <br />#87' DECK SCREWS @ 6"4" O.C. MAX <br />EDGES & 17O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />HIP ROOF TF—A' <br />ROOF WIND DESIGN PRESSURES <br />NET (GRO%) ASCE T-16 <br />ZgJEt=-Tl.3 3=3Z.3 <br />ZONEa=32.B ZONE 3e=.iB.5 <br />ZONEa=38.5 ZONE 3,=-55.3 <br />zoNE a. ae.s <br />'= 4'O" f ND ZCP£ geTav-E <br />WINDSPFEO 150 MPH <br />E%f4SWE GTEGORY'.'B" <br />R64LGlTPGORY'. 11 <br />APPLICABLE INIEWNL <br />PRE39lRiE CAEFFlgENT. al-O.t6 <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLICATION <br />SIZE <br />1. <br />SPACING <br />REMARKS <br />APPUGTION <br />SIZE <br />TYPE <br />SPAGNG <br />REMARKS <br />1 PTFURPoNG TO <br />MASONRYICONC <br />CABEHMDEtEDOOL <br />NA 11 -LONG. <br />B, <br />OARAOEDOOR BUpt <br />To— <br />1l4"DV. <br />NO WASHER <br />TAPCON MA9d1RY <br />FAN.— <br />B"O� <br />tt?EMBED., 4'FHI tl3T., <br />I —EDGE— <br />BOO, AL. EXT. DOORS <br />-III RDENEDOOL <br />3'dO <br />YNNOONMDOORIFASTENED <br />MRAOEDOdt— <br />3I&DIA'OR <br />EXPANSIONWti <br />1S'dC (316"tlA) <br />4°EMSED.,4"END qST.. <br />1X PT,BF-ENOTEB <br />NML1 tR"LONG. <br />STA__ <br />NRYX]FIC. <br />TO MASCNRYpdVC. <br />N1wAD11 <br />Z4"dCltiZ'tl/4 <br />3'EDGE dei. <br />WINDOW BUCK <br />CASE HARDENED CUL <br />R'OlG <br />WINCOWIDOORI FASTENED <br />METAL STRAP TO <br />CONTACT THIS ENGINEER FOR SPACING <br />tX PT. SEE NOTES <br />NAILI IIY'L . <br />STAGGERED <br />NTO MAEIJNRYA>DNC. <br />MABONRYICONC, <br />REQUIREMENTS <br />EXT.BWNG DOOR <br />&1CKa PT. SEENOTE6 <br />I213I18pA <br />NO WASHER <br />'iAPC0f1' <br />FAWNER <br />18 <br />11IS EMBED,-140 <br />g3T.,11R"EDGE pST. <br />NON BEARING WOOD <br />WPLL TO CONC. &.AB <br />12"° PPNSION 4'EMBED. 4•E1O <br />WI WASHER BOLT �•• eT., 3'EOOE p3T. <br />a PT wINDOW BUCK O.Ib°PAFa 11/6" YOA: 4" END. EX T. I TIE' <br />PT TO STEEL6 SEE —ESSTAGGERED EDOE q3i. <br />NOTES <br />NOTES <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WANDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4, PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />8. INDOW AND DOOR BUCKS SHALL BE AS W DE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED Wf TAPCONS OR PAF TO THE SUBSTRATE. <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C3303M. MAXIMUM AGGREGATE SIZE SHALL BE 3W. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE O%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ALL EXPOSED EDGES OF CONCRETE <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 78t EDITION <br />ARE TO BE CHAMFERED 3I4'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE N0, 2 0R BETTER. Fb = 1100 PSI ANDA MODULUS OF <br />FOR STRUCTURAL CONCRETE, TMS 402J802-16 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE "IL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SlABS-0N-GROUND WHERE INDICATED ON <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS <br />DRAWINGS. SEAMS LAPPED 6INCHE3 AND SEALED WITH ADHESIVE TAPE. <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -NARK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WTH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN 5S OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS, <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEI WING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM A1064/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE ITH THE <br />WOW TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WTH V CHAIRS SPACED 3'-0' OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WTH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY AL DI <br />L DIMENSIONS M 10 S PRIOR 10 <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF AND MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A815A615M GRADE 401N CONCRETEREBAR DEFORMED BARS,DPLSHALL BE ASTM A615 <br />GRADE 80 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />E0,036" <br />MEETING THE REQUIREMENTS OF ASTM A448/A448M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />A, A A <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOPDRAWINGS FOR REVIEW RI DRAIN E EW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL-PLATE-CONNECTE0.WOOD TRUSS CONSTRUCTION:, AND "SCSI LATEST EDITION' <br />ROOF: LIVE LOAD FLOORLIVE LOAD 40 psf <br />AND <br />DDIVERTICAL BARS SHALL LAP 8 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 psf TOP CHORD n oncumem <br />EW <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />WOOD TRUSSES. <br />10 psf STM CHORD rion—current <br />#5 BAR - 3W #7 BAR - 42" <br />TRUSS MANUFACTURER ILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36=x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL- ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990. <br />15 psf TOP CHORD 20 psf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) (10 psf w/ No GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 psf BTM CHORD 5 psf BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: IDpsf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 psf <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD SPEED MPH 3-SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(MICE (FBC 020) EXPOSURE B, RISK CATEGORY Ip <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LIVE LOADS: UNINHABITABLE <br />ABLE ATTIC WITHOUT STORAGE: 10paf, UNINHABITABLE ATTIC WTH LIMITED <br />LAYOUT, SPANS &ALL TRUSS/ HEADER ENGINEERING, ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WTH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS' 40psf, GUARDS AND HANDRAILS' 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WTHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50pef, ROOMS OTHER THAN SLEEPING ROOM'. 40psf, SLEEPING ROOM$: 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40P0 <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-B0, GRADE Pm = 2000 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWINGS SUBMITTED WITHOUT REVIEW ILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />I <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR WHEAL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />IT <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C476' AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS ILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWSE ON FOUNDATION PLAN, THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10', USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATIONI SITE PREPARATION' <br />"M" "S" <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PSI, FOOTING <br />TYPE OR MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WTH ASTM D-1557. TREAT ALL <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILL CMU CELLS SOLID ITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR 6 X BAR NO. 148 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WTH THE <br />CONCRETE: <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36/A36M, Fy = W W FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />A500/ASOOM, GRADE B, Fy= 46 1.!, STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE 8, TYPE E OR S, Fy = <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURALTERRACE SWAB, <br />35 W, TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />CONTRACTOR SHALL SUBMR PROPOSED MIXDESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5'-- PRIOR TO THE ADDITION OF PLASTICIZER <br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND A3TMC94C94M OR MEASURING, MIXING,TRANSPORTING, <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL.J-BOLTS ARE TO BE STEEL, <br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT 18 DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A MAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. R SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A. T FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONSI: <br />B. FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER <br />1AIT FOR NS AND SMALLER <br />2" FOR 108 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4' FOR SLABS, WALLS AND JOISTS <br />1-1R" FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />A R C H I T E C T• <br />6 <br />Despin <br />Gr <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL32750 <br />PH: 407-7746078 <br />FAX: 407.7744078 <br />www.abdesigngroup.com <br />AA #: 0003325 <br />h <br />q�qpp <br />h <br />myO <br />f: <br />SLTHDrv. ee LOT: <br />SILVERADO <br />LOT #6 <br />BLK #16 <br />PROJECT* <br />03719.001-06161 <br />MODELS <br />"2558-HAWTHORNE" <br />GARAGE 911PING: <br />LEFT <br />PAGE: <br />DETAILS <br />150 MPH B If <br />