<br />DABLE END
<br />HIP ROOK ,F w
<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) 7-1
<br />ZONE 1 - 8.97 PSF (19.97)
<br />ZONE 2 - 17.98 PSF (27.98)
<br />ZONE 3 - 33.53 PSF (43.53)
<br />"A"- 4'-O" END ZONE DISTANCE
<br />BASIC WIND SPEED: 150 MPH
<br />WIND EXPOSURE: "B"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT , 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7116'
<br />O.S.B. OR 1/2" COX EXT. PLYWOOD, FOR
<br />CEMENTITIOUS TILE AND METAL ROOFING, USE
<br />MIN. 6/8 COX EXT. PLYWOOD, WITH 8d RING
<br />SHANK GUN NAILS AT 4" O.C. AT SUPPORTED
<br />PANEL EDGES AND 8d RING SHANK GUN NAILS
<br />AT 6" O.C. AT INTERMEDIATE SUPPORTS. SEE
<br />DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE
<br />8d GUN NAILS @ 4" O.C. EDGEWISE 2x4
<br />BLOCKING ALL PANEL JOINTS W/ IN 4' OF GABLE
<br />END.
<br />ROOF/ WALU FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL SCHEDULE
<br />SIZE
<br />TYPE
<br />MIN. LENGTH
<br />MIN. DIA.
<br />SHANK
<br />TENSILE STR.
<br />SHANK
<br />Sd
<br />RING SHANK,
<br />SCREW SHANK
<br />21/2"
<br />0.120"
<br />170,000
<br />RING
<br />(16-20 RINGS
<br />PER INCH)
<br />8d
<br />SCREW SHANK
<br />21/2"
<br />0.120'
<br />PNEUMATIC
<br />SCREW -NAILS
<br />1. NAIL SIZE PER ASTM F1664
<br />2. INTERNATIONAL STAPE, NAIL & TOOL
<br />ASSOCIATION (ISANTA) ESR-1539
<br />EXTERIOR SHEATHING
<br />USE 1/2" CDX OR 7/16" O.S.B. PLY WITH 8d RING
<br />SHANK GUN NAILS AT 4" O.C. AT PANEL SIDES
<br />AND 8d RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN
<br />NAILS AT WO , C. AT INTERMEDIATE SUPPORTS
<br />OR 7/16" ZIP SEATHING SYSTEM (INSTALLED
<br />PER MANUR SPECS.) SEE DETAIL.
<br />8d RING SHANK GUN NAILS @ 4" O.C.
<br />TOP & BOTTOM EDGES
<br />IF I . . . . . . . . .
<br />a
<br />J
<br />Q
<br />Z (Wry
<br />Z w
<br />0 W
<br />� W
<br />ry LL
<br />z
<br />Y U
<br />x 0
<br />= 0
<br />o
<br />Z
<br />J
<br />Z Lu
<br />w
<br />z
<br />(� W
<br />ZY V
<br />= U
<br />C 0
<br />a a
<br />z
<br />W
<br />J J
<br />z Qw7
<br />W o*
<br />2 Uh U
<br />O rn� O
<br />z W to
<br />¢
<br />m a
<br />Do
<br />TOP CORD BLOCKING AT W
<br />O.C. MAX. IN FIRST 2 FRAMING
<br />SPACES AT EACH END.
<br />RAFTER OR TRUSS
<br />R[1f1F CHFATHIN[:
<br />6
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GIABLE END FRAMING
<br />CSd RING SHANK GUN NAILS
<br />@ 6" O.C. IN FIELD
<br />T. S A ING ATTACHMENT SH ATHING (O.S.B.
<br />TO BE STRUCTURAL GRADE
<br />C8d RING SHANK GUN NAILS @ 17' O.C. IN
<br />FIELD or 8d x 2 1/2" SCREW SHANK
<br />PNEUMATIC SCREW -NAILS @ 12" 0.6,yN
<br />FIELD J\
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM 033. MAXIMUM AGGREGATE SIZE SHALL BE 3/4'.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />WOOD"
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />PROVIDE 8%AR ENTRAINED CONCRETE EXPOSED TO EARTH OR HEATHER
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2017, 6th EDITION
<br />ALL QED EDGES OF CONCRETE ARE TO BE CHAMFERED Yr.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER Fb. 1100 PSI AND A MODULUS OF
<br />FOR STRUCTURAL CONCRETE, ACI 630-13/ASCE 5-13 AISI SPECIFICATION FOR THE DESIGN OF
<br />PROVIDE 64ML CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL RABB-ON GROUND WHERE INDICATON
<br />®
<br />ELASTICITY .1,s00,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2011, ASCE 7-10 AND ABC SPECIFICATIONS
<br />DRAWING& BEAMS LAPPED B INCHES AND SEALED WITH ADHESIVE TAPE.
