i <br />• <br />4 <br />q <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) 7-10 <br />ZONE 1 = 8.97 PSF (19.97) <br />ZONE 2 = 17.98 PSF (27.98) <br />ZONE 3 = 33.53 PSF (43.53) <br />"A"= 4'4" END ZONE DISTANCE <br />BASIC WIND SPEED: 150 MPH <br />WIND EXPOSURE: 'B' <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT , 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/19' <br />O.S.B. OR 1/2" CDX EXT. PLYWOOD, FOR <br />CEMENTITIOUS TILE AND METAL ROOFING, USE <br />MIN. 518 CDX EXT. PLYWOOD, WITH 8d RING <br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED <br />PANEL EDGES AND 8d RING SHANK GUN NAILS <br />AT S' O.C. AT INTERMEDIATE SUPPORTS. SEE <br />DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE <br />8d GUN NAILS C& 4" O.C. EDGEWISE 2X4 <br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE <br />END. <br />ROOF/ WALLA FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />NAIL SCHEDULE <br />SIZE <br />TYPE <br />MIN. LENGTH <br />MIN. DIA <br />SHANK <br />TENSILE STR. <br />SHANK <br />8d <br />RING SHANK, <br />21/7 <br />0.120" <br />170,000 <br />RING <br />SCREW SHANK <br />16-20 RINGS <br />ER INCH) <br />8d <br />SCREW SHANK <br />2 112' <br />0.120" <br />PNEUMATIC <br />SCREW -NAILS <br />1. NAIL SIZE PER ASTM F1664 <br />2. INTERNATIONAL STAPE, NAIL & TOOL <br />ASSOCIATION (ISANTA) ESR-1539 <br />EXTERIOR SHEATHING <br />USE 1IT COX OR 7/16" O.S.B. PLY WITH Sd RING <br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES <br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND 8d RING SHANK GUN <br />NAILS AT 6" O.C. AT INTERMEDIATE SUPPORTS <br />OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />'a <br />CO <br />CO <br />Z LU <br />Z O <br />w <br /><Z <br />U <br />SCO <br />p <br />Z <br />2 <br />8d RING SHANK GUN NAILS @ 4" O.C. <br />TOP & BOTTOM EDGES <br />m <br />I <br />Z O <br />� W <br />Y Z <br />Z - . <br />2 i <br />m O <br />J <br />Z Y <br />Q <br />U 1n <br />Y 3 <br />w <br />= 2 <br />Z� <br />¢. <br />m <br />F <br />m <br />TOP CORD BLOCKING AT 4' <br />O.C. MAX. IN FIRST 2 FRAMING <br />SPACES AT EACH END. <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />(7 <br />Z ti <br />3 <br />m <br />I, BUILDING LENGTH <br />I, <br />ROOF SHEATHINGLAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />8d RING SHANK GUN NAILS <br />(� 6" O.C. IN FIELD <br />8d RING SHANK GUN NAILS @ 12' O.C. IN <br />FIELD or Sd x 21/7SCREW SHANK <br />PNEUMATIC SCREW -NAILS @ 1210.7 <br />FIELD <br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. MAXIMLM AGGREGATE SIZE SRALL BE NIT. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD. <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE 6%NR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 6th EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED Mr. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACT 318.14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER RD -1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, ACI AS SPECIFICATION FOR TH DESIGN OF <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS0NGROUND WHERE INDICATED ON <br />ELASTICITY - PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL <br />L MEMBERS 011. ICATI <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND RISC SPECIFICATIONS <br />DRAWINGS. SEAM9LAPPED 61NCHES AND SEALED NTH ADHESIVE TAPE <br />A <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />TREATED- <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORM -WORK: <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 POF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347, <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN W OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2017, 6th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP n• <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 PST <br />20 Psi TOP CHORD -ranconcurreM <br />10 psf BTM CHORD -rron-concur .0 <br />DEAD LOAD DEAD LOAD <br />15 psf TOP CHORD 20 psf TOP CHORD <br />(7 psf w/ ASPHALT SHINGLES) IT 0 psf w/ No GYPCRETE) <br />10 PSt BTM CHORD 5 psf BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT: IOpst <br />BALCONY LIVE LOAD 60 psf <br />WIND: DEAD LOAD SPEED -150 MPH 3- SECOND GUST <br />(ASCE 7-10 (FBC R2017) EXPOSURE B, RISK CATEGORY 11) <br />SHOP DRAWING REVIEW. <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO <br />THE ARCHITECT. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. <br />SHOP DRAWINGS IN THE FORM OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON- <br />TRACT DOCUMENTS) ARE PROHIBITED WITHOUT THE EXPRESS WRITTEN PERMISSION FROM <br />THE ENGINEER. <br />IN ALL INSTANCES, THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS <br />CHECKED, UNLESS OTHERWISE SPECIFIED IN WRITING BY THE ARCHITECT. <br />FOUNDATION/ SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PST, <br />FOOTING EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY <br />OF AT LEAST 95%OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN <br />ACCORDANCE WITH ASTM D-1557. TREAT ALL SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER <br />TO VERIFY SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS <br />FAILING TO MEET THE GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RE -COMPACTED AND <br />RETESTED AT THE CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN <br />CERTIFICATION THAT THE MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION <br />REQUIREMENTS HAVE BEEN MET SHALL BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND $- STRUCTURAL TERRACE SUB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MAX DESIGNS, WITH HISTORICAL STRENGTH DATA <br />FOR EACH SEPARATE MX PRIOR TO CONCRETE PLACEMENT. CONCRETE SLUMP SHAL! <br />NOT EXCEED F N-PRIORTOTHE ADDITION OF RASTICM <br />CONCRETE SHALL COMPLY WITH ALL THE REOUIREMENTS OF ACI 301 AND ASTM C-94OR <br />MEASURING, MANG, TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE TIMESTAWED <br />WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN WATER IS ADDED <br />TO THE MX UNTL IT IS DEPOSITED IN ITS FINAL POSITION SKALL NOT EXCEED 90 MINUTES, <br />IF FOR ANY REASON THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN <br />90 MNUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE RESPONSIBILITY OF <br />THE TESTING LABORATORY TO NOTIFY THE ONNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON COM'UANCE WITH THE <br />ABOVE <br />REWIRED CONCRETE COVERAGE OVER REBAR WALL BE AS FOLLOWS. <br />A Y FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />a FOR CONCRETE EXPOSED TO EARTH ANDAM WEATHER <br />1-VT FOR 05 AND SMALLER <br />T FOR 88 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />3/4" FOR SLABS, WALLS AND JOISTS <br />1-1R' FOR SEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />WELDED WIRE MESH: <br />WELDED WIRE MESH, SHALL BE ASTM AT 85, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI <br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE <br />SUPPORTED WITH 2" CHAIRS SPACED T-O" OC, EACH WAY. <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM A615 GRADE 60 DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN <br />ACCORDANCE W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND <br />SPECIFICATIONS. CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO <br />FABRICATION. HORIZONTAL AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE <br />SUBJECT TO ENGINEER'S REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: ♦4 BAR - 25" M6 BAR - 36" <br />M5 BAR - 30' M7 BAR - 42" <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATRML DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS" BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL-PLATECONNECTED-WOOD TRUSS CONSTRUCTION:, AND "IWTCA BCSI 1" <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />PROVIDE 36" x 36 CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />FOR ADDITIONAL INFORMATION. <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A58.1-1982. