ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCE 7-16
<br />ZONE 1 = 53.00 PSF (63.00) ZONE 3
<br />= 60.90 PSF (70.90)
<br />ZONE 2e = 60.90 PSF (70.90) ZONE 3e
<br />= 70,40 PSF (80.40)
<br />ZONE 2n = 70.40 PSF (80.40) ZONE 3r
<br />= 83.80 PSF (93.80)
<br />ZONE 2r = 70.40 PSF (80.40)
<br />"A"=4'-0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />EXPOSURE CATEGORY: "C"
<br />RISK CATAGORY: It
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT: +A 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/32" STRUCTURAL SHEATHING
<br />EXP 1 (4020), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN.
<br />19/32" STRUCTURAL SHEATHING EXP 1 (4020).(SEE TABLE FOR FIELD
<br />AND EDGE SPACING) SEE DETAIL
<br />ROOF SHEATHING TO GABLE END FRAME USE 1 Od RING SHANK GUN
<br />NAILS @ 4" O.C. EDGEWISE 2X4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF
<br />GABLE END.
<br />ROOF/ WALU FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />SIZE
<br />HEAD
<br />LENGTH
<br />I DIAL
<br />TENSILE STR.
<br />SHANK
<br />ASTM
<br />t0tl
<br />RING SHANK,
<br />21/Z
<br />0131
<br />F166
<br />SCREW SHANK
<br />170'0D0
<br />RING
<br />(16-20 RINGS
<br />RSRS-03
<br />8tl
<br />RING SHANK,
<br />23/8"
<br />0.113
<br />F1667
<br />SCREW SHANK
<br />PER INCH)
<br />RSRS-01
<br />8d
<br />RING SHANK,
<br />PNEUMATIC
<br />2 3/8"
<br />0.113
<br />Fi6R67
<br />SCREW -NAILS
<br />RS-01
<br />S
<br />nrlcK un lecu��
<br />ROOF SHEATHING
<br />EXTERIOR SHEATHING
<br />z F
<br />USE 12" CDX OR 7116" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4"
<br />9 0
<br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP 8,
<br />g 3
<br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6' O.C. AT
<br />m
<br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUR SPECS.) SEE DETAIL.
<br />U BUILDING LENGTH
<br />ROOF SHEATHING LAYOUT
<br />AND ENOWALL BRACING
<br />FOR GABLE END FRAMING
<br />ROOF SHEATHING ATTACHEMENT SPACING
<br />ZONE 1: 10d NAILS Q 4" O.C. ON EDGE AND 6' O.C. IN FIELD
<br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED
<br />ZONE 2e, 2n, 2c 10d NAILS 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />TRUSS 2X4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING
<br />ZONE 3,3e, 3r: 10d NAILS 0 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />16"O.C. IF NO DROPPED GABLE END, ATTACH SYP
<br />NAILS
<br />BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12tl NAILS EA.
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 21
<br />al ncRlNr cco nlml wr_ e...n. B c
<br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED
<br />AND ADHERES TO ASCE 7-16
<br />84 RING SHANK GUN NAILS 0 4' O C.
<br />TOP 4 BOTTOM EDGE"
<br />aD
<br />w
<br />C1. RING SHANK GUN NAILS -
<br />SEE "ROOF SHEATHING ATTACHMENT'
<br />TABLE FOR FIELD SPACING .
<br />TYP. EXT. SHEATHING ATTACHMENT FOR STRUCTURAL ROOF
<br />SHEATHING
<br />#8 7' DECK SCREWS 0 6"4" O.C. MAX
<br />EDGES & 12' O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING--------------
<br />`
<br />TYP. 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBER
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS, CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2020, 75T EDITION
<br />ACI 318-14, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE, TMS 402/602-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7.16 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />15 COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33fC33M. MAXIMUM AGGREGATE SIZE SHALL BE 3/4.
<br />PROVIDE 6%AIR ENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 314'.
