ROOF WIND DESIGN PRESSURES
<br />7-
<br />ZONE 1 = 23.79 PSF
<br />ZONE 2 = 39.48 PSF (49.48)
<br />ZONE 3 = 67.16 PSF (77.16)
<br />"A"= 4'4" END ZONE DISTANCE
<br />BASIC WIND SPEED: 160 MPH
<br />WIND EXPOSURE: "C"
<br />RISK CATAGORY: II
<br />APPLICABLE INTERNAL
<br />PRESSURE COEFFICIENT - 0.18
<br />ROOF DIAPHRAGM
<br />FOR ASPHALT SHINGLE ROOF, USE MIN 7/16' STRUCTURAL
<br />SHEATHING EXP 1(24/16) or 15/32" STRUCTURAL SHEATHING EXP 1
<br />(32116), FOR CEMENTITIOUS TILE AND METAL ROOFING, USE 15/32"
<br />STRUCTURAL SHEATHING EXP 1 (32/16) .(SEE TABLE FOR FIELD AND
<br />EDGE SPACING) SEE DETAIL.
<br />ROOF SHEATHING TO GABLE END FRAME USE 8d RING SHANK GUN
<br />NAILS @ 4" O.C. EDGEWISE 2x4 BLOCKING ALL PANEL JOINTS WI IN 4'
<br />OF GABLE END,
<br />ROOF/ WALU FLOOR
<br />SHEATHING
<br />FASTENER SCHEDULE
<br />NAIL REQUIREMENTS
<br />SIZE
<br />HEAD
<br />LENGTH
<br />DIA.
<br />TENSILE STR.
<br />SHANK
<br />ASTM
<br />8d
<br />RING SHANK,
<br />2 GIB"
<br />0.113
<br />170,000
<br />RING RINGS
<br />F1667
<br />SCREW SHANK
<br />P6-20 ER INCH)
<br />RSRS-01
<br />8d
<br />RING SHANK,
<br />PNEUMATIC
<br />2 318"
<br />0.113
<br />F1667
<br />SCREW -NAILS
<br />RSRS-01
<br />EXTERIOR SHEATHING
<br />USE 1/2" CDX OR 7/16" O.S.B. PLY WITH Bd RING SHANK GUN NAILS AT
<br />4" O.C. AT PANEL SIDES AND Bd RING SHANK GUN NAILS 4" O.C. TOP IL
<br />BOTTOM PANEL AND 8d RING SHANK GUN NAILS AT 6" O.C. AT
<br />INTERMEDIATE SUPPORTS OR 7/16" ZIP SHEATHING SYSTEM
<br />(INSTALLED PER MANUF. SPECS.) SEE DETAIL.
<br />ROOF SHEATHING ATTACFEMENT SPACING
<br />ZONE 1: S4 NAILS @ 4" O.C. ON EDGE AND S" O.C. IN FIELD
<br />ZONE 2e, 2n,C 2r: 8d NAILS @ 4" O.C. ON EDGE AND 4" O.C. IN FIELD
<br />ZONE 3,3e, 3Sd NAILS @ 4- O.C. ON EDGE AND 4- O.C. IN FIELD
<br />8d RING SHANK GUN NAILS @ 4" O.C.
<br />TOP 8 BOTTOM EDGES
<br />N
<br />-
<br />VIED
<br />VO
<br />Y 0
<br />UU
<br />00
<br />RAFTER OR TRUSS—
<br />ROOF SHEATHING
<br />■�MM�I II
<br />�mm 11
<br />.—__�,
<br />BUILDING LENGTH
<br />/ ROOF SHEATHING LAYOUT
<br />AND ENDWALL BRACING
<br />FOR GABLE END FRAMING
<br />NOTE: GABLES -DROP GABLE ENO A (1) ADD-L DROPPED
<br />TRUSS 2x4 #2 SYP OUTLOOKER RAFTER W/ BLOCKING @
<br />I G'O.C. IF NO DROPPED GABLE END, ATTACH 2x4 #2 SYP
<br />BLOCKING @ 16" O.C. FIRST 4 BAYS W/ (2)12d NAILS EA.
