IF RODE i�-i <br />ROOF WIND DESIGN PRESSURES <br />NET (GROSS) ASCE 7-16 <br />ZONE 1 • 52.70 IF (62.70) <br />ZONE 3 = 60.50 PSF (70.50) <br />ZONE 2e • 60.60 PSF (70.50) <br />ZONE 3e • 69.80 IF (79.80) <br />ZONE 2n • 69.80 IF(79.80) <br />ZONE 3r • 83.80 IF (93.80) <br />ZONE 2r • 69.50 PSF (79.80) <br />W- 4'-0' END ZONE DISTANCE <br />BASIC WIND SPEED: 160 MPH <br />EXPOSURE CATEGORY 'C" <br />RISK CATAGORY: 11 <br />APPLICABLE INTERNAL <br />PRESSURE COEFFICIENT:+I-GAB <br />ROOF DHAPFIRA0IA <br />FOR ASPHALT SHINGLE ROOF, USE MIN 19W STRUCTURAL SHEATHING <br />EXP 1 (40120). FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN. <br />19/32" STRUCTURAL SHEATHING EXP 1 (4020)(SEE TABLE FOR FIELD <br />AND EDGE SPACING) SEE DETAIL <br />ROOF SHEATHING TO GABLE END FRAME USE 101 RING SHANK GUN <br />NAILS04"O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS WIN 4- OF <br />GABLE END. <br />ROOF/ WALU FLOOR <br />SHEATHING <br />FASTENER SCHEDULE <br />SIZE <br />HEAD <br />LENGTH <br />DA <br />TENSILESTR. <br />SHANK <br />ASTM <br />10d <br />RING SHANK <br />212' <br />0.131 <br />F1687 <br />170,000 <br />RING <br />(16-20 RINGS <br />RSRS-03 <br />8d <br />RING SHANK <br />2 31W <br />0. 113 <br />F1887 <br />SCREW SHANK <br />PER INCH) <br />RSRS-01 <br />8d <br />RING SHANK <br />PNEUMATIC <br />2 3AT' <br />0.113 <br />F1667 <br />SCREW -,NAILS <br />RSRS-01 <br />EXTERIOR SHEATHING <br />USE 1 /2" CDX OR 7116" O. S. B. PLY WITH 8d RING SHANK GUN NAILS AT 4' <br />O.C. AT PANEL SIDES AND 8d RING SHANK GUN NAILS 4" O.C. TOP 8 <br />BOTTOM PANEL AND Bd RING SHANK GUN NAILS AT 8" O.C. AT <br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM (INSTALLED <br />PER MANUF. SPECS.) SEE DETAIL. <br />ROOF SHEATHING ATTACHHBiT SPACING <br />ZONE 1: 10d NAILS 0 4` O.C. ON EDGE AND 6' O.C. IN FIELD <br />ZONE 2e, 2n, 2r 10d NAILS 0 4" O.C. ON EDGE AND 4` O.C. IN FIELD <br />ZONE 3,3e, 3­ 10d NAILS 0 4" O.C. ON EDGE AND C O C. IN FIELD <br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED <br />AND ADHERES TO ASCE 7-16 <br />WRING SHANK GUN NAPS ® IOC <br />TOP a BOTTOM-1 <br />O <br />�1%1%yy <br />Uul <br />20 <br />=0 <br />8 <br />Z LL <br />S Z <br />N <br />U <br />2 O <br />TYP. EXT. SHEATHING ATTACHMENT <br />RAFTER OR TRUSS <br />ROOF SHEATHING <br />b o <br />1, BUILDING LENGTH U <br />ROOF SHEATHING LAYOUT <br />AND ENDWALL BRACING <br />FOR GABLE END FRAMING <br />GABLES -DROP GABLE END 8 (1)ADDL DROPPED <br />TRUSS 2x4 N2 SYP OUTLOOKER RAFTER W/ BLOCKING C <br />18"O.C. IF NO DROPPED GABLE END, ATTACH 2x492 SYP <br />BLOCKING 0 16` O.C. FIRST 4 BAYS W (2)12d HAULS EA <br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/ <br />BLOCKING PER NAILING SCHEDULE <br />- 10d RING SHANK GUN NAILS <br />SEE "ROOF SHEATHING ATTACHMENT` <br />TABLE FOR FIELDS PACING <br />(-lyB 2` DECK SCREWS 0 6'4r O.C. MAX <br />EDGES 8 12" O.C. MAX IN FIELD. UNTHREADED <br />SHANK TO EXTEND BEYOND THICKNESS OF <br />SUB -FLOOR SHEATHING ` <br />rYP. 3/4` TSG SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS <br />GENERAL. NOTES: <br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C3YC33M. MAXIMUM AGGREGATE SIZE SNAIL BE Yr. <br />STRUCTURALDRANNGS SHALL BE USED IN CONJUNCTION WTH JOB SPECFICA11ONS AND <br />Wom <br />UR ARCHITECTALCO , MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. NSULT <br />pRpylpE BAIR ENTRAINED CONCRETE TO EARTH OR WEATHER: <br />%C <br />NON -BEARING WOOD HALLS TOP PLATES 8 STUDS CAN BE SPF. <br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN <br />ON STRUCTURAL DRAWINGS . APPLICABLE BUILDING CODE STANDARDS'. FBCR 2020, 71N EDITION <br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHNIFHi®14'. <br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING, <br />ACI 318-14, BUILDING CODE REQUIREMENTS <br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO. 2 OR BETTER. Fb = 1100 PSI AND A MODULUS OF <br />FOR STRUCTURAL CONCRETE, TMS 402/602-16 ANSI SPECIFICATION FOR THE DESIGN OF <br />PROVIDE fi4aL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UIDBt P11 SIAIiSONN7DUD WM6E INDOOR®ON <br />ELASTICITY - 1.400,000 PSI. ALL WOOD IN CONTACT NTH CONCRETE OR CONCRETE BLOCK SHALL BE <br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS <br />DRAWINGS . SEMM9 LAPPED fi INCHES AND SEALED WTH ApFSNE TIPS <br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES <br />FORM <br />SHALL BERATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISCOIUM <br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND <br />-WORK- <br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL LASE THAT SHALL BE TREATED FOR ANY <br />SHALL BE CONSTRUED TO APPLY TO ANY SI MLAR SITUATION ELSEWHERE ON THE PROJECT, <br />FORWWORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, VNALLS, <br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED <br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. <br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST <br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BLFY1NG TREATED LUMBER THAT <br />EDITIOWRECOMMENDED PRACTICE FOR CONCRETE FORM -WORK. <br />CONTAINS MORE THAN WOF HEARTWOOD. <br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE <br />DRAWNGS FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT <br />EXCLUSIONS FROM THESE PLANS: <br />MINIMUM NAILING PER FBCR 2020. 7N EDITION. SEE NAILING SCHEDULE ON PUNS. <br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING NTH THE AFFECTED PART <br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS <br />OF THE WORK. <br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURAL. DEPENDING <br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS NTH 2X STRUCTURAL LUMBER <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING <br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS. <br />SYP $2, <br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND <br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SFALL BE PROVIDED <br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS <br />WEUAT <br />' <br />BEARING LOCATIONS WITHOUT WOODEN TOP PLATES. <br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, <br />TEMPORARY BRACING, GUYS OR TIE -DOWNS. <br />TEMPORARY <br />WELDED WIRE MESH, SHALL BE ASTM A1064/A1084M GRADE 65 AND BE PLACED INACCORDANCE WITH THE <br />WOW TRUSSE8i <br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION <br />AG TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL <br />BE SUPPORTED WTH 2' CHAIRS SPACED 3'-0' OC, EACH WAY. <br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE NTH THE NATIONAL DESIGN SPECIFICATIONS FOR <br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNEDAND <br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS. <br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWNGS. <br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR <br />REINFORCING STEEL' <br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0. 038' AND BE MANUFACTURED FROM STEEL <br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. <br />REBAR SHALL BE ASTM A61SA615M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM AS15 <br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE <br />MEETING THE REQUIREMENTS OF ASTM A448/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED <br />DESIGN LOADS: <br />W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS. <br />DESIGN FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE NTH TPI-14, "DESIGN NATIONAL <br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL <br />STANDARDS FOR METAL-PLATECONNECTED-WOOD TRUSS CONSTRUCTION'., AND "SCSI LATEST EDITION' <br />ROOF'. LIVE LOAD FLOOR: LIVE LOAD 40 Pd <br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS <br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED <br />20 pd TOP CHORD nofHcpnwnent <br />REVIEW. <br />TYP. MIN LAPS SHALL BE AS FOLLOWS'. $4 BAR - 25' 00 BAR - 38" <br />WOOD TRUSSES. <br />10 pd STM CHORD+IpnaDnwnent <br />p5 BAR - 30" 07 BAR - 42` <br />TRUSS MANUFACTURER W ILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF <br />DEAD LOAD DEAD LOAD <br />PROVIDE 36' x 38' CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS <br />FOR ADDITIONAL INFORMATION. <br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQ UIR WADDITIONAL ROOF FRAMING FOR <br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WTHANSI/ASCE 788. 1990 <br />16 pd TOP CHORD 20 pd TOP CHORD <br />(7 pd wY ASPHALT SHINGLES) (10 pd W NO GYPCREI-E) <br />10 psf STM CHORD 5 pd BTM CHORD <br />DEAD LOAD TO RESIST WIND UPLIFT-. 