<br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER All SLABS ON -GROUND WHERE INDICATED ON
<br />DRAWINGS. SEAMS UPPED 6INCHES AND SEALED NTH ADHESIVE TAPE.
<br />FORM -WORK:
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK
<br />WOOD:
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />CRIPPLERS, SILLS, ETC„ SHALL BE SOUTHERN PINE NO.2 OR BETTER. F6 = 1100 PSI AND A MODULUS OF
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />EXCLUSIONS FROM THESE PLANS;
<br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL.DEPENDING
<br />VI
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />WELDED WIRE MESH:
<br />AT BEARING LOCATIONS WTHOUT WOODEN TOP PLATES.
<br />WELDED WIRE MESH, SHALL BE ASTM A1D64/A1D64M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE
<br />WOOD TRUSSES:
<br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL
<br />BE SUPPORTED WITH 2' CHAIRS SPACED T-O' OC EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE"NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.03W AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES
<br />C E IES ARE FOUND.
<br />REBAR SHALL BE ASTM GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />DEFORMED
<br />GRADE 601N MASONRY DEFORMED BARS FREE FROM OIL SCALE AND RUST AN PLACED
<br />D LA ED IN ACCORDANCE
<br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />DESIGN LOADS:
<br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS,
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />STANDARDS FOR METAL-PLATETRUSS CONSTRUCTION:, AND METAL LATEST EDITION"
<br />ROOF', LIVE LOAD FLOOR:
<br />LIVE LOAD 40 psf
<br />AND VERTICAL BARS SHALL LAP 8 z BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />ER
<br />TIONS FOR
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />20 pef TOP CHORD -non—ncuRent
<br />REVIEW.
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: 44 BAR - 25" #6 BAR - 36"
<br />WOOD TRUSSES.
<br />10 pef BTM CHORD -non-concurrent
<br />#5 BAR - 30" #7 BAR - 42"
<br />TRUSS MANUFACTURER MALL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 36' z 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD
<br />DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 68: 1990,
<br />15 p#f TOP CHORD
<br />20 pef TOP CHORD
<br />(7 pef m ASPHALT SHINGLES)
<br />(10 Psf W No GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS,
<br />10 pef BTM CHORD
<br />5 psf BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: 1 Opsf
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 pef
<br />WALL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 psf
<br />INFORCI
<br />WIND: DEAD LOAD SPEED =160 MPH 3- SECOND GUST
<br />(ASCE 7-16 (FBC R2020) EXPOSURE C, RISK CATEGORY II)
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10pef, UNINHABITABLE ATTIC WITH LIMITED
<br />STORAGE: 20pef, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30psf, BALCONIES (EXTERIOR)
<br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200paf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER
<br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS:
<br />40psf
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TOQUANTITY, E S LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THEFORM O M
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />WRITING BY THE ARCHITECT.
<br />FOUNDATION/ SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 psf, FOOTING
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 5 F T B %O HE
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SUB.
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED SPd- PRIOR TO THE ADDITION OF PLASTICIZER.
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94IC94M OR MEASURING, MIXING, TRANSPORTING,
<br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN
<br />WATER 15 ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FOR ANY REASON
<br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL
<br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPLIANCE WITH THE ABOVE.
<br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A 3PFOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS)'.
<br />S. FOR CONCRETE EXPOSED TO EARTH AND/ORWEATHER:
<br />1-112PFOR #6 AND SMALLER
<br />2PFOR#6 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />31C FOR SLABS, WALLS AND JOISTS
<br />1.12PFOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />RUN RE NG BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />WITHOUT THE APPROVAL OF THE ENGINEER. STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />MASONRY: PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WTH ALL REQUIREMENTS OF THE LICENSED PROFESSIONAL ENGINEER.
<br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BV CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C80, GRADE fm = 2000 PSI. BLOCK SHALL BE PLACED USING OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />RUNNING BOND UNLESS OTHERWISE NOTED, LAY-UP MASONRY WALLS TO BOTTOM OF TIE MS BBEFORE
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH ALL TRUSS TO TRUSS CONNECTIONS.
