GABLE -END <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-15 <br />ZONE 1 = 52.70 PSF (62.70) <br />ZONE 3 = 60.50 PSF (70.50) <br />ZONE 2e - 60.50 PSF (70.50) <br />ZONE 3e = 69.80 PSF (79.80) <br />ZONE 2n = 89.80 PSF (79.80) <br />ZONE 3r = 83.80 PSF (93.80) <br />ZONE 2r • 69.00 PSF (79.80) <br />"A"- 4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY: "C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: -/- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/37' STRUCTURAL SHEATHING <br />EXP 1 (4020), FOR CEMENTrTIOUS TILE AND METAL ROOFING, USE MIN. <br />19/32" STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE 1 Od RING SHANK GUN <br />NAILS 0 4" O.C. EDGEWISE 2X4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END. <br />ROOF/ WALL/ FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />DIA <br />TENSILE STR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK, <br />21/7' <br />0131 <br />F1667 <br />S REW HANK <br />170,000 <br />RING <br />16-20 RINGS <br />RSRS-03 <br />Sd <br />RING SHANK, <br />2 3/8' <br />0.113 <br />F1667 <br />SCREW SHANK <br />PER INCH ) <br />RSRS-01 <br />8d <br />RING SHANK, <br />PNEUMATIC <br />23/8" <br />0.113 <br />F1667 <br />SCREW -NAILS <br />RSRS-Ot <br />KAt I tK VK I KE.- <br />ROOF SHEATHING <br />EXTERIOR SHEATHING <br />OZ Fz- <br />USE 12" COX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4" <br />9 g <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP 8 <br />5 3 <br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6' O.C. AT <br />m <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />BUILDING LENGTH L <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />ROOF SHEATHING ATTACHEMENT SPACING <br />NOTE; GABLES-PDROP GABLE END 8 (1) ADD'L DROPPED <br />ZONE 1: 10d NAILS 4" O.C. ON EDGE AND 8' O.C. IN FIELD <br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING 0 <br />20NE 2e, 2n, 2r. tOd NAILS 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />@ <br />16"O.C. IF NO DROPPED GABLE END, ATTACH 2X4 #2 SYP <br />ZONE 3,3e, 3r: 10d NAILS C 4" O.C. ON EDGE AND 4" O.C. IN FIELD <br />BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2( <br />RI nculur_ - _IIIN, RI.- B <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />Bd RING SHANK -NAILS Q 4" 00, <br />TOP 1-01 EDGES <br />- 10d RING SHANK GUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT' <br />TABLE FOR FIELD SPACING <br />�#8 2' DECK SCREWS @ 6"4" O.C. MAX <br />EDGES & 17O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />I YK W4" I &G 5UB-FL0UK UE(;KINU ULULU I U ALL EXPUSEU MEMBERS <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM 033IC33M MAXIMUM AGGREGATE SIZE SHALL BE 314". <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />pROyIDE6%AIR ENTRAINED CONCRETE EXPOSEDTO EARTH ORWEATHER <br />WOOD: <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPR <br />ARCHITECTURAL DRAWINGS FOR SLEEVES,DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 761 EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3/1'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Rb = 11 DO PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, TMS 4021602-16 AISI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE 64#L CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALL SLABS-0fIGROUNDYMEREINDICATED ON <br />MEMBRANE <br />PRANINGS. <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2018, ASCE 7-16 AND AISC SPECIFICATIONS <br />SEAMS LAPPED 6 INCHETANDSEALED WITHRRIE <br />E. <br />PRESSURE TREATED, PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NONSTRUCTURAL USES <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORMWORK: <br />SHALL BE RATED TO RETENTION LEVELS OF 0,25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN %* OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY, ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020, 7tN EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2, STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP 02, <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND S1TE PREPARATION <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. N <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />DESIGN LOADS: <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 paf <br />20 paf TOP CHORD -concurrent <br />10 pV BTM CHORD -non- N,ent <br />DEADLOAD DEAD LOAD <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE, SEAT PLATES SHALL BE PROVIDED. <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />WOOD TRUSSES: <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036' AND BE MANUFACTURED FROM STEEL <br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED. <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "BCSI LATEST EDITION" <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING INSTALLATION BRACING METAL -PLATE -CONNECTED <br />WOOD TRUSSES. <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990. <br />to WTOP CHORD <br />SHINGLES) (1 psf W No GYPCRETE) psf TOP CHORD <br />(7 Dsf ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />B ASPHALT 5 p HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 pcf BTM CHORD 5 sf BTM CHORD THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: 10ps/ MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 paf WALL TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 psf RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS DOWEL ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />WELDED WIRE MESH: <br />WELDED WIRE MESH, SHALL BE ASTM Al 064/A1064M, GRADE 85 AND BE PLACED IN ACCORDANCE WITH THE <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WITH T CHAIRS SPACED 3'-O' OC, EACH WAY. <br />REINFORCING STEEL: <br />REBAR SHALL BE ASTM A615A615M GRADE 40 IN CONCRETE DEFORMED BARS REBAR SHALL BE ASTM A615 <br />GRADE 60 IN MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE <br />W/THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: 04 BAR - 25" MI6 BAR - 36" <br />#5 BAR - 39' #7 BAR - 4Z' <br />PROVIDE 36' x 36' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />WIND: DEAD LOAD SPEED 020) MPH 3- SECOND GUST <br />(ASCE EXPOSURE C, RISK CATEGORY II) <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />BIT BLE(FBC ATTIC ATTIC WITH LIMITED <br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10IT <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />FIXED TAIR&E <br />STORAGE: ZOpsf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS' 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: SOPsf, PASSENGER <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30ps1, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40psf <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT, SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY LENGTH ELEVATIONS DIMENSIONS ETC <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm = 2000 PSI. BLOCK SHALL BE PLACED USING <br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8" <br />WRITING BY THE ARCHITECT. <br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF W TO 10". USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATION/ SITE PREPARATION' <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE <br />SHALL BE 318" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL <br />CELLS TO BE FILLED. <br />SOIL FOR TERMITE PROTECTION. <br />FILL CM CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />REINFORCING. <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />LAP VERTICAL REBAR SX BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />STRUCTURAL STEEL: <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />CONCRETE: <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS' <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A38/A36M, Fy = 36 W FOR ANGLES, PLATES, AND W-SHAPES, STRUCTURAL TUBING SHALL BE ASTM <br />A500/A500M, GRADE B, Fy = 46 W. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy = <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE <br />35 kv. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH OOUBLE-NUT LEVELING. ALL <br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />OTHER BOLTS SHALL BE ASTM F3125/1`3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5'd- PRIOR TO THE ADDITION OF PLASTICIZER. <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN-0FF-THE-NUT METHOD. <br />CONCRETE SWILL COMPLY NTH ALL THE REQUIREMENTS OF AC1318 AND ASTM C94/C94M OR MEASURING, MIXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JSOLTS ARE TO BE STEEL. <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE NTH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3'FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH(FOUNDATIONS): <br />B FORCONCRETE EXPOSED TO EARTH ANDOR WEATHER: <br />1-112' FOR A5 AND SMALLER <br />T FOR N AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />314' FOR SLABS, WALLS AND JOISTS <br />i-IT FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PROVIDED BY THE TRUSS ENGINEER, <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING NAND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK <br />FASTENERS <br />FASTENER <br />APPLICATION <br />911E1. <br />SpA _ <br />REMARKS <br />APP ON <br />812E <br />1. <br />1SPACING1 <br />REMARKS <br />14PT FLRRING TO <br />MAaIXJRT/CGNG <br />CASE HARDOiED WIL <br />8. <br />GPRAGE DOOR BIICI( <br />OMASONRYxXXiC. <br />IIe DVi <br />NO WASHER <br />TAPiANMASONRY <br />FASTENER <br />6 OIC <br />11?EMBED.,4"ENO qST., <br />tt4'EDGE DIST. <br />aGO AL EXr. DOOrffi <br />Ix RT, SEE NOTES <br />G9EIWRDENEO WILL <br />NNL 1 1? LONG. <br />e'dC <br />6TAGGER. <br />YANWNFDOOIN FASTENED <br />MYlTGMx:. <br />---EDOC S­ <br />TO MA90NRY.CONC. <br />e'qA OR <br />1? qA <br />v� <br />EXPANSION BOLT <br />te'O'C -'A) <br />BED., x'ElUgai., <br />SEDGE q9i. <br />YANDOTI BUCK <br />lWRDENEGCAIL <br />S.- <br />1mNwraooaPo-T.. <br />METAL 9nUP TO <br />CONTACT THIS ENGINEER FOR SPACING <br />Ix PT. SEE NorE6 <br />L11?LGNG. <br />.-GEREO <br />IN-RT.rnrc <br />REQUIREMENTS <br />EXT BMNO CODR (x1111@iXA. 'TA- 1 1? EMBED, W END <br />Bl1CK h PT, SEE NOTE 6 NO WASHER PASTIER 16 QC q3T., 1 1? EDGE IXST. <br />i PTN1N00WBUCK 0.136°PAFx]1NH" 6'Ox: <'END. DIST., 11. <br />PT TO BATE IS. SEE W/WASHER 6TAGGEREO EDGE qaT. <br />NOTES <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3, ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4. PAF SHALL BE HILTI X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER A$ SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NON OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WTH A WOOD DOOR FRAME. ix MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED WI TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL32750 <br />PH: 407-774-6078 <br />FAX: 407.774.4078 <br />www.abdesigngroup.com <br />AA #: 000332E <br />o <br />4 <br />04 <br />mm <br />SUHDIV. de LLoT <br />ABBOTT PARK <br />LOT #12 <br />BLK #13 <br />PHASE #4B <br />PROJECT# <br />04181.04E-12131 <br />1LODEIe <br />3EAB <br />"1504- ALLEX" <br />GARAGE aMMIG: <br />RIGHT <br />PAGE: <br />DETAILS <br />%160 MPH EXP. C <br />PRINT 10 28 21 <br />DATE: / / <br />SCALE: 1/4"=1'-0" <br />SHEET <br />S N1 <br />