Laserfiche WebLink
FOR ASPHALT SHINGLE ROOF, USE MIN 7/16' STRUCTURAL <br />SHEATHING EXP 1(24/16) or 15132" STRUCTURAL SHEATHING EXP 1 <br />(32/16), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE 15/32" <br />STRUCTURAL SHEATHING EXP 1 (32/16) .(SEE TABLE FOR FIELD AND <br />EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 8d RING SHANK GUN <br />NAILS @ 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' <br />OF GABLE END. <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL REQUIREMENTS <br />SIZE <br />HEAD <br />LENGTH <br />CIA. <br />TENSILE STR. <br />SHANK <br />ASTM <br />Btl <br />RING SHANK, <br />23/8" <br />OA13 <br />170.000 <br />RING <br />(16-20 RINGS <br />F1667 <br />SCREW SHANK <br />PER INCH) <br />RSRS-01 <br />Sol <br />RING SHANK, <br />PNEUMATIC <br />2 318" <br />0.113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 1/2" COX OR 7/16" O.S.B. PLY WITH Bd RING SHANK GUN NAILS AT <br />4" O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Bd RING SHANK GUN NAILS AT 6' O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16' ZIP SHEATHING SYSTEM <br />(INSTALLED PER MANUR SPECS.) SEE DETAIL. <br />ZONE 1: 8d NAILS @ N. O.C. ON EDGE AND 6' O.C. IN FIELD <br />ZONE 2e, 2n, 2r: 8d NAILS @ 4" O.C. ON EDGE AND f. O.C. IN FIELD <br />ZONE 3,3e, 3r Bd NAILS @ 4" O.C. ON EDGE AND 4" O.C. IIN FIELD <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />Z Q <br />Z 0 <br />�W <br />Y c <br />Q U <br />N O <br />(0 <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />TOP & BOTTOM EDGES <br />- <br />w <br />zW <br />Dw <br />Y <br />= U <br />q O <br />Z <br />S <br />• �A�A���A�.�A�A�A�A�A'JrM J <br />s ® 'A'A11102 <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />Z = <br />O <br />9� <br />m <br />D BUILDING LENGTH U <br />T ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING @ <br />16"O.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP <br />BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />Sol RING SHANK GUN NAILS <br />SEE'ROOF SHEATHING ATTACHMENT' <br />TABLE FOR FIELD SPACING <br />#8 2" DECK SCREWS @ 6"-B" O.C. MAX '@ <br />EDGES & 12' O.C. MAX•IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />HIP RDOF <br />ROOF VIAND DESIGN PRESSURES <br />NET(GPOS9) ASCE 7-16 <br />ZONEb= 1 3e=3B.7 <br />IONE ZONE 11 SS7 ZONE 3r=55.6 <br />L' EIDZONE DSTANC< <br />BASIC WIND SPEED 150 MPH <br />RISKI-K INTE­ <br />Ta <br />APPLIGBL OOEFP.E <br />PRESSIAiE OJEFFlgEM. N-0 IS <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />MRIUTION <br />SPAGNG <br />REMARKS <br />APPLICATION <br />Sim <br />1. <br />SPACING <br />REMARKS <br />fz2PT URR <br />MAeONRY/GONG. <br />G HMOENEOODL <br />NA 2'LONG. <br />9 OK: <br />AGES DOORBUCX <br />To MANC. <br />1/4'•DA. <br />NOWASHER <br />RV <br />TA FASTENER <br />„ <br />6 OH: <br />.4"ENo DIST <br />—EDGE.. <br />SODDOORS <br />L. EXT. DRS <br />USE HAR DENEDOJIL <br />E.- <br />WINDOW/OOORI FASTENED <br />RAG EOOORBUC!( <br />oA'O <br />IIY qA <br />EXPANSION BOLT <br />ie"OIC I31P CIA)EMBED, <br />CENO T., <br />g9 <br />x PA <br />9TASOEPEp <br />NNYILtl6C. <br />xJ WASHER <br />2I"OIC lt2'DAj <br />WEDIST <br />aox; <br />WINDDWmooR/FA9TENED <br />CONTACT THIS ENGINEER FOR SPACING <br />GA9EHAROENEOwIL <br />NALI I2 LONG. <br />INTO MASDNaY/oGNc. <br />rensoNalT° sic <br />REQUIREMENTS <br />EXT. SWING WON <br />SUCK d PT, 9EENOTE6 <br />(2)3116'gA <br />—HER <br />"TAPWN" <br />FASTNER <br />1B OO <br />111Y EMBEq. B"END. <br />OIST., 112"EWE DST. <br />NON -BEARING WOOD <br />I2"° EXPANSION 4•'EMBED. 4-END <br />W/WASHER BOLT 2401C DST., I EDGE DST. <br />Tzr T WINDOW BUCK Se° PAF 21 fry' O/C 4° END GERED EI TT,I Im <br />P 09TEEL COL, SEE S'1y,,/WA911FR /S <br />NOTE6 <br />NOTES <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS VIDE OR WDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. lx MEMBERS ARE NAILED AND <br />2T MEMBERS ARE SECURED W TAPCONS OR PAF TO THE SUBSTRATE. <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C3LC33M. MAXIMUM AGGREGATE SIZE SHALL BE Mr. <br />STRUCTURAL DRAW NGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAW NGS. CONSULT <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAW NGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3/4'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF <br />'= <br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS-0GROUND-GROUND WHERE INDICATED ON <br />POLYETHYLENE <br />ELASTICITY 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCd( SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS <br />PROVIDES. SEAMS NAPPED 61NCHE SEALED WITHRRIADHESIVEME TAPE. <br />AND <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAW NGS ARE INTENDED TO BE TYPICAL AND <br />FORMWORK: <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0,42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />I IN PER <br />MINIMUM NAILING G E FBCR 2020 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WTH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WTH 2. STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />20 psf TOP CHORD -non-concurrent <br />10 psf BTM CHORD -non -concurrent <br />DEAD LOAD DEAD LOAD <br />15 psf TOP CHORD 20 psf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) (10 psf IN/ No GYPCRETE) <br />9f BT CHORD 5 sf BTM CHORD 10 M p P <br />DEAD LOAD TO RESIST VIAND UPLIFT: 10psf <br />BALCONY LIVE LOAD 80 psf <br />STAIRS LIVE LOAD 40 psf <br />WIND : DEAD LOAD SPEED =150 MPH 3-SECOND GUST <br />(ASCE 7-18 (FBC R2020) EXPOSURE B, RISK CATEGORY II) <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 1Opsf, UNINHABITABLE ATTIC WTH LIMITED <br />STORAGE: 20PSf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30pe,, STAIRS: <br />40psf <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS W ILL BE REVIEWED FOR GENERAL COMPLIANCE WTH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT <br />DRAWINGS SUBMITTED WITHOUT REVIEW W LL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />WRITING BY THE ARCHITECT. <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING <br />WELDED WIRE MESH: <br />WELDED WIRE MESH, SHALL BE ASTM A1064/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WTH THE <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WITH T CHAIRS SPACED T-O' OC, EACH WAY. <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM A615A615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />GRADE 601N MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36" <br />#5 BAR - 30" #7 BAR - 42" <br />PROVIDE 36". 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION, <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />THICKENED SLAB BEAM O LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />C D R <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />WALL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />MASONRY: <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />THE MASONRY STANDARDS JOINT COMMITTEE, <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />MANUFACTURED IN CONFORMANCE WTH ASTM C-90, GRADE fm = 2000 PSI. BLOCK SHALL BE PLACED USING <br />RUNNING BOND UNLESS OTHERW SE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318" <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 6" TO 10". USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557, TREAT ALL CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5" N- PRIOR TO THE ADDITION OF PLASTICIZER. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94IC94M OR MEASURING, MIXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A. T FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER <br />1-1Q" FOR (b AND SMALLER <br />2" FOR 06 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4" FOR SLABS, WALLS AND JOISTS <br />1-112- FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36IA36M, Fy = 36 ksi FOR ANGLES, PLATES, AND WSRAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/A500M, GRADE B, Fy = 46 ksi. STRUCTURAL PIPE SHALL BE ASTM A531A53M, GRADE S, TYPE E OR S, Fy = <br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WTH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WTH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE 'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "SCSI LATEST EDITION" <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990. <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAW NGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />PROVIDE ENGINEERED SHOP DRAW NGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />PLAN STOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />LICENSED PROFESSIONAL ENGINEER. <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PROVIDED BY THE TRUSS ENGINEER. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />A N C NI T E C T i <br />6 <br />Grohs <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-774-4078 <br />www.abdesigngroup.com <br />AA #: 0003325 J <br />DRAFTING BY: <br />A.B. DESIGN GROUP <br />DRAFTING INC. <br />5439 BEAUMONT CENTER BLVD. <br />SUITE 1004 <br />TAMPA, FLORIDA 33634 <br />PH: 813-886-2628 <br />FAX: 813-886-2802 <br />