• s e u E r e e r• <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16' STRUCTURAL <br />SHEATHING EXP 1(24116) or 15/32" STRUCTURAL SHEATHING EXP 1 <br />(32/16), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE 15/32" <br />STRUCTURAL SHEATHING EXP 1 (32116) .(SEE TABLE FOR FIELD AND <br />EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 8d RING SHANK GUN <br />NAILS @ 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS W/ IN 4' <br />OF GABLE END. <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL REQUIREMENTS <br />SIZE <br />HEAD <br />LENGTH <br />DIA, <br />TENSILE STR. <br />SHANK <br />ASTM <br />Bd <br />RING SHANK, <br />2 3/e" <br />0.113 <br />170.000 <br />(16 -20 RINGS <br />rl667 <br />SCREW SHANK <br />PER INCH) <br />8d <br />RINGSHANK, <br />PNEUMATIC <br />23/8" <br />0.113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 1/2" COX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT <br />4" O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6' O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM <br />(INSTALLED PER MANUF. SPECS.) SEE DETAIL. <br />ZONE 1: 8d NAILS 0 4" O.C. ON EDGE AND 6' O.C. IN FIELD <br />ZONE 2e, 2n, 2r: 8d NAILS ® 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r: 8d NAILS C 4" O.C. ON EDGE AND V O.C. IN FIELD <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />8d RING SHANK GUN NAILS ® 4" O.C. <br />TOP & BOTTOM EDGES Ir <br />li <br />TYP. EXT. SHEATHING ATTACHMENT <br />L—L <br />�J <br />W <br />C7 <br />Nw <br />V tj <br />00 <br />IN iD <br />GABLE END <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />Z = <br />93 <br />m <br />I, BUILDING LENGTH <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING G <br />16"0 C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP <br />BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />8d RING SHANK GUN NAILS <br />SEE"ROOF SHEATHING ATTACHMENT" <br />TABLE FOR FIELD SPACING ` <br />#8 7' DECK SCREWS @ 6"-8" O.C. MAX @ <br />EDGES & 17 O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />HIP ROOF LEI. <br />ROOF WIND DESIGN PRESSURES <br />NET (CROSS) ASOE7-15 <br />ZONE 3= S <br />ZONE b = 3].S <br />ZONE 2n=38.5 ZONE 3r=-55.3 <br />CNE 2r= NDI <br />- L"ENDZONEDSTPNCE <br />WIW SPEED. f E0 MPH <br />RISK— <br />ISK A2E GTEOORY.'e' <br />RISKCATAOORY:II <br />APPLI—EOEFFO L <br />PRESSURE <br />COEFFlCIEN-8.18 <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLICATION <br />SIZE <br />TYPE <br />SPACING <br />REMARKS <br />APPLICATION <br />SIZE <br />TYPE <br />SPACING <br />REMARKS <br />1x2PT FURRING TO <br />MASONRY/GONG. <br />CASE HARDENED WIL <br />NAILI —LONG. <br />BO/C <br />Cv1RAGE DOOR BUCK <br />TO MASONRY/CONC. <br />1/!'DA. <br />NO NMSHER <br />TAFCON MASONRY <br />FASTENER <br />S. <br />I - EMBED., 4-END DST., <br />I —EDGE DST. <br />SOD PAL. —DOORS <br />x T, SEE NOTE <br />CASE HARDENED COL <br />I -LOW <br />5.I <br />STAOOERED <br />WNDGWA]OOW FASTENED <br />INTO MASONgYroCNC. <br />GARAGE DOOR BUCK <br />TOMASONRY/CONC. <br />3IBn DAOR <br />yy,wgSHER <br />EXPANSION BOLT <br />11111IA) <br />dCN1 A) <br />I—SED., VENDDST., <br />3"EDGE DST. <br />—BUCK <br />CASE. DENEDDDL <br />B"OIC <br />WN00WNODLFASTENED <br />MI —STRAP TO <br />CONTACT THIS ENGINEER FOR SPACING <br />x <br />STAGGERED <br />INTO MAEONRY,gCFIC <br />MAsoNRYlwgO. <br />REQUIREMENTS <br />O DOOR <br />BUCK 2x PT, SEENOTE6 <br />()3118'D0. <br />WASHER <br />"TPPNN' <br />FASTNER <br />150� <br />i111 EMBED. 6'END <br />OISi., 112' EDGE DIST. <br />N0IFBEAgIND NroOD <br />WALL TO CONC. STAB <br />1l2"° PANSION 240� C"EMBED. O"END <br />WI WASHER BOLT OIST., 3"EWEDST. <br />LPTIMNOOW&KK qFx 21R' 4-EN0. D3T.,11I[' <br />01� <br />Pr TO STEELC0...9EE WI WASHER GERED EDGE DST. <br />NOTES <br />N <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />B. W NDOW AND DOOR BUCKS SHALL BE AS WDE OR WIDER AS THE DOOR OR W NDOW FRAME EXCEPT FOR AN EXTERIOR SW NG DOOR WITH A WOOD DOOR FRAME. 1. MEMBERS ARE NAILED AND <br />Z, MEMBERS ARE SECURED VW TAPCONS OR RAF TO THE SUBSTRATE. <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C331C33M, MAXIMUM AGGREGATE SIZE SHALL BE XT, <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD: <br />DRAWINGS CONSULT <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAW <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />NON -BEARING WOOD WALLS TOP PLATES &STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWNGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7th EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 314' . <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-1 4, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 20R BETTER. Fb = 1100 PSI AND MODULUS OF <br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABSONGROUNO WHERE INDICATED ON <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WTH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS <br />DRAWINGS. SEAMS TAPPED B INCHES AND SEALED WITH ADHESIVE TAPE. <br />PRESSURE TREATED, PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />SHALL BE RATED TO RETENTION LEVELS OF 0,25 PCF OF A BORATE PRESERVATIVE TREATMENT'. DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0,42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WTH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION,"RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THANIA" OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWNGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WTH 2. STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE <br />WELDED WIRE