<br />END. ATTACH ROOF SHEATHING TO RAFTERS 2/
<br />BLOCKING PER NAILING SCHEDULE
<br />C8d RING SHANK GUN NAILS
<br />SEE "ROOF SHEATHING ATTACHMENT"
<br />TABLE FOR FIELD SPACING `
<br />C#8 2" DECK SCREWS @ 6"-8. O.C. MAX @
<br />EQGES 8 12" O.C. MAX IN FIELD. UNTHREADED
<br />SHANK TO EXTEND BEYOND THICKNESS OF
<br />SUB -FLOOR SHEATHING `
<br />GENERAL NOTES:
<br />STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND
<br />ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND SITE DRAWINGS. CONSULT
<br />ARCHITECTURAL DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN
<br />ON STRUCTURAL DRAWINGS, APPLICABLE BUILDING CODE STANDARDS: FSC4R 2020, 7M EDITION
<br />ACI 315-14, BUILDING CODE REQUIREMENTS
<br />FOR STRUCTURAL CONCRETE. TMS 402160E-16 AISI SPECIFICATION FOR THE DESIGN OF
<br />COLD FORMED
<br />STEEL STRUCTURAL MEMBERS 2016, ASCE 7-16 AND AISC SPECIFICATIONS
<br />ALL DETAILS AND SECTIONS SHOW ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND
<br />SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,
<br />EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.
<br />ALL DIMENSIONS AND CONDITIONS MUST BE VERIFIED IN THE FIELD. DO NOT SCALE THE
<br />DRAWINGS. FOLLOW WRITTEN DIMENSIONS ONLY. ANY DISCREPANCIES SHALL BE BROUGHT
<br />TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE AFFECTED PART
<br />OF THE WORK.
<br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER THE BUILDING
<br />IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND
<br />SEQUENCES TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS
<br />WRING ERECTION. THIS WORK INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING,
<br />TEMPORARY BRACING, GUYS OR TIE -DOWNS.
<br />THE CONTRACTOR SHALL SUPPLEMENT THE MINIMUM REQUIRED FOUNDATION AND SITE PREPARATION
<br />REQUIREMENTS AND SLAB -ON -GRADE THICKNESS TO HANDLE CONSTRUCTION LOADS.
<br />ALL AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTMC331cm MMAXIMUMAGGREGATE SIZE SHALL BE 31P.
<br />PROVIDE 6%NR ENTRAINED CONCRETE EXPOSED TO EARTH ORWEATHER
<br />WOOD:
<br />NON43EARING WOOD WALLS TOP PLATES 8 STUDS CAN BE SPF.
<br />ALL E7 PARE) EDGES OF CONCRETE ARE TO BE CH MFERED 3W.
<br />ALL WOOD FOR BEAMS. BEARING WALLS, SOLE PLATES, TOP PLATES, BRACING, LEDGERS, BLOCKING,
<br />CRIPPLERS, SILLS, ETC., SHALL BE SOUTHERN PINE NO.2 OR BETTER. FI = 1100 PSI AND A MODULUS OF
<br />PROVIDE EVIL CONTINUOUS POLYETHYLENE VAPOR BARRIER M MNW E UNDER ALL SIPBSOWGROI#O WHERE INDICATED ON
<br />ELASTICITY = 1,400,ODO PSI. ALL WOOD IN CONTACT WITH CONCRETE OR CONCRETE BLOCK SHALL BE
<br />DRAWINGS SEAMS LAPPED 8 INCHES AND S�ALEDYAfIi ADFESNETAPE
<br />PRESSURE TREATED. PRESSURE TREATED BOTTOM PLATE REQUIRED. WOOD FOR NON-STRUCTURAL USES
<br />SHALL BE RATED TO RETENTION LEVELS OF 0.25 PCF OF A BORATE PRESERVAT VE TREATMENT: DISODIUM
<br />FORM -WORK:
<br />CORROBORATE TETRAHEDRAL (DOT). WOOD FOR STRUCTURAL USE THAT SHALL BE TREATED FOR ANY
<br />FORM -WORK, SHORING, AND BRACING FOR ALL CONCRETE BEAMS, SLABS, COLUMNS, WALLS,
<br />REASON SHALL BE RATED TO RETENTION LEVELS OF 0.42 PCF FOR DOT OR MORE. NAILS, SPIKE, BOLTS USED
<br />AND FOOTINGS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ACI 347 LATEST
<br />W/ DOT SHALL BE HOT DIPPED GALV. FOR STRUCTURAL USES, AVOID BUYING TREATED LUMBER THAT
<br />EDITION; RECOMMENDED PRACTICE FOR CONCRETE FORM -WORK.
