Laserfiche WebLink
♦Aq ♦Aq♦A <br />Y©r <br />HIP <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE = 53.00 PSF(63.00) ZONE = 60,90 PSF (70.90) <br />ZONE 2e = 60.90 PSF (70.90) ZONE 3e = 70.40 PSF (8040) <br />ZONE 2n = 70.40 PSF (80.40) ZONE 3, = 83.80 PSF (93.80) <br />ZONE 2r = 70.40 PSF (80,40) <br />1.11=4'-0" END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY:'C" <br />RISK CATAGORY: II <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT: +/- 0.18 <br />ROOF DIAPHRAGM <br />FOR ASPHALT SHINGLE ROOF USE MIN 19/3 STRUCTURA SHEATHING <br />7 L <br />EXP 1 (4020), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19132" STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL. <br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN <br />NAILS @ 4" O.C. EDGEWISE 2X4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF <br />GABLE END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />CIA. <br />TENSILE STR, <br />SHANK <br />ASTM <br />10d <br />RING SHANK, <br />2 12" <br />0.131 <br />F1667 <br />SCREW SHANK <br />170,000 <br />RING <br />1RINGS <br />RSRS-03 <br />Btl <br />RING SHANK, <br />2 3/8" <br />0.113 <br />F1667 <br />SCREW SHANK <br />ER INCH) <br />PER <br />RSRS-01 <br />8d <br />RING SHANK, <br />PNEUMATIC <br />2 3/8" <br />0.113 <br />F1667 <br />SCREW -NAILS <br />RSRS-01 <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />EXTERIOR SHEATHING <br />i <br />USE 12" CDX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4" <br />(� o <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP & <br />j <br />BOTTOM PANEL AND Bd RING SHANK GUN NAILS AT 6" O.C. AT <br />In <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUR SPECS.)SEE DETAIL <br />L BUILDING LENGTH <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />ROOF SHEATHING ATTA NAILS <br />0 4" T SPACING NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED <br />ZONE 1: 10tl NAILS 4" O.C. ON EDGE AND 6" O.C. IN FIELD TRUSS 2x4 N2 SYP OUTLOOKER RAFTER W/ BLOCKING 0 <br />ZONE 2e, 2n, 2r: 10d NAILS 4" O.C. ON EDGE AND 4" O.C. IN FIELD 16"O.C, IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP <br />ZONE 3,3e, 3r: lOd NAILS ®4" O.C. ON EDGE AND 4" O.C. INFIELD BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA. <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />NOTE ROOF SHEATHING THICKNESS WAS CALCULATED BLOCKING PER NAILING SCHEDULE <br />AND ADHERES TO ASCE 7-16 <br />Stl RM1G SHANK GUN NAILS Q N O.C. <br />TOPS BOTTOM EDGES <br />e <br />z� <br />o <br />8 <br />§ � 1. RING SHANK GUN NAILS <br />O SEE "ROOF SHEATHING ATTACHMENT" <br />o TABLE FOR FIELD SPACING ` - <br />� e J\ <br />8 <br />TYP. EXT. SHEATHING ATTACHMENT FOR STRUCTURAL ROOF <br />SHEATHING <br />A <br />#e 2' DECK SCREWS (m 6"-8" O.C. MAX a <br />a9 EDGES & 17' O.C. MAX IN FIELD. UNTHREADED <br />SHANKTO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING <br />I- I TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />TYP. EXT. SHEATHING ATTACHMENT <br />GENERAL NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33C33M. MAXIMIRAAGGREGATE SIZE SHALLBE 3W. <br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND <br />WOOD. <br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT <br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH ORWEATHER <br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020 7th EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 314'. <br />ALL WOOD FOR BEAMS BEARING WALLS SOLE PLATES TOP PLATES BRACING LEDGERS BLOCKING <br />ACI 316-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. F6 = 1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, AISI SPECIFICATION FOR THE DESIGN <br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPORBARRIERMEMBRANE UNDER ALL SLABS-0ON-GROUND WHERE INDICATED ON <br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-18 AND AISC SPECIFICATIONS <br />RA MEMBER IO <br />DRAWINGS. SEAMS LAPPED 6INCHES AND SEALED WITH ADHESIVE TAPE. <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />FORMWORK: <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT <br />EDITION, RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN SS' OF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWNGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FSCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK, <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAYBE REQUIRED BUT ARE BY OTHERS <br />SYP #2. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WELDED WIRE MESH: <br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />WELDED WIRE MESH, SHALL BE ASTM Al 064/Al 064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE <br />WOOD TRUSSES: <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WITH 2' CHAIRS SPACED 3'-0' OC EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL: <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A615AB15M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615 <br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED, <br />GRADE 60 IN MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AND PLACED IN ACCORDANCE <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />G <br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES ACCORDANCE WITH , "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />N:, A <br />STANDARDS FOR METAL -PLATE -CONNECTED -WOOD TRUSS CONSTRUCTION:, AND "SCSI LATEST EDITION" <br />D E <br />ROOF: LIVE LOAD FLOOR: LIVE LOAD 40 psf <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 psf TOP CHORD+1Gncon-m <br />REVIEW <br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25` #G BAR - 3S' <br />WOOD TRUSSES. <br />10 DST BTM CHORD ilonSonCUrteM <br />#5 BAR - 30" #7 BAR - 47' <br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />PROVIDE 36' x 36° CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR <br />DEAD LOAD DEAD LOAD <br />FOR ADDITIONAL INFORMATION. <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WTH ANSI/ASCE 7 Be: 1990. <br />pelf CHORD psf TOP CHORD <br />(7 (1 <br />(7 psf W/ ASPHALT SHINGLES) psf W/ No GYPCRETE) <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, <br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS. <br />10 psf BTM CHORD 5 5 psf BTM CHORD <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opsf <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE <br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />BALCONY LIVE LOAD 60 psf <br />Wes' <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />STAIRS LIVE LOAD 40 PSf <br />W ND: DEAD LOAD SPEED=10) MPH 3- SECOND GUST <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />(ASCE (FBC C, RISK CATEGORY IO <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />BIT <br />LIVE LOADS:UNINHABITABLEATTIC <br />ATTIC WITHOUT STORAGE: UNINHABITABLEATTICWTHLIMITED <br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />AND ATTICS WITH <br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WTH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR) <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE <br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />WTHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL <br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS: <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />40psf <br />MASONRY: <br />PLAN SHOWNG COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />SHOP DRAWING REVIEW: <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WTH THE DESIGNING INTENT <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE <br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />THE MASONRY STANDARDS JOINT COMMITTEE, <br />PROVIDED BY THE TRUSS ENGINEER, <br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT. <br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE F. = 2000 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. VIAND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT <br />AND CLADDING WIND LOAD PRESSURES, THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR <br />DRAWNGS SUBMITTED WITHOUT REVIEW WALL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM <br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUP USED TO FILL MASONRY CELLS SHALL COMPLY WITH <br />THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />ASTM C-47Q AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />DOCUMENTS <br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />SPECIFICALLY NOTED OTHERWISE FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318 <br />WRITING BY THE ARCHITECT, <br />COURSE AGGREGATE, AND SHALL BEE PLACEDW/ ASLUMP OF 0" TO 10'. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />FOUNDATIOW SITE PREPARATION: <br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PSI, FOOTING <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WTH ASTM D-I EST TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE: <br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS: <br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB-OWGRADE <br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SLAB. <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, NTH MSTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 51`4- PRIOR TO THE ADDITION OF PLASTICIZER. <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94UW OR MEASURING, MIXING, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN <br />WATER IS ADDED TO THE MX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL <br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WITH THE ABOVE. <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS: <br />A 3PFOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS): <br />B. FOR CONCRETE EXPOSEDTO EARTH ANNORWEATHER <br />1-10FOR NSAND SMALLER <br />2PFOR AS AND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />314' FOR SLABS, WALLS AND JOISTS <br />1-12PFOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE U8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING, <br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />lfill19101i�� <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE <br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36/A36M, Fy = 36 km FOR ANGLES, PLATES, AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500/A500M, GRADE B, Fy = 46 ksi. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy = <br />35 ksi. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING ALL <br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND DOOR BUCK FASTENERS <br />FASTENER <br />APPIKATION <br />I <br />TYPE <br />SPACING <br />APPLIUTICN <br />ZE <br />TYPE <br />SPApNG <br />REMAPo(3 <br />1.PTPURRINOTO <br />MASONRYICONC. <br />USEHAROENFDWIL <br />-,IIYL , <br />S- <br />GARAGE ODOR BUp( <br />TO MA�NTVICONC. <br />/1"pA <br />TAPCON MASOARY <br />SOC <br />1?EMBED., i'ENO p3T., <br />11rz'EDGE pei. <br />8G0, AL. EXT. OOOR3 <br />-E. -.-IL <br />S`OIC <br />NWWIp%JRIFASTENEp <br />WINIO <br />OPAAOE DOOR BUp( <br />9I0"OIA OR <br />/Y pA <br />E%PPNSIgN BOLT <br />18'OIC (LB"pA) <br />VEMBEp, 4"ENDgST., <br />1x R, 9EE NOTES <br />NNL11I1"LONp. <br />STAGGERED <br />M450NRY/GONG. <br />TO MA90NY/ICONC <br />W WASHER <br />OIC (fYY'pAl <br />3"EWE pSi. <br />IT, RE— <br />-EHAROEHEOGaL <br />S`orD <br />W114DD.vrpppw1A .1) <br />CONTACT THIS ENGINEER <br />FOR SPACING <br />a <br />NAnt,a'LGNG. <br />AGGERED <br />INro MA- <br />wns�vicaric. <br />REQUIREMENTS <br />ExT. mM,b-1xA •rAPOJN' 10,E 112'EMBED. S'EW <br />BucXaRT, sEENOT.EE.T Ee r»wASHax FASTr,<R psr.,l lrrEpcE paT. <br />Ot3B"PPFxlte" 9'CE i-E.-E..,I tIY <br />PT�TOS =ES <br />�' SEE WI WASHER STAGGERED EIX3E p3T. <br />NOTES <br />NOTES <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WNDOWS AND EXTERIOR SW NG DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA <br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED <br />4, PAF SHALL BE HILTI X.ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE <br />6. W NDOW AND DOOR BUCKS SHALL BE AS W DE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SW NG DOOR WTH A WOOD DOOR FRAME. ix MEMBERS ARE NAILED AND <br />2x MEMBERS ARE SECURED V✓ TAPCONS OR PAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-774-4178 <br />www.a bdeslgngroup.com <br />AA k: 0003325 <br />F <br />r <br />C <br />OZ <br />V <br />D� <br />W <br />St <br />stmDrv. ec LOT <br />ABBOTT PARK <br />LOT #12 <br />BLK #14 <br />PHASE #4C <br />PROJECT# <br />04181.04C-12141 <br />1LODULA <br />4EAB <br />"1672-ARIA" <br />GARAGE 8WrNG: <br />LEFT <br />PAGE: <br />DETAILS <br />160 MPH EXP, C <br />AR NO 93723 <br />DA 02/07/22 <br />SCALE: 1/4"=1'-0" <br />SKEET <br />SN1 <br />