HVAC NOTES <br />1. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH PROPER CLEARANCE, FOR SERVICING, PER <br />MFG. REQUIREMENTS. <br />2. ALL DUCT SYSTEMS INSTALLED IN NON -CONDITIONED AREAS SHALL BE CONSTRUCTED OF A VALUE <br />OF NO LESS THEN R-6 RATING. ALL SEAMS SHALL BE SEALED WITH GLASS PAIS 4 MASTIC. AND <br />INSTALLED AS PER FBC ITH EDITION (2020) MECHANICAL BLDG. CODE SECTION 603. <br />3. ALL FLEX DUCTS SHALL BE APPROVED UL 181 CLASS I AIR DUCT AS PER NFPA WA 2-3.1 <br />4. FRESH AIR INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FT. FROM ANY CHIMNEY OR VENT <br />OUTLET, OR SANITARY SEWER VENT OUTLET <br />S. ALL EXHAUST AND OUTSIDE AIR INLET DUCTS, SHALL BE CONSTRUCTED OF SMOOTH GALV. METAL. <br />OR OTHER MATERIALS AS PER FBC ITH EDITION (2020) MECHANICAL CODE SECTION 603 <br />6. ENCLOSED SUPPORT PLATFORMS SHALL BE CONSTRUCTED IN ACCORDANCE TO FBC ITH EDITION <br />(2020) MECHANICAL CODE 603.1 <br />1. BATHROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR BATHING FIXTURES SHALL BE <br />MECHANICALLY VENTED IN ACCORDANCE WITH PBC 1TH EDITION (2020) MECHANICAL CODE SECTION <br />403. <br />S. ALL EXHAUSTED BATH ROOMS, SHALL HAVE UNDER -CUT DOORS FOR MAKE-UP AIR TO BE <br />RETURNED, TO EQUAL AIR EXHAUSTED, <br />S. ALL FIRE RATED CEILINGS AND WALLS SHALL HAVE AN APPROVED FIRE OR FIRE/SMOKE <br />DAMPER'S LOCATED AT CEILING OR WALL PENETRATION AND BE SLEEVED WITH ACCESS DOORS, TO <br />RESET DAMPER ALL DAMPERS SHALL BE INSTALLED TO MFG. REC "IENDATIONS AND FBC ITH <br />EDITION (2020) MECHANICAL CODE SECTION 601. <br />10. GRILLES AND DIFFUSERS SHALL 6E PROVIDED WITH BALANCING DAMPERS. <br />11. DRYER BOOSTER TO BE A PANTEC14 DBF BOOSTER PAN OR EQUAL. <br />PANTEC14 DBF 110 DRYER BOOSTER CAPACITY 60 LINEAR FEET WITH MAX. SIX ELBOWS. <br />LEGEND <br />® <br />SUPPLY AIR DIFFUSER <br />RETURN AIR GRILL <br />® <br />SIDE -WALL OR I WAY DIFFUSER <br />— <br />SOLID LINE- SUPPLY TRUNK <br />— <br />BROKEN LINE. RETURN TRUNK <br />l <br />BALANCING DAMPER OR OBD <br />O <br />CEILING EXHAUST FAN <br />CEILING EXHAUST FAN 4 LIGHT <br />O/A <br />OUTSIDE AIR <br />® <br />THERMOSTAT <br />MI <br />PASS-THRU AIR GRILL <br />12X8 <br />14' DIA. S/A FROM <br />1CHASE ABOVE <br />1 <br />12X8 / <br />NOTE: <br />ALL HVAC TO HAVE PROPER <br />16XIi <br />ATTIC <br />PANS, W/ DRAINS <br />---------------------- <br />CEILING <br />O <br />O <br />EXTERIOR WALL <br />SECURE STRAP TO CONC. <br />CONDENSER <br />e o I <br />PLENUM <br />AIR RETURN <br />W/ (2)-3/I6'?(2' TAPCONS <br />UNIT <br />WB ROLL STRAP <br />OR <br />OR EQUAL <br />y <br />N <br />711 <br />8X4 <br />SUCTION AND LIQUID <br />I <br />AIR SUPPLY <br />y <br />REFRIGERANT LINES <br />—_ IZXS <br />— <br />AIR HANDLER----e8XI <br />y <br />4' CONCRETE BLAB SECURE STRAP TO UNIT W/ (2) <br />1/4' SHT. MTL. SCREWS <br />P1YDR <br />EXTERIOR WALL <br />-- <br />_ <br />-- <br />I <br />L-I <br />oO <br />y <br />CONDENSER UNIT <br />o 0 <br />3/4' PVC CONDENSATE DRAIN LINE <br />EVAP. TRAY—___y <br />PVC SLEEVE TO LINES BELOW SLAB <br />CONNECTION TO PAD <br />? <br />REFRIGERANT LINES TONOTE: <br />MAIN COND. DRAM 3/4'DIA <br />Ell, <br />— <br />O <br />VENT <br />THRUPLATFORM <br />WALL <br />RETURN <br />CONDENSING UNIT <br />OVER HEAD 121 FROM STRUCTURE <br />FOYE <br />TRAP DRAM LINE AND TERMINATE <br />IN AN APROVED DRAM, AS PER <br />FBCR ITH EDITION (2020) <br />MECHANICAL BLDG. CODE <br />SECTION U".2.4 <br />HVAC <br />DRAINS <br />— — — <br />I <br />GARAGE <br />SCORIATED NICKEL <br />FK FLOOR <br />C40MTERSL WC <br />I <br />L — — — — — — — <br />BRONZE FL. PL. <br />OR WALL <br />CA. PLUG <br />_ <br />-- ENTRY- <br />6' <br />SEE OPEC. <br />------- <br />BRASS PLUG <br />P-8'XB' CONC. <br />FRyGR.d,pE, <br />FITTING OR EXTENSION TO <br />OR PAVING <br />SOIL OR WASTE AS <br />FITTING OR <br />REQUIRED <br />EXTENSION TO SOIL <br />WADE 8240-K J06AM 86000 <br />OR WASTE AS <br />INSIDE <br />SERIES NICKEL BRASS TOP <br />REQUIRED <br />CAULK <br />P.V.0 OPTI/SPEC <br />INV. <br />SITE PLAN <br />E <br />ITE PLAN <br />FIRST FLOOR <br />FLOOR SLAB <br />CLEAN —OUT (TYN, <br />vEXT. GROUND CLEAN —OUT (TYPN) <br />MECHANICAL <br />PLAN <br />SCALE: 1/4 • I'-0' <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32760 <br />PH:407-774-W78 <br />FAX: 407.7744078 <br />www.abdeslgngroup.00m <br />AA A: 0003326 <br />q <br />P. <br />BUDDIV de LOT: <br />ABBOTT PARK <br />LOT #17 <br />BLK. #11 <br />PROJECT# <br />04181.000-17111 <br />MODEM <br />3EEB <br />"2260-ELSTON" <br />GARAGE ffTr MG: <br />RIGHT <br />P'T'IRST <br />FLOOR <br />MECHANICAL <br />PLAN <br />160 MPH EXP. C <br />202 <br />DARE: 05/25/21 <br />BCAXA: 1/4"=l'—O" <br />SHEET <br />M1 <br />