<br />CONTAINS MORE THAN W OF HEARTWOOD.
<br />EXCLUSIONS FROM THESE PL MS:
<br />MINIMUM NAILING PER FBCR 2020, 71h EDITION. SEE NAILING SCHEDULE ON PLANS.
<br />WATERPROOFING, FLASHING, SOUND ISOLATION, FIRE SEPARATION, OR OTHER NON STRUCTURAL ITEMS
<br />ARE NOT PART OF THE STRUCTURAL PLANS AS THEY ARE NOT CONSIDERED TO BE STRUCTURALAEPENDING PROVIDE SOLID BLOCKING UNDER ALL POINT LOADS AND WOOD COLUMNS WITH 2x STRUCTURAL LUMBER
<br />ON THE TYPE OF CONSTRUCTION THESE ITEMS SOME OR ALL MAY BE REQUIRED BUT ARE BY OTHERS.
<br />SYP #2.
<br />WELDED WIRE MESH:
<br />WELDED WIRE MESH, SHALL BE ASTM Al064/A7064M, GRADE 65 AND BE PLACED IN ACCORDANCE WITH THE
<br />ACI TYPICAL DETAILS. MINIMUM LAP SHALL BE ONE SPACE PLUS TWO INCHES. WIRE MESH FOR SLABS SHALL
<br />BE SUPPORTED WITH T CHAIRS SPACED Y-O' OC, EACH WAY.
<br />DO NOT SCALE DRAWINGS. THE CONTRACTOR AND SUBCONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR REINFORCING STEEL:
<br />TO WORK PERFORMED AND SHALL NOTIFY THE ARCHITECT IF ANY DISCREPANCIES ARE FOUND. REBAR SHALL BE ASTM A61SA815M GRADE 40 IN CONCRETE DEFORMED BARS, REBAR SHALL BE ASTM A615
<br />GRADE 60 IN MASONRY DEFORMED BARS. FREE FROM OIL, SCALE, AND RUST AND PLACED IN ACCORDANCE
<br />DESIGN LOADS: W/ THE TYPICAL BENDING DIAGRAM AND PLACING DETAILS OF THE ACI STANDARDS AND SPECIFICATIONS.
<br />CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR REVIEW PRIOR TO FABRICATION. HORIZONTAL
<br />AND VERTICAL BARS SHALL LAP 6 x BAR NO. UNSCHEDULED FIELD LAPS ARE SUBJECT TO ENGINEERS
<br />ROOF: LIVE LOAD FLOOR LIVE LOAD 40 psf REVIEW.
<br />UNTREATED WOOD SHALL NOT BE IN DIRECT CONTACT WITH CONCRETE. SEAT PLATES SHALL BE PROVIDED
<br />AT BEARING LOCATIONS WITHOUT WOODEN TOP PLATES.
<br />WORD TRUSSES:
<br />TO BE DESIGNED AND FABRICATED IN ACCORDANCE WITH THE NATIONAL DESIGN SPECIFICATIONS FOR
<br />STRESS -GRADE LUMBER AND ITS FASTENINGS' BY THE NFPA. TRUSS DESIGNS SHALL BE SIGNED AND
<br />SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN FLORIDA. SEE NOTED FOR SHOP DRAWINGS.
<br />CONNECTOR PLATES SHALL BE A MINIMUM THICKNESS OF 0.036" AND BE MANUFACTURED FROM STEEL
<br />MEETING THE REQUIREMENTS OF ASTM A446/A446M, GRADE A. AND SHALL BE HOT -DIPPED GALVANIZED
<br />DESIGN, FABRICATE, AND ERECT WOOD TRUSSES IN ACCORDANCE WITH TPI-14, "DESIGN NATIONAL
<br />STANDARDS FOR METAL-PLATE-CONNECTED-W000 TRUSS CONSTRUCTION:, AND 'SCSI LATEST EIXTKN:
<br />COMMENTARY AND RECOMMENDATIONS FOR HANDLING, INSTALLATION BRACING METAL -PLATE -CONNECTED
<br />WOOD TRUSSES.
