SY' HIP ROOF I
<br />ROOF WIND DESIGN PRESSURES
<br />NET (GROSS) ASCE 7-16
<br />ZONE 1 = 52.70 PSF (62.70) ZONE 3 = 60.50 PSF (70.50)
<br />ZONE 2e = 60.50 PSF (70.501 ZONE 3e = 69,80 PSF (79.80)
<br />ZONE 2n = 69.80 PSF (79.80) ZONE 3r = 83.80 PSF (93.80)
<br />ZONE 2, = 69.80 PSF (79.80)
<br />"A"= 4'-0" END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />EXPOSURE CATEGORY: "C"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT: 1/- 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 19/37' STRUCTURAL SHEATHING
<br />EXP 1 (4020), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE MIN.
<br />19/32" STRUCTURAL SHEATHING EXP 1 (4011 TABLE FOR FIELD
<br />AND EDGE SPACING) SEE DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE 10d RING SHANK GUN
<br />NAILS @ 4" O.C. EDGEWISE 2z4 BLOCKING ALL PANEL JOINTS W/ IN 4' OF
<br />GABLE END.
<br />ROOF/ WALL/ FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />SIZE
<br />HEAD
<br />LENGTH
<br />CIA.
<br />TENSILE STIR.
<br />SHANK
<br />ASTM
<br />10d
<br />RING SHANK,
<br />21/7'
<br />0.131
<br />F1667
<br />SCR SHANK
<br />70 000
<br />RING
<br />1ING RINGS
<br />RSRS-03
<br />8d
<br />RING SHANK,
<br />2 3/6'
<br />0.113
<br />Fi667
<br />SCREW SHANK
<br />PER INCH )
<br />RSRS-01
<br />Sol
<br />RING SHANK,
<br />PNEUMATIC
<br />2318"'
<br />0.113
<br />F1667
<br />SCREW -NAILS
<br />RSRS-01
<br />KAF ItK UK IKUJtI
<br />ROOF SHEATHING
<br />EXTERIOR SHEATHING
<br />USE 1/7' CDX OR 7/16" O.S.B. PLY WITH 8d RING SHANK GUN NAILS AT 4"
<br />O.C. AT PANEL SIDES AND Bd RING SHANK GUN NAILS 4" O.C. TOP &
<br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6" O.C. AT
<br />INTERMEDIATE SUPPORTS OR 7/16' ZIP SHEATHING SYSTEM (INSTALLED
<br />PER MANUF. SPECS.) SEE DETAIL.
<br />BUILDING LENGTH U
<br />ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />NOTE: GABLES -DROP GABLE END & (1) ADD'L DROPPED
<br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING @
<br />16'0
<br />.C. IF NO DROPPED GABLE END, ATTACH 214 #2 SYP
<br />BLOCKING @ 16' O.C. FIRST 4 BAYS W/ (2)12d NAILS EA.
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/
<br />BLOCKING PER NAILING SCHEDULE
<br />ZONE 1: 10d NAILS @ 4" O.C. ON EDGE AND 6" O.C. IN FIELD
<br />ZONE 2e, 2n, 2r 1Gd NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />ZONE 3,3e, 3r. 10d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />NOTE: ROOF SHEATHING THICKNESS WAS CALCULATED
<br />AND ADHERES TO ASCE 7-16
<br />80 RING SHANK GUN NAILS D 4" O.C.
<br />TOP S ECTTOM EDGES
<br />2
<br />TYP. EXT. SHEATHING ATTACHMENT
<br />11
<br />Emmmll
<br />=61
<br />11
<br />- 10d RING SHANK GUN NAILS
<br />SEE "ROOF SHEATHING ATTACHMENT'
<br />TABLE FOR FIELD SPACING ,
<br />#8 2" DECK SCREWS @ 6"-8" O.C. MAX @
<br />EDGES & 17 O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING
<br />TYP, 3/4" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />GENERAL NOTES:
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33/C33M MAXIMUM AGGREGATE SIZE SHALL BE 3I4'.
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />WOOD:
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />PROVIDE 6%AIRENTRAINED CONCRETE EXPOSED TO EARTH OR WEATHER
<br />NON -BEARING WOOD WALLS TOP PLATES & STUDS CAN BE SPF.
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS. APPLICABLE BUILDING CODE STANDARDS: FBC-R 2D20, 7th EDITION
<br />ALL EXPOSED EDGES OF CONCRETE ARE TO BE CHAMFERED 3l4'.
<br />ALL WOOD FOR BEAMS, BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />ACI 31 B-14, BUILDING CODE REQUIREMENTS
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. Fb= 1100 PSI ANDA MODULUS OF
<br />FOR STRUCTURAL CONCRETE, TMS 402/602-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />PROVIDE 6-MIL CONTINUOUS POLYETHYLENE VAPOR BARRIER MEMBRANE UNDER ALLSLABSONGROUND WHERE INDICATED ON
<br />IL CO BARRIERMEMBRANE
<br />NE VAPOLED R
<br />ELASTICITY = 1,400,000 PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />COLD -FORMED STEEL STRUCTURAL MEMBERS 2016, ASCE 7.16 AND AISC SPECIFICATIONS
<br />UPPED 61NCHETHYL
<br />PROVIDES. E -
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVATIVE TREATMENT: DISODIUM
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />FORM -WORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />FORM -WORK SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST
<br />WI DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN •h" OF HEARTWOOD.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />EXCLUSIONS FROM THESE PLANS:
<br />MINIMUM NAILING PER FBCR 2020, 7th EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />OF THE WORK.