10pd <br />BALCONY LIVE LOAD 60 pd <br />STAIRS LIVE LOAD 40 Pd <br />WIND. DEAD LOAD SPEED =160 MPH 3-SECOND GUST <br />(ASCE 7-16 (PBC R2020) EXPOSURE C, RISK CATEGORY II) <br />LIVE LOADS'. UNINHABITABLE ATTIC WITHOUT STORAGE: 1Opsf, UNINHABITABLE ATTIC WTH LIMITED <br />STORAGE. 20pef, HABITABLE ATTICS AND ATTICS SERVED WTH FIXED STAIRS: 30pd, BALCONIES (EXTERIOR) <br />AND DECKS: 40pd, GLARDS AND HANDRAILS'. 2DOpd, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER <br />VEHICLE GARAGES: 50pof, ROOMS OTHER THAN SLEEPING ROOM: 40ps1, SLEEPING ROOMS. 30psf, STAIRS: <br />4Opd <br />SHOP DRAWING REVIEW: <br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT <br />OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY <br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHTECT <br />DRAWNGS SUBMITTED WTHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWNGS IN THE FORM <br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CONTRACT DOCUMENTS) ARE PROHIBITED <br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT <br />DOCUMENTS WLL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN <br />WRITING BY THE ARCHITECT. <br />FOUNDATIOW SITE PREPARATKNI: <br />FOOTINGS WERE DESIGNED FOR AN ALLOVIABLE SOIL BEARING PRESSURE OF 2,000 pd. FOOTING <br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE <br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE W TH ASTM D-1557. TREAT ALL <br />SOIL FOR TERMITE PROTECTION. <br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERFY <br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE <br />GEO-TECHNICAL ENGINEERS REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE <br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE <br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL <br />BE MADE BY THE GEO-TECH. ENGINEER. <br />CONCRETE SHALL ACHIEVE MINMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS <br />2.500 PSI REGULAR MIGHT FOR FOOTINGS, AND SLAB ONGRADE <br />3.000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5' STRUCTURAL TERRACE SLAB <br />CONTRACTOR SHALL SUBMIT PROPOSED MX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO <br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED 5' 4. PRIOR TO THE ADDITION OF PLASTICIZER <br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 318 AND ASTM C94C94M OR MEASURING. MANG, TRANSPORTING, <br />ETC. CONCRETE TICKETS SHALL BE TIMESTAMPEO WHEN CONCRETE 15 HATCHED. THE MAXIMUM TIME ALLOWED FROM WWFN <br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS FINAL POSITION SWILL NOT EXCEED 90 MINUTES IF FOR ANY REASON <br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PUCE. R SHALL <br />BE THE RESPONSBUTY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY <br />NON COMPLIANCE WTH THE ABOVE <br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL SEAS FOLLOWS: <br />A Y FOR CONCRETE CAST AGMNST AND PERMANENTLY EAPOSE X TO EARTH FOUNDATIONS) <br />a FOR CONCRETE EXPOSED TO EARTH ADOR WEATHER <br />1-1/2'FOR e5 AND SMALLER <br />Y FOR MI6 WIND LARGER <br />C. FOR CONCRETE NOT EXPOSED TO WEATHER <br />N' FOR SLABS, WALLS AND JOISTS <br />1-1/2'FOR BEAM AND COLUAM PRIMARY REINFORCEMENT, TIES, STIRRUPS <br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING, HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS <br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH <br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT <br />WALL. <br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL. <br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL <br />ROOF 8 FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING <br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. <br />DETERMINATIONS, FEASIBILITY a ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL <br />LAYOUT, SPANS 8 ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT <br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS <br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NNOTIFIEDTO THE <br />WITHOUT THE APPROVAL OF THE ENGINEER. <br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SMALL <br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION <br />MASONRY: <br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA <br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE <br />LICENSED PROFESSIONAL ENGINEER. <br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY <br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDEDTO FACILITATE THE <br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BY <br />THE MASONRY STANDARDS JOINT COMMITTEE. <br />CONSTRUCTION SCHEDULE. AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS <br />PROVIDED BV THE TRUSS ENGINEER. <br />ALL BLOCK V ALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK <br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE <br />MANUFACTURED IN CONFORMANCE WTH ASTM CbO, GRADE fm - 2000 PSI. BLOCK SHALL BE PLACED USING <br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7.18 COMPONENT <br />RUNNING <br />UNM NG BOND UNLESS OTHERW SE NOTED. LAY-UP MASONRY HALLS TO BOTTOM OF THE BEAMS BEFORE <br />AND CLADDING WIND LOAD PRESSURES. i L Ai TRUSS ENGINEER SHA L B <br />11E DELEGATED ED L E RESPONSIBLE FOR <br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH <br />ALL TRUSS TO TRUSS CONNECTIONS. <br />ASTM C 476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS <br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 18" <br />COURSE AGGREGATE, AND SHALL BE PLACED W A SLUMP OF 8" TO 10'. USE ONLY MECHANICAL VIBRATION <br />TO CONSOLIDATE GROUT. <br />TYPE "M" OR"S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE <br />PROPORTIONED AND MIXED AS OUTLINED LARDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS <br />SHALL BE 18" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO <br />CELLS TO BE FILLED. <br />FILL CMU CELLS SOU D WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL <br />REINFORCING. <br />LAP VERTICAL RESAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O. <br />STRUCTURAL STEEL: <br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WTH THE <br />SPEGFIGATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, <br />9TH EDITON, BY THE AMER CAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM <br />A36/A36M, FY 36 kd FOR ANGLES, PLATES, AND WSKAPES. STRUCTURAL TUBING SHALL BE ASTM <br />A500IA500M, GRADE B, Fy - 46 k.. STRUCTURAL PIPE SHALL BE ASTM A51A53M, GRADE B, TYPE E OR S. FY = <br />35 ku. TUBE AND PIPE COLUMNS SMALL BE CONCRETEFILLED IN THE SHOP. <br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL <br />OTHER BOLTS SHALL BE ASTM F3125IF3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS <br />SHALL BE TIGHTENED IN ACCORDANCE WTH THE TURNOFF-THE-NUr METHOD. <br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. JAOLTS ARE TO BE STEEL. <br />FASTENER SCHEDULE <br />WINDOW AND <br />DOOR BUCK FASTENERS <br />FASTENER <br />__TON <br />Slff <br />ivFE <br />STRONG <br />REMARKS <br />TIC, <br />BII <br />ttPE <br />REMARI6 <br />,. PTRIRRNG TO <br />MASONRv, CONIC <br />„-ONG <br />rqC <br />ODIC SUCK <br />MVx]NG <br />tR'OA <br />NO MA9t6i <br />ABCON MASOEH! <br />FASiEN6T <br />SOc <br />/YEMSEO.x- ENG NISI, <br />G'®GE DeT <br />-A. EXT. DOORS <br />1. IT SEENOTEE <br />CASEHARDENED.- <br />S'OO <br />STAGGBtEO <br />_ <br />ARAOEOOIX- <br />T. 90M'/.WNC <br />r%OR <br />W,tA,�� <br />E%RANSIONBOLI <br />O'OIYTOVJ <br />04; (�?pV <br />x'EMBEO. x'BO65T. <br />3'EWEPef <br />NNOow BxK <br />EHARDENEocox <br />rGGEREG <br />WNroMrpOOfU FASTENED <br />CONTACT THIS ENGINEER <br />FOR SPACING <br />,. AT. SEE <br />ML I LONG <br />INTDMAeOERrx>xc <br />REQUIREMENTS <br />EAT_ WOR NOS W�9.8'W t -EMBED.e@D <br />BUCK h IT, SEENOTEE HV p9T. 11 DGEOST <br />ot18 vAEEl tb- .-ENO dST,I <br />vrETo sTEELOWI. E S-pC <br />wA9iH! EDGE OxR <br />MCM <br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS <br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MINI UFACTURER'S SPECS AND/OR NOA <br />3. ALL FASCIN MATER AL SHALL BE HAND FRAMED <br />4. RAF SHALL BE HILT X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN <br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE WA OR THE SPACING DETAILED ABOVE <br />6. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1A MEMBERS ARE NAILED AND <br />2, MEMBERS ARE SECURED W TAPCONS OR RAF TO THE SUBSTRATE. <br />1441 N. RONALD REAGAN BLVD. <br />LONGWOOD, FL 32750 <br />PH: 407-774-6078 <br />FAX: 407-774-4078 <br />www.abdesWr%roup.com <br />AA M: 0003325 <br />M�l <br />suzwxv. a< Zom <br />ABBOTT PARK <br />LOT #7 BLK" #14 <br />PHASE: 4C <br />P1 onwT# <br />04 8 .04C-07 41 <br />4EBB <br />"1828-CALI" <br />GA>RAGN ewnaa: <br />RIGHT <br />PAGIM <br />DETAILS <br />V. 160 MPH EXP. C <br />27 <br />Dvlulwv 10/28/21 <br />DCAXJM 1/4'=1'-0" <br />ZT <br />SN1 <br />