<br />20 psf TOP CHORD—wrrent
<br />10 psf BTM CHORD alDemnc rd
<br />TYP. MIN LAPS SHALL BE AS FOLLOWS: #4 BAR - 25" #S BAR - 36'
<br />#5 BAR - 30' #7 BAR - 42"
<br />TRUSS MANUFACTURER WALL PROVIDE CALCULATIONS INDICATING ADDITIONAL DEAD LOADS FOR THE ROOF
<br />PROVIDE 36' x 36" CORNER BARS, BOND BEAM ONLY, LAPPED AND TIED TO EACH BEAM REBAR, SEE DETAILS
<br />LOCATIONS WITH GUSSETS, CRICKETS AND VALLEY LOCATIONS REQUIRING ADDITIONAL ROOF FRAMING FOR
<br />DEAD LOAD DEAD LOAD
<br />FOR ADDITIONAL INFORMATION.
<br />INTERSECTIONS OF HIGHER OR LOWER ROOFS IN ACCORDANCE WITH ANS#ASCE 7 88: 1990,
<br />15 PW TOP CHORD 20 PSf TOP CHORD
<br />(7 Pat w/ ASPHALT SHINGLES) (10 pSf W No GYPCRETE)
<br />ALL VERTICAL REINFORCING BARS IN CMU CELLS SHALL BE ANCHORED IN THE FOOTING,
<br />HURRICANE STRAPS SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S INSTRUCTIONS.
<br />10 Psf BTM CHORD 5 Par BTM CHORD
<br />THICKENED SLAB, BEAM OR LINTEL SUPPORTING THE WALL AT THE TOP AND BOTTOM WITH
<br />DEAD LOAD TO RESIST WIND UPLIFT: 10PSf
<br />MINIMUM 10 INCH HOOKS OR BENDS AND SHALL BE CONTINUOUS THROUGHOUT THE HEIGHT OF THE
<br />CONTRACTOR SHALL SUBMIT SIGNED AND SEALED DRAWINGS FOR ALTERNATE CONNECTION DETAILS AT
<br />BALCONY LIVE LOAD 60 psf
<br />WAIL.
<br />TRUSSES/GIRDERS TO COLUMNS AND WALLS FOR APPROVAL.
<br />STAIRS LIVE LOAD 40 psf
<br />RUN REINFORCING BARS CONTINUOUSLY LAPPED AT SPLICES AND AROUND CORNERS. DOWEL
<br />ROOF A FLOOR LAYOUTS PROVIDED ON THESE PLANS ARE TO BE USED AS A GUIDE FOR BEARING
<br />WINO: DEAD LOAD SPEED 020) MPH 3-SECOND GUST
<br />INTO INTERSECTING WALLS AND HOOK AT ENDS. STAGGER SPLICES WHEREVER POSSIBLE.
<br />DETERMINATIONS, FEASIBILITY 8 ARCHITECTURAL AIDE. TRUSS MANUFACTURER IS RESPONSIBLE FOR FINAL
<br />(NICE EXPOSURE C, RISK CATEGORY tl)
<br />(FBCBLE
<br />LAYOUT. SPANS 8 ALL TRUSS/ HEADER ENGINEERING. ANY DISCREPANCIES FROM THESE LAYOUTS THAT
<br />BIT ATTIC UNINHABITABLE ATTIC WITH LIMITED
<br />LINE LOADS: UNINHABITABLE ATTIC WITHOUT STORAGE:
<br />DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE THE INSTALLATION OF EMBEDDED RENTS
<br />AFFECT THE STRUCTURAL BEARING AS CALLED OUT ON THESE PLANS SHALL BE NOTIFIED TO THE
<br />WITH
<br />STORAGE: 20psi HABITABLE ATTICS AND ATTICS SERVED WITH FIXED STAIRS: 30ps1, BALCONIES (EXTERIOR)
<br />WITHOUT THE APPROVAL OF THE ENGINEER.