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALDEPENDING
<br />PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP #Z
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WELDED WIRE MESH'
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />DURING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />WELDED WRE MESH, SHALL BE ASTM A1064/A1064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE
<br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL
<br />WOOD TRUSS ES
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />BE SUPPORTED WITH 2' CHAIRS SPACED T-O' OC, EACH WAY.
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE'NATIONAL DESIGN SPECIFICATIONS FOR
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR
<br />REINFORCING STEEL:
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036` AND BE MANUFACTURED FROM STEEL
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND.
<br />REBAR SHALL BE ASTM A615AB15M GRADE 40 IN CONCRETE DEFORMED BARS,.REBAR SHALL BE ASTM A615
<br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A, AND SHALL BE HOT -DIPPED GALVANIZED.
<br />GRADE 60 IN MASONRY DEFORMED BARS, FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />DESIGN LOADS:
<br />All THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI44, "DESIGN NATIONAL
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION, HORIZONTAL
<br />STANDARDS FOR METAL-PLATECONNECTED-W000 TRUSS CONSTRUCTION:, AND "BCSI LATEST EDITION"
<br />FLOOR: LIVE 40
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEER'S
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />ROOF: LIVE LOAD LOAD pst
<br />REVIEW
<br />WOOD TRUSSES.
<br />20 psf TOP CHORD -non-oonounent
<br />10 psf BTM CHORD-noncronwnent
<br />DEAD LOAD DEAD LOAD
<br />15 psf TOP CHORD 20 psf TOP CHORD
<br />(7 psf w/ ASPHALT SHINGLES) (10 psfw/ No GYPCRETE)
<br />10 psf BTM CHORD 5 psf BTM CHORD
<br />DEAD LOAD TO RESIST WIND UPLIFT: IOpsf
<br />BALCONY LIVE LOAD 60 psf
<br />STAIRS LIVE LOAD 40 psf
<br />WIND: DEAD LOAD SPEED =160 MPH 3-SECOND GUST
<br />(ASCE 7-16 (FBC R2020) EXPOSURE C, RISK CATEGORY IN
<br />LIVE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE: 10psf, UNINHABITABLE ATTIC WTH LIMITED
<br />STORAGE: 20psf, HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30pd,, BALCONIES (EXTERIOR)
<br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 201 GUARD IN -FILL COMPONENTS: 50Psf, PASSENGER
<br />VEHICLE GARAGES: 50psf, ROOMS OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30W,, STAIRS:
<br />40psf
<br />SHOP DRAWING REVIEW:
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />OF THE CONTRACT DOCUMENTS ONLY, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />COMPLIANCE WTH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT
<br />DRAW NGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />DOCUMENTS WLL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />WRITING BY THE ARCHITECT.
<br />FOUNDATION/ SITE PREPARATION:
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,ODO psf, FOOTING
<br />EXCAVATIONS AND SLAB SUB -GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95%OF THE
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GE04ECHNICAL ENGINEER TO VERIFY
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />CONTRACTOR'S EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH, ENGINEER.
<br />CONCRETE:
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAB -ON -GRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5" STRUCTURAL TERRACE SUB.
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WITH HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />CONCRETE PLACEMENT. CONCRETE SLUMP SHALL NOT EXCEED T * PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 316 AND ASTM C94C94M OR MEASURING, MIXING, TRANSPORTING,
<br />ETC. CONCRETE TICKETS SHALL BE TIME -STAMPED WHEN CONCRETE IS BATCHED. THE MAXIMUM TIME ALLOWED FROM WHEN
<br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED IN ITS RNAL POSITION SHALL NOT EXCEED 90 MINUTES. IF FORANY REASON
<br />THERE IS A DELAY IN SUCH THAT A BATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE SHALL NOT BE PLACED. IT SHALL
<br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPLIANCE NTH THE ABOVE.
<br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL SEAS FOLLOWS:
<br />A. 3' FOR CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B. FOR CONCRETE EXPOSED TO EARTH ANDIOR WEATHER'.
<br />1-1/2-FOR #6AND SMALLER
<br />2" FOR 06 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />31V FOR SLABS, WALLS AND JOISTS
<br />1-11T FOR BEAM AND COLUMN PRIMARY REINFORCEMENT, TIES, STIRRUPS
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25' #6 BAR - 36'
<br />#5 BAR - 30' #7 BAR - 42"
<br />PROVIDE 36' x 36` CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />FOR ADDITIONAL INFORMATION.
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />WALL.
<br />TRUSS MANUFACTURER WILL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANSI/ASCE 7 88: 1990.