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORM -WORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORMWORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF DA2 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRL ICTED IN ACCORDANCE WITH ACI 347,
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />'RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2017, 6th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THEAFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL. DEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2X STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP 02.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTORS RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH'
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />WELDED WIRE MESH, SHALL BE ASTM A185, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE ACI
<br />WW
<br />WOOD TRUSSES:
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL BE
<br />SUPPORTED WITH 2" CHAIRS SPACED T-W OC, EACH WAY.
<br />BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NA710RAL DESIGN SPECIFICATIONS FOR
<br />TOSTRESS-GRADEDESIGNEDWITHTH 71ONS F
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />LUMBER AND ITS FASTENINGS" BY THE TRUSS DESIGNS SHALLEC SIG
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR REINFORCING STEEL:
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. REBAR SHALL BE ASTM A615 GRADE 60 DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN
<br />ACCORDANCE W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND
<br />DESIGN (DADS; S
<br />PECIFICATIONS. CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO
<br />FABRICATION, HORIZONTAL AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE
<br />ROOF: LIVE LOAD FLOOR LIVE LOAD 40 p6f SUBJECT TO ENGINEER'S REVIEW.
<br />20 pet TOP CHORD-noncorwumNN TYP. MIN LAPS SHALL BE AS FOLLOWS: k4 BAR - 25" 66 BAR - 36"
<br />N5 BAR - 30" N7 BAR - 42'
<br />10 pef STM CHORD -non-comwreM PROVIDE 36" %36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />DEAD LOAD DEAD LOAD
<br />15 p6f TOP CHORD 20 p6f TOP CHORD
<br />(7 pat w/ ASPHALT SHINGLES) (10 p6f w/ No GYPCRETE)
<br />10 p61 BTM CHORD 5 pst BTM CHORD
<br />DEAD LOAD TO RESIST WIND UPLIFT: i OP61
<br />BALCONY LIVE LOAD 60 p6f
<br />WIND: DEAD LOAD SPEED-150 MPH 3-SECOND GUST
<br />(ASCE 7.10 (FBC R2017) EXPOSURE B, RISK CATEGORY If)
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO
<br />THE ARCHITECT. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED.
<br />SHOP DRAWINGS IN THE FORM OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON.
<br />TRACT DOCUMENTS) ARE PROHIBITED WITHOUT THE EXPRESS WRITTEN PERMISSION FROM
<br />THE ENGINEER.
<br />IN ALL INSTANCES, THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS
<br />CHECKED, UNLESS OTHERWISE SPECIFIED IN WRITING BY THE ARCHITECT.
<br />FOUNDATION/ SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FORAN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 p6f,
<br />FOOTING EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY
<br />OF AT LEAST 96%OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN
<br />ACCORDANCE WITH ASTM D4557. TREAT ALL SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER
<br />TO VERIFY SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS
<br />FAILING TO MEET THE GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RE -COMPACTED AND
<br />RETESTED AT THE CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN
<br />CERTIFICATION THAT THE MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION
<br />REQUIREMENTS HAVE BEEN MET SHALL BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2,600 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3.000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5- STRUCTURAL TERRACE SLAB.
<br />CONTRACTOR SHALL SUBMT PROPOSED MX DESIGNS, WITH HSTORICAL STRENGTH DATA
<br />FOR EACH SEPARATE MX PRIOR TO CONCRETE PLACEMENT. CONCRETE SLUM' SHALL
<br />NOT EXCEED 5" 41- PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 301 AND ASTM C44OR
<br />MEASURING, M9XING, TRANSPORTING, ETC. CONCRETE TICKETS SHALL BE TIME STAMPED
<br />WHEN CONCRETE 18 BATCHED. THE MAXIMUM TIME ALLOYED FROM WHEN WATER IS ADDED
<br />TO THE MX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 WRITES.
<br />IF FOR ANY REASON THERE 18 A DELAY IN SUCH THAT A BATCH IS HEW FOR LONGER THAN
<br />90 MNUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL BE THE RESPONSIBILITY OF
<br />THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY NON COWUPNCENTH THE
<br />ABOVE.
<br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B. FOR CONCRETE EXPOSED TO EARTH ANDIORWEATHER
<br />1.1/7 FOR 65 AND SMALLER
<br />Y FOR N6 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />TV FOR SLABS, WALLS AND JOISTS
<br />1412' FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL
<br />MEETING THE REQUIREMENTS OF ASTM A446, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14,'DESIGN NATIONAL
<br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "TPIMTTCA SCSI 1"
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />WOOD TRUSSES.
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI A5BA-1982.
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURERS INSTRUCTIONS.
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />WALL.