<br />STRUCTURAL ENGINEER OF RECORD PRIOR TO MANUFACTURE OF TRUSSES. THE TRUSS FABRICATOR SHALL
<br />AND DECKS: 40psf, GUARDS AND HANDRAILS: 200psf, GUARD IN -FILL COMPONENTS: 50psf, PASSENGER
<br />AND
<br />PROVIDE ENGINEERED SHOP DRAWINGS OF EACH INDIVIDUAL TRUSS AND A FULLY DIMENSIONED ERECTION
<br />VEEHII L HE GARAGES: 50psf, OTHER THAN SLEEPING ROOM: 40psf, SLEEPING ROOMS: 30psf, STAIRS:
<br />MASONRY.
<br />PLAN SHOWING COMPONENT LAYOUT. SHOP DRAWINGS SHALL BE SIGNED AND SEALED BY A FLORIDA
<br />MASONRY CONSTRUCTION AND MATERIALS SHALL CONFORM WITH ALL REQUIREMENTS OF THE
<br />LICENSED PROFESSIONAL ENGINEER.
<br />SHOP DRAWING REVIEW:
<br />'SPECIFICATION MASONRY STRUCTURES" (TMS 402, BUILDING CODE REQUIREMENTS FOR MASONRY
<br />THE HURRICANE STRAPS SPECIFIED ON THE WALL SECTIONS AND PLANS ARE PROVIDED TO FACILITATE THE
<br />SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGNING INTENT
<br />STRUCTURES AND SPECIFICATIONS FOR MASONRY STRUCTURES AND COMMENTARIES), AS PUBLISFED BY
<br />CONSTRUCTION SCHEDULE, AND MAY CHANGE PREDICATED ON THE TRUSS AND GIRDER REACTIONS
<br />OF THE CONTRACT DOCUMENTS ONLY, IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
<br />THE MASONRY STANDARDS JOINT COMMITTEE.
<br />PROVIDED BY THE TRUSS ENGINEER.
<br />COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.
<br />THE TRUSS TO STRUCTURE CONNECTIONS AND LOADS SPECIFIED ON THIS PLAN SHALL SUPERCEDE THOSE
<br />ALL BLOCK WALLS SHALL 8E TWA -CELL HOLLOW CONCRETE MASONRY REGULAR SIZE BLOCK
<br />OF THE DELEGATED TRUSS ENGINEER. WIND UPLIFT VALUES HAVE BEEN BASED ON ASCE 7-16 COMPONENT
<br />ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTORS PRIOR TO SUBMITTAL TO THE ARCHITECT,
<br />MANUFACTURED IN CONFORMANCE WITH ASTM C-90, GRADE Pm = 2000 PSI. BLOCK SHALL BE PLACED USING
<br />AND CLADDING WIND LOAD PRESSURES. THE DELEGATED TRUSS ENGINEER SHALL BE RESPONSIBLE FOR
<br />DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. SHOP DRAWINGS IN THE FORM
<br />RUNNING BONG UNLESS OTHERWISE NOTEDLAY-UP MASONRY WALLS TO BOTTOM OF TIE BEAMS BEFORE
<br />. -
<br />ALL TRUSS TO TRUSS CONNECTIONS.
<br />OF REPRODUCIBLE SEPIAS OF STRUCTURAL DRAWINGS (CON -TRACT DOCUMENTS) ARE PROHIBITED
<br />PLACING CONCRETE FOR IN -WALL COLUMNS. GROUT USED TO FILL MASONRY CELLS SHALL COMPLY WITH
<br />WITHOUT THE EXPRESS WRITTEN PERMISSION FROM THE ENGINEER. IN ALL INSTANCES, THE CONTRACT
<br />ASTM C476, AND SHALL PROVIDE A MINIMUM COMPRESSIVE STRENGTH OF 30M PSI AT 28 DAYS, UNLESS
<br />DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS CHECKED, UNLESS OTHERWISE SPECIFIED IN
<br />SPECIFICALLY NOTED OTHERWISE ON FOUNDATION PLAN. THE GROUT MIX SHALL HAVE A MAXIMUM 3/8'
<br />WRITING BY THE ARCHITECT.
<br />COURSE AGGREGATE, AND SHALL BE PLACED W/ A SLUMP OF 8- TO