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAW NGS FOR ALTERNATE CONNECTION DETAILS AT
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL ROOF & FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE. DETERMINATIONS, FEASIBILITY & ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />LAYOUT, SPANS & ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />00 NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED ITEMS AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TOTHE
<br />WITHOUT THE APPROVAL OF THE ENGINEER. STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />MASONRY: PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE LICENSED PROFESSIONAL ENGINEER.
<br />"SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISHED BV CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />THE MASONRY STANDARDS JOINT COMMITTEE. PROVIDED BY THE TRUSS ENGINEER.
<br />ALL BLOCK WALLS SHALL BE TWO -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE fm = 2000 PSI. BLOCK SHALL BE PLACED USING OF THE DELEGATED TRUSS ENGINEER. WHO UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT
<br />RUNNING BOND UNLESS OTHERWISE NOTED. LAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE AND CLADDING W ND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WTH ALL TRUSS TO TRUSS CONNECTIONS.
<br />ASTM C478, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS, UNLESS
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/e"
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8" TO 10". USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />TYPE "M" OR "S" MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />SHALL BE 310" THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />CELLS TO BE FILLED.
<br />FILL CMU CELLS SOLID WTH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O
<br />STRUCTURAL STEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />9TH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36/A36M FY = 36 ksi FOR ANGLES PLATES AND W-SHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />ASOO/ASOOM GRADE B P = 46 ksi. STRUCTURAL PIPE SHALL BE ASTM A53/A53M GRADE BTYPE E OR S F =
<br />Y Y
<br />35 kai. TUBE AND PIPE COLUMNS SHALL BECONCRETE-FILLEDIN THE SHOP.
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A307 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />OTHER BOLTS SHALL BE ASTM F3125/F3125M BOLTS WTH WASHERS UNDER THE TURNED ELEMENT. BOLTS
<br />SHALL BE TIGHTENED IN ACCORDANCE WTH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPLICATION
<br />SIZE
<br />SPACING
<br />REINARKS
<br />APPLICATON
<br />SIZE
<br />TYPE
<br />SPACING
<br />REMARKS
<br />1x2PTFURRIHO TO
<br />MA9CNJRTICONC.
<br />CASEHARDENEDCOIL
<br />L111 LONG.
<br />S NC
<br />GARAGE DOOR SUCK
<br />TO MASCNRYIGJNC
<br />TAPCON M450NRY
<br />ASTENER
<br />BDOjI/Y
<br />EMBE0., 4"END qST.,
<br />II- EDGE —
<br />D AL COOKS
<br />1. PT, SEE NOTE
<br />CASE CASE HARDENEDCOIL
<br />NNLI III LONG.
<br />9' OIC
<br />HIS
<br />WINOOWIODOR/FASTENED
<br />E DOOR BUCK
<br />318 DA DR
<br />w WASHER 2°qA
<br />EXPANSIgJ BOLT
<br />18" DC ISIB" DAI
<br />O/C(2'gA)
<br />4' EMBEp.. <" ENpgST..
<br />3"EDGE qST.
<br />— ARGENEDDoa
<br />e•o
<br />ASTENED
<br />R11
<br />CONTACT THIS ENGINEER FOR SPACING
<br />1: viDowBUGK
<br />, SEE NOTE
<br />I11TLDNG.
<br />STAGGERED
<br />NnAsoraavI CONC.
<br />REQUIREMENTS
<br />EXT. SIMNGDXM Iy18"PI1 TAPCON II,R"EMBED, BEND
<br />&/Cx2v PT,SEENGIES ER ASTNER Ie'.D'C PST.. 112' EDGE DST.
<br />N WINDOWSUCK III AF xl19" S.— IED. DST., 1 III
<br />PT TO STEEL COL..:: W/Wp'—IR STAGGERED EDGE DIST.
<br />NOTE6
<br />NOTES
<br />1. STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWNG DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURER'S SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAP SHALL BE HILT] X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />6. WINDOW ANO DOOR BUCKS SHALL BE AS W DE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WTH A WOOD DOOR FRAME. iz MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED VW TAPCONS OR PAC TO THE SUBSTRATE,
<br />Il N. RONALD REAGAN BI
<br />LONGWOOD, FL32780
<br />PH: 407-774-6078
<br />FAX: 407-7744078
<br />www.abdesigngroup.com
<br />AA #: 0003325
<br />14
<br />ear
<br />a
<br />aaa�+s
<br />C
<br />C
<br />E
<br />SLJHD V. & LOT:
<br />ABBOTT PARK
<br />LOT #22
<br />BLK #11
<br />PROJECT#
<br />04181.000-22111
<br />MODEL:
<br />4EBB
<br />"1828—CALF"
<br />GARAGE SWING:
<br />LEFT
<br />PAGE:
<br />DETAILS
<br />%160 MPH EXP.
<br />J 211V
<br />%, NO AR N �J 80723
<br />DAw. E 09/21/21
<br />SCALE: 1 /4"=1'-0"
<br />SKEET
<br />S N1