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />MASONRY:
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />'SPECIFICATION MASONRY STRUCTURES" (ACI 530/ ASCE SRMS 402, BUILDING CODE REQUIREMENTS FOR
<br />LICENSED PROFESSIONAL ENGINEER
<br />MASONRY STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />PUBLISHED BY THE MASONRY STANDARDS JOINT COMMITTEE.
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />PROVIDED BY THE TRUSS ENGINEER
<br />MANUFACTURED IN CONFORMANCE WITH ASTM G90, GRADE I'm. 1500 PSI. BLOCK SHALL BE PLACED USING
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-10 COMPONENT
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />ASTM 0-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8'
<br />ALL SHEET METAL FRAMING CONNECTORS SHOWN ON THE PLANS SHALL BE "USP STRUCTURAL
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION
<br />CONNECTORS" BY USP, OR EQUAL UNLESS NOTED OTHERWISE ON PLANS, INSTALL CONNECTIONS
<br />TO CONSOLIDATE GROUT.
<br />WITH THE SIZE AND NUMBER OF BOLTS/NAILS AS RECOMMENDED BY THE MANUFACTURER IN THE
<br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT, MORTAR SHALL BE
<br />LATEST CATALOG.
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL BE 3/8. THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR 6 X BAR NO, (48 BAR DIAMETERS)., U.N.O.
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36, Fy . 36 K61 FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM A-500, GRADE B,
<br />Fy - 46 ka1. STRUCTURAL PIPE SHALL BE ASTMS3, GRADE B, TYPE E OR S, Fy .35 MI. TUBE AND PIPE
<br />COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM A325-N BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS SHALL
<br />BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK FASTENERS
<br />FASTENER
<br />APPLIGTION
<br />S�
<br />TYPE
<br />6PAgN0
<br />RFAMRKS
<br />API-TION
<br />TYPE
<br />I SPACING
<br />IREMAPKB
<br />,x]PTFIIRI NGT
<br />CASEHIRDENED COB
<br />SE
<br />GARAGEDOOR6To
<br />GAUGE ooRBNC.
<br />SEE DETAIL
<br />SEE DEtAA
<br />BEE DETAIL
<br />GEE DETAIL
<br />MA60NRY, GONG
<br />1DNED O.
<br />w
<br />SOD, AL EXT DOORS
<br />CMEHAROENEOCOIL
<br />6.00
<br />WINDOW/DOOR/F"TENED
<br />GARAGE DOOR&1CK
<br />bEE DETNL
<br />BEE DERAIL
<br />EEE DETAIL
<br />I EE DETAA
<br />,x PT, SEE NOTE.
<br />NAIL I IYY LONO.
<br />9TAGGERED
<br />INTO MABONRYMANC,
<br />TO MASOwVYMATE.
<br />WNDOWBUCK
<br />CABEHAROENEOCOB
<br />B•O.O
<br />WIN-11-TENED
<br />METAL STRAP To
<br />CONTACT THIS ENGINEER FOR SPACING
<br />,.PT,SEEN0TE6
<br />NAIL, I/T LONG.
<br />STAODEREO
<br />_M480NRVMANo
<br />MA60NRYICONC.
<br />REQUIREMENTS
<br />EXT.SWNGDOOR
<br />11,
<br />-TAP—
<br />'lotD4T.,
<br />IVI EMBED.IEND.
<br />NON -BEARING WOOD
<br />flY° E%PAN6pN
<br />R4
<br />4•—D. 4' END
<br />BUCKa1 PT, SEE NOTE.
<br />NO WASHER
<br />F"TNER
<br />I- EDGE DST.
<br />WALLTOCONC. SIAB
<br />wWA6HEP BOLT
<br />D4T., S•EDGEDIST.
<br />OA-P0.21/B' 'QC Y END. DIET., 11,R'
<br />PT TO STEEL COL., GEE
<br />NOTE. y/I WASHER STAGGERED EDGE DIST.
<br />NOTES
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALLBE AS PER MANUFACTURERS SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />6. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXPECT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1x MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL 32780
<br />PH: 407-774-6078
<br />FAX: 407-774.4078
<br />www.abdeslgngroup.com
<br />AA M: 0003325
<br />V
<br />0
<br />N
<br />O
<br />SLTBDIV. & LOT:
<br />SILVERADO
<br />LOT #5
<br />BLK, #12
<br />PROJECT#
<br />04128.001-05121
<br />MODEL:
<br />4EBB
<br />"1828-CALI"
<br />GARAGE SWING:
<br />LEFT
<br />PAGE:
<br />DETAILS
<br />150 MPH EXP. B
<br />8
<br />PRINT 9 18
<br />DATE
<br />SCALE:1/4 f-0"
<br />8�s N1