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OFTHE <br />WALL. <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />WITHOUT THE APPROVAL OF THE ENGINEER <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />MASONRY: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />"SPECIFICATION MASONRY STRUCTURES" (ACI 5301 ASCE 5/TMS 402, BUILDING CODE REQUIREMENTS FOR <br />LICENSED PROFESSIONAL ENGINEER. <br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE. <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />ALL BLOCK WALLS SHALL BE TWOCELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />PROVIDED BY THE TRUSS ENGINEER <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE F. - 1500 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASIDE T10 COMPONENT <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8' <br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USN STRUCTURAL <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10'. USE ONLY MECHANICAL VIBRATION <br />CONNECTORS" BY USP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS <br />TO CONSOLIDATE GROUT. <br />WITH THE SIZE AND NUMBER OF BOLTS/NAILS AS RECOMMENDED BY THE MANUFACTURER IN THE <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />LATEST CATALOG. <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 3/8" THAT <br />THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS AT EXTEND INTO <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., UN.O <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />ASS, Fy - 36 ksi FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B, <br />Fy - 46 km. STRUCTURAL PIPE SHALL BE ASTM-S3, GRADE 8, TYPE E OR S, Fy - 35 kSL TUBE AND PIPE <br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL <br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />APPLICATION <br />SIZE <br />TYPE <br />S-ING <br />REIAAPKS <br />APPLICATION <br />SQE <br />TYPE <br />I SPACING <br />REMARKS <br />tNPTRIRRING TO <br />OASEINRDENED.1 <br />• <br />-I-- <br />SEE DETAIN <br />SEE DETjASEEDETAIL <br />GEE DETAx <br />ASONRY I OOINC <br />-11 iR•LONG <br />TO MASOWT=w <br />-D.. EXT. DOO145 <br />WSE....ED- <br />a'O,C <br />WINWW/DOOIL FAGTENED <br />GARAGEDOOP BDCK <br />SEE PEfAx <br />SEE <br />SEE DETAA <br />GEE DETAA <br />t4P.SEENDTE6 <br />NMlii?LONG. <br />STAGGERED <br />HMO MASONRYxxIND. <br />TO MASOMiY/COlC. <br />wNDowaxac <br />cASEHAAOENEDca4 <br />WNDOWtDOOaEASTENED <br />METALSTiUPTO <br />CONTACT THIS ENGINEER FOR SPACING <br />i. PTSEF-TE,, <br />vY LONG. <br />STAGGERED <br />INTOKaso -orc. <br />MasoNRr�cONc. <br />REQUIREMENTS <br />ExT. SWING DOOR <br />I- <br />•TAPCON• <br />ttIY EMBED, 4-END. <br />NONBEARING W000 <br />trl-° ExPANSION 4'EMBED.4•END <br />BDOK h PT, SEE NOTEe <br />NO WASHER <br />fAS1NER <br />iY On: <br />OUST., t VY EDGE DUST <br />WILLL TO CONC. SLAB <br />Wl WASHER BOLTDUST., 3' EDGE 06T. <br />24 PT WNWW RUCK P END. DUST., <br />D'2t,E• c•OIC 4• I tl2' <br />PTTOSTEELOOL.'SEE •W30°t WASHER STAGGERED E DGE DUST. <br />NOTES <br />NOTES <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENINGOF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TD FRAMING BUCKS "UBE AS PER MAAIUFACTURERS SPECS AND/OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X.ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. Ix MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLV <br />LONGWOOD, FL 32750 <br />PH: 407-774.6078 <br />FAX: 407-774-4078 <br />www.abdesigngroup.com <br />AA B: 0003325 <br />F. <br />�V <br />h <br />V <br />�V <br />Fti <br />V <br />O <br />F <br />O <br />SUDDIV. do LOT <br />SILVERADO <br />LOT #4 <br />BLK #12 <br />PROJECT* <br />04128.001-04121 <br />MODEL' <br />4EHB <br />"2605-HAYDEN" <br />GARAGE STrngG: <br />RIGHT <br />PAGE: <br />DETAILS <br />50 MPH EXP. <br />DwRTE 08/18/18 <br />SCR= 4"=1'-0" <br />sxES <br />