MESH, SHALL BE ASTM AT 064/Ai D64M, GRADE 65 AND BE PLACED IN ACCORDANCE WTH THE <br />WOOD TRUSSES: <br />-DOWNS. <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION BE SUPPORTED WTH 2 CHAIRS SPACED 3-0 OC, EACH WAY. <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. STRESS -GRADE LUMBER AND ITS FASTENINGS' THE NFPA. TRUSS DESIGNS SHALL SIGNED AND <br />SEA <br />LED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR. SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS A E A, A AND A MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. REBAR SHALL BE ASTM DEFORMED <br />GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 MEETING THE REQUIREMENTS OF ASTM A448/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />601N MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE <br />GRADE E <br />DESIGN LOADS: W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WTH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "BCSI LATEST EDITION" <br />ROOF: LIVE LOAD FLOOR'. LIVE LOAD 40 psf AND VERTICAL BARS SHALL LAP 6. BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />REVIEW. WOOD TRUSSES. <br />20 psf TOP CHORD-no—oncunent <br />10 psf BTM CHORD—oncurrent TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - " #6 BAR - 2" 304 <br />#5 BAR - 30" #7 BAR - TRUSS MANUFACTURER W LL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 38° z 38° CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAMM REBAR, SEE DETAILS LOCATIONS WTH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD FOR ADDITIONAL INFORMATION. INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990. <br />15 psf TOP CHORD <br />20 psf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) <br />(10 psf w/ No GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 psf BTM CHORD <br />5 psf BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: tops( <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 psf <br />WALL. <br />TRUSSESIGIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />WIND'. DEAD LOAD SPEED 020) MPH 3-SECOND GUST INTO INTERSECTING WALLS AND HOOK AT ENDS, STAGGER SPLICES WHEREVER POSSIBLE. DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE, TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />(ASCE 7-16 (BBC ATTIC EXPOSURE B, RISK CATEGORY II) LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />LIVELOADS:UNINHABITABLEATTIC WITHOUT DATTISTORAGE:1MT UNINHABITABLEATTICWTHLIMITED <br />STORAGE: 20pst, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS'. 30psf, BALCONIES (EXTERIOR) DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200paf, GUARD IN -FILL COMPONENTS50psf, PASSENGER WITHOUT THE APPROVAL OF THE ENGINEER. STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: PROVIDE ENGINEERED SHOP DRAW NGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40psf MASONRY: PLAN SHOWING COMPONENT LAYOUT. SHOP DRAW NGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: "SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE MASONRY STANDARDS JOINT COMMITTEE. PROVIDED BY THE TRUSS ENGINEER. <br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE Fm = 2000 PSI. BLOCK SHALL BE PLACED USING OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />ALL SHOP DRAW NGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAW NGS SUBMITTED WTHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWNOS (CON -TRACT DOCUMENTS) ARE PROHIBITED PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT ASTM C476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />WRITING BY THE ARCHITECT. COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10", USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION: TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT, MORTAR SHALL BE <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 DO,, FOOTING PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WTH ASTM D-1557. TREAT ALL CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE REINFORCING. <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2.500 PSI REGULAR WEGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3.000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WTH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5'4- PRIOR TO THE ADDITION OF PLASTICIZER. <br />CONCRETE SHALL COMPLY WITH ALL THE REOUIREMENTS OF ACI 318 AND ASTM C941C94M OR MEASURING, MIXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIMEBTAMPED WHEN CONCRETE IS BATCHED, THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES. THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SNALL BE AS FOLLOWS: <br />A. T FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />B. FOR CONCRETE EXPOSED TO EARTH ANDADR WEATHER: <br />1.1/2' FOR 16 AND SMALLER <br />2' FOR #8 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />314- FOR SLABS, WALLS AND JOISTS <br />1.12- FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A38/A36M, Fy = 36'.ksi FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/A500M, GRADE B, FY - 46 ksi. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy = <br />35 IrSL TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WTH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />6 <br />Design <br />Grou �nm <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL32750 <br />PH: 407-774-6078 <br />FAX: 407-7744078 <br />www.abdesigngroup.com <br />AA #: 0003325 <br />mPi <br />t <br />9UBDM at LOT: <br />SILVERADO <br />LOT #12 <br />BLK #16 <br />PROJECT4y <br />03719.001-12161 <br />MODEL <br />"2558-HAWTHORNE" <br />GARAGE 9WIIJG: <br />LEFT <br />PAGE: <br />DETAILS <br />150 MPH E . B <br />