<br />CO
<br />ASTM C476 AND SHALL PROVIDE A MINIMUM COMPRESSIVE TR T STRENGTH H OF 3000 PSI AT 28 DAYS, UNLESS
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 318"
<br />COURSE AGGREGATE, AND SHALL BE PLACED WI A SLUMP OF 8" TO 10'. USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />TYPE "W OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL BE 3/8" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />FILL CMU CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING,
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O.
<br />STRUCTURAL STEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION, STRUCTURAL STEEL SHALL BE ASTM
<br />A36/A36M, Fy = 36 ksi FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />A500/A500M, GRADE B, Fy = 46 ksi. STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy =
<br />35 W. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS
<br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL, J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND DOOR BUCK FASTENERS
<br />FASTENER
<br />PPPLIGTbN
<br />91ZE
<br />1 TYPE
<br />9PACIN3
<br />REMAPo(3
<br />APPLIGTICN
<br />IE
<br />iYPE
<br />PPfANG
<br />REMMM9
<br />1#Pi FURRING TO
<br />RYI NNC.
<br />GSE MBRCENEDWIL
<br />NMLt 1IY LONG.
<br />OOh;
<br />GARAGEDOORBIKK
<br />TO MASOMY/COf1C.
<br />114'DA
<br />NO WATER
<br />TOW.GV MASONT/
<br />FA9TElkA
<br />0.�
<br />2'EMBED 4'EIDPST.,
<br />1 /L'ES%SEtl9T.
<br />BCC. N. E%T. -IG6E
<br />HGfAEfED OJIL
<br />9"01C
<br />YANDu`W,9DDP/FASTENED
<br />GARAGE DOOR BIIfM
<br />3l�°A�
<br />10'OC(310'GW)
<br />BED
<br />M3'EWEdSTtl�
<br />tF 1.. SEE NOTES
<br />NNl1 VY LONG.
<br />INTO MA6W-AYIC/JNC.
<br />TO MA90NiYlLUJC.
<br />W1W R
<br />FIfPANgCN BOLT
<br />WQC (fIY'b.N
<br />�nmwBuac
<br />G9E HARDENEDOJIL
<br />rac
<br />NWNpDOOR/ FASTENED
<br />Y"'"TO
<br />METU STRAn To
<br />CONTACT THIS ENGINEER
<br />FOR SPACING
<br />" .SEE raTEe
<br />NML1 vrLorvG.
<br />TAGGERED
<br />MnsGwrrox.
<br />MAsorarrc«c.
<br />REQUIREMENTS
<br />IT DOOR (2) L10'4A 1 12 EMBED, 0' END
<br />BICKh PT, 9EE WlEe NJ WASHER 100� OI6T,11IS'EOC tl6T.
<br />NANDDWBUC% 0.13B"PAFx31I0" 8°QG <"EnG DI9T„1t?
<br />PT TO 6IEEL OCL., 9EE
<br />W1 LyR AGGEREO EDGE q6T.
<br />NJTEB ST
<br />11 STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, W DOVVS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND /OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILTI XZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />S. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1%MEMBERS ARE NAILED AND
<br />2%MEMBERS ARE SECURED V,# TAPCONS OR PAF TO THE SUBSTRATE,
<br />F
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL 32750
<br />PH: 407-7744078
<br />FAX 407-7744078
<br />www.abdesigngroup.com
<br />L AA #: 0003325
<br />6
<br />g
<br />BunDIV. Ac LOT
<br />ABBOTT PARK
<br />LOT #17
<br />BLK #12
<br />PHASE #4C
<br />PROJECT#
<br />04181.04C-17121
<br />MODELS
<br />4EAB
<br />"1672—ARIA"
<br />GARAGE SWING:
<br />RIGHT
<br />PAGE:
<br />DETAILS
<br />160 MPH EXP. C
<br />F02/07/22
<br />E:1/4"=1'-0"
<br />N1