kLW.: <br />FOUNDATION PLAN <br />SCALE: 1/4" =1'-0" <br />FOUNDATION NOTES <br />1. SEE SLAB SCHEDULE FOR SLAB REQUIREMENTS. SEE GENERAL NOTES FOR <br />COMPACTING REQUIREMENTS. <br />2. TOP OF FINISHED SLAB SHALL BE <br />3. COLUMN AND FOOTING CENTERLINES, SHALL COINCIDE UNLESS DIMENSIONED <br />OTHERWISE. <br />4. REFERENCE ELEVATION +-0`0", SEE SURVEY PLOT FOR NGVD. <br />S. PROVIDE A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN <br />TERMITES. TREATMENT SHOULD BE IN ACCORDANCE WITH THE RULES AND LAWS AS <br />ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER <br />SERVICES. <br />6. PROVIDE ISOLATION JOINTS BETWEEN INTERIOR AND EXTERIOR SLABS ON GRADE: <br />PROVIDE 1/2" FELT PAPER AT THE JOINT. <br />7. COORDINATE SLAB ELEVATIONS, STEPS, AND SLOPES WITH ARCHITECTURAL <br />DRAWINGS. <br />8. SEE ARCHITECTURAL DRAWINGS FOR THE ORIENTATION OF THE BUILDING. <br />9. WINDOWS, DOORS AND ROUGH OPENINGS ARE TO BE COORDINATED WITH THE <br />WINDOW/DOOR TYPES AND LOCATIONS NOTED ON THE ARCHITECTURAL DRAWINGS <br />AND WITH THE MANUFACTURES SPECIFICATIONS. <br />10. SEE ARCHITECTURAL DRAWINGS FOR WALKWAY SLAB LAYOUT. <br />1113INDICATED #5 BAR, OINDICATES #6 BAR,lNDICATES #7 BAR VERTICAL <br />REINFORCING BAR IN CELLS FILLED WITH GROUT. ENDS OF REINF. BARS SHALL BE <br />HOOKED INTO FOUNDATION BOND BEAM OR TIE BEAMS WITH AN ACI STANDARD 90" <br />HOOK. BARS SHALL BE PLACED AS SHOWN IN HE PLANS. <br />12. SPLICES IN REINFORCING BARS SHALL NOT BE LESS THEN 48 BAR DIAMETERS (#5 = <br />30", #6 -36% AND REINFORCING SHALL BE CONTINUOUS. <br />13. RATIONAL ANALYSIS WAS PERFORMED TO DETERMINE SIZE AND STEEL <br />REINFORCING FOR ALL FOUNDATIONS. DESIGNED WAS BASED ON ALL ALLOWABLE <br />SOIL BEARING CAPACITY OF 2,000 PSF. TRANSFER REINFORCING (TOP STEEL) HAS <br />BEEN DELETED UNLESS NOTED OTHERWISE. <br />14. VERTICAL REINFORCING IN CMU SHALL BE #5'S AS SHOWN ON THIS PLAN, UNLESS <br />OTHERWISE NOTED IN THE PLAN. ONE REINFORCING BAR SHALL BE: <br />A) IN ALL WALL INTERSECTIONS B) CHANGES IN ELEVATION <br />C) EACH SIDE OF ALL OPENINGS D) ALL CORNERS <br />15. STRUCTURAL DESIGN IS IN ACCORDANCE WITH A.C.I.530-13(ASCE 513, BUILDING <br />CODE REQUIREMENTS FOR MASONRY STRUCTURES AND THE COMMENTARY. <br />CONSTRUCTION SHALL BE IN ACCORDANCE WITH A.C.I. 530.13/ASCE 5-13, USING: Fm = <br />1,500 PSI, TYPE "M" OR"S" MORTAR, ASTM C476 GROUT (30D0 PSI), UNITS LAID IN <br />RUNNING BOND. <br />16. WIRE WELDED MESH LOCATED IN THE MIDDLE TO UPPER j OF SLAB SUPPORTED <br />3'-0" O/C MAX. SEE PLAN FOR W WM SIZE. <br />INSPECTOR NOTE: <br />1. STRUCTURE WAS DESIGNED BASED ON THE 2017 FLORIDA RESIDENTIAL BUILDING <br />CODE, RESIDENTIAL, 6th EDITION <br />SLAB SCHEDULE <br />SLAB <br />THICKNESS <br />I REINF. <br />REMARKS <br />616 W1.41WIA OVER <br />GENERAL <br />3 7/2" <br />6 MIL VAPOR <br />COMPACTED FILL <br />BARRIER <br />FOOTING SCHEDULE <br />PROVIDE CORNER BARS SAME SIZE QUANTITY AS BARS IN FOUNDATION WITH 30" LEG EACH WAY. <br />MARK <br />WIDTH <br />LENGTH <br />THICKNESS <br />BOTTOM REWF. <br />TOP REINF. <br />T.O.F. <br />SHORT <br />LONG <br />FM42x18 <br />12" <br />CONTINUOUS <br />18" <br />- <br />(2) #5's <br />FMC-12x18 <br />12" <br />CONTINUOUS <br />18" <br />- <br />(2) #5's <br />#5 IN CURB <br />VARIES <br />FM-12xi2 <br />12" <br />CONTINUOUS <br />12" <br />- <br />(2) #5s <br />(-)0'-4" <br />TE-1 <br />8" <br />SEE PLAN <br />8" <br />- <br />8 <br />#5 IN CURB <br />(-)0'-0" <br />1441 N. RONALD REAGAN 8l <br />LONGWOOD, FL 32780 <br />PH: 407-77"078 <br />FAX: 407-774.4078 <br />www.abdeslgngroup.com <br />AA M. 0003325 <br />h <br />V <br />0 <br />y <br />O <br />a <br />SuaDIV. & =7- <br />SILVERADO <br />LOT #1 <br />BLK #12 <br />PROJECT* <br />04128.001-01121 <br />MODEL.• <br />4ENB <br />"1751- NEUVILLE" <br />GARAGE SWING: <br />RIGHT <br />PAGE: <br />FOUNDATION <br />PLAN <br />50 MPH EXP. ly <br />PRWT 08/15 18 <br />DATE: / <br />SCALE: 1/4"=1'-0" <br />SHEET <br />S1 <br />