ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 = 58.50 PSF (68.50) ZONE 3 = 67.10 PSF (77,10) <br />ZONE 2e = 67,10 PSF (77.10) ZONE 3e = 77.50 PSF (87.50) <br />ZONE 2n = 77.50 PSF (87.50) ZONE 3r = 91.60 PSF (101.60) <br />ZONE 2r = 77,50 PSF(87.50) <br />4' -6* END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: IP 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/3Y' STRUCTURAL SHEATHING <br />EXP 1(40/20),FOR CEMENTITIOUS TILE AND METAL ROOFING USE MIN. <br />19132'. STRUCTURAL SHEATHING EXP 1 (40/20).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS @ 4" O.C. EDGEWISE 2X4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />DIA. <br />TENSILE STR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK, <br />21/Z' <br />0.131 <br />F1667 <br />SCREW SHANK <br />170,000 <br />RING <br />(16-20 RINGS <br />RSRS-03 <br />8d <br />RING SHANK, <br />2 3!S' <br />0.113 <br />F1667 <br />SCREW SHANK <br />PER INCH) <br />RSRS-01 <br />8d <br />RING SHANK, <br />PNEUMATIC <br />23/8" <br />0,113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />HAF 1tm UK IHU66 <br />ROOF SHEATHING <br />EXTERIOR SHEATHING <br />USE 1!Z' COX OR 7116' O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4" <br />O.C. AT PANEL SIDES AND SO RING SHANK GUN NAILS 4" O.C. TOP & <br />BOTTOM PANEL AND Bd RING SHANK GUN NAILS AT 6" O.C. AT <br />INTERMEDIATE SUPPORTS OR 7116" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. BUILDING LENGTH <br />n <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />ZONE 1: 1GO NAILS @ 4" O.C. ON EDGE AND 6" O.C. IN FIELD <br />ZONE 2e, 2n, 2r, I Od NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />ZONE 3,3e, 3r. 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />NOTE ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />BB RING SHANK GUN NAILS I$ C O.C. <br />TOPS BOTTOM EDGES <br />Y 49 <br />�O <br />l° o <br />�� �I . <br />I <br />I <br />I <br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />TRUSS 2X4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING <br />16'0.C. IF NO DROPPED GABLE END, ATTACH 2e4 42 SYP <br />BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />10d RING SHANK GUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT" <br />TABLE FOR FIELD SPACING ` <br />#e Z' DECK SCREWS 0 6" A" O.C. MAX <br />EDGES & 12" O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />I YP. 3/4" 1 &G SUB -FLOUR UEUKINU ULUEU TO ALL EXPUSEU MEMBERS <br />GENERAL NOTES: <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 7Ih EDITION <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />FOR STRUCTURAL CONCRETE, TMS 402/602-10 AISI SPECIFICATION FOR THE DESIGN OF <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND RISC SPECIFICATIONS <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />EXCEPT MERE A DIFFERENT DETAIL IS SHOWN, <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS, FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />OF THE WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS, <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: UVE LOAD FLOOR: LIVE LOAD 40 psf <br />20 psf TOP CHORD nanaoncunent <br />10 psf BTM CHORD - -concurrent <br />DEAD LOAD DEADLOAD <br />15 p#f TOP CHORD 20 psf TOP CHORD <br />(7 pV W! ASPHALT SHINGLES) (10 psf W/ No GYPCRETE) <br />10 psf BTM CHORD 5 psf BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT: IOpsf <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORMTO ASTM C3W33M. MAXIMUM AGGREGATE SIZE SHALL BE 3/4'. <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER WOOD. <br />NON -BEARING WOOD WALLS TOP PLATES S STUDS CAN BE SPF. <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFELE03W. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO, 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS ON -GROUND WHERE INDICATED ON <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />DRAWINGS. SEAMS LAPPED 6 INCHES AND SEALED WITH ADHESIVE TAPE. <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />FORMWORK: <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN IN OF HEARTWOOD. <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS, <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2z STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP #2. <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WATH CONCRETE. SEAT PLATES $HALL BE PROVIDED <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WELDED WIRE MESH, SHALL BE ASTM A10S4/AI064M, GRADE 65 AND BE PLACED IN ACCORDANCE OATH THE <br />WOOD TRUSSES: <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLAWS SHALL <br />BE SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC <br />' EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE 'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS, <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM A615A615M GRADE 40 IN CONCRETE DEFORMED BARS REBAR SHALL BE ASTM A615 <br />GRADE 601N MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE <br />W/THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 X BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #6 BAR - 36' <br />#5 BAR - 30" #7 BAR - 47' <br />PROVIDE 36". 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036° AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A448IA446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "SCSI LATEST EDITION' <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 68: 1990. <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS, <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 psf <br />WALL. <br />TRUSSESIGIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf <br />WIND: DEAD LOAD SPEED=10) MPH 3-SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE (FBC EXPOSURE C, RISK CATEGORY Ip <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY d ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />ATTIC UNINHABITABLEATTICOATHLIMITED <br />LIVELOADS:UNINHABITABLEATTIC WITHOUT STORAGE, <br />BIT <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />VVIT <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30pef, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THERE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS' 50psf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50PO, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40psf <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />LICENSED PROFESSIONAL ENGINEER, <br />SHOP DRAWING REVIEW: <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C90, GRADE rm = 2000 PSI. BLOCK SHALL BE PLACED USING <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C-476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8' <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED WI A SLUMP OF 8" TO 1T. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT, <br />FOUNDATION/ SITE PREPARATION' <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2.000 Psf, FOOTING <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />CELLS TO BE FILLED. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURALTERRACE SUB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, OATH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP $HALL NOT EXCEED 5PN- PRIOR TO THE ADDITION OF PLASTICIZER. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94OW OR MEASURING, MXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMIED WKEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SIXTH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE, <br />REWIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3PFOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS). <br />B FOR CONCRETE EXPOSED TO EARTH AND/OR WEATHER <br />I-IRPFOR 16 AND SMALLER <br />2PFOR 06 AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />34' FOR SLABS, WALLS AND JOISTS <br />1.12PFOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A361A36M FY = 36 kwFOR ANGLES PLATES AND WSRAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/A500M GRADE B F = 46 k. STRUCTURAL PIPE SHALL BE ASTM A53/A53M GRADE 0 TYPE E OR S F = <br />Y Y <br />35 k. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVEUNG. ALL <br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PROVIDED BY THE TRUSS ENGINEER. <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />OF THE DELEGATED TRUSS ENGINEER. WAND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />FASTENER SCHEDULE <br />WINDOW AND DOOR BUCK FASTENERS <br />FASTENER <br />APPLICATION <br />SIZE <br />TYPE <br />SPACING <br />REALIR. <br />APPLICATION <br />SIZE <br />TYPE <br />SPACING <br />REMARIfS <br />14pTFW2RIwm <br />MASWRV/WING. <br />CASE INROENEDCDL <br />NNLI-LONG. <br />B" <br />GARAGE COOR BqX <br />TO MA6pfRYM.gJC. <br />1/i°DA <br />NO WASIER <br />TNWNMA90N1RY <br />FASTENER <br />6C� <br />rz'EM .1-E-DST.. <br />t/lEDGE- <br />SGO, AL EXT. DOORS <br />CA6B HARDENEDODL <br />0"OIC <br />W1NDpNNDOOWFASTENEO <br />GARADE DOOR BUCK <br />-AO <br />11Y qA. <br />-N.. Bq.T <br />18'O'C (31B"GIAI <br />C" EMBED., C END T. <br />1 x PT.SEENOTE6 <br />NNL 11I2'LGNG <br />9TADGERED <br />INTO M49JNRY/WING. <br />TOMA80NRY/CONO <br />RCONTACT <br />x<•aD(irY'Dgl <br />3°EOGEDST. <br />WNoowBGa <br />C EWIRDENEDWIL <br />YANOONIDOOPo FASTENED <br />METusTRAPTo <br />THIS ENGINEER <br />FOR SPACING <br />I. PT, SEE NOTES <br />NNL I - LONG. <br />STgt3 _G <br />IMO MA9CMRY/GONG <br />MA6JNRY ICONC. <br />REQUIREMENTS <br />EXT. SWING DOOR (2).-TP➢ODJ' IS'OC 11?EMBED,BEND <br />WASHER FA6TNER gST.,11?EDGE DST. <br />I <br />PTWINroVd BUCK Fv3f/B" &'OIL 4"EW.OI6T.,I trY' <br />PTTTO6TEf1 COL..6EE WI WASHER STAGGERED EDGE qST. <br />NDTEfi <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />S. ...AND OR BUCKS SHALL BE AS WIDE OR W DER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR W TH A WOOD DOOR FRAME. iX MEMBERS ARE NAILED AND <br />2X MEMBERS ARE SECURED W TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX 407-7744078 <br />W W W.abdesigngmUp.com <br />AA #: 0003325 <br />4 <br />L4 <br />8 <br />U <br />01 <br />WM4 <br />o <br />LMZ�L. <br />d <br />7ey� <br />N <br />QRQ <br />D�7 <br />QU <br />p❑ <br />QQQ <br />A <br />Q <br />¢ <br />4 <br />Q <br />A��fi <br />LOT #13 <br />BLK #13 <br />PHASE #413 <br />PROJECT* <br />04181.04B-13131 <br />moDELc <br />E401 <br />°2828-ENSLEYr <br />GARAGE OWWO: <br />LEFT <br />PAGEc <br />DETAILS <br />160 MPH EXP. C <br />AR NO 93723 <br />DI <br />TIT <br />02 07 22 <br />SCALE: 1/4"=V-0" <br />SHEET <br />S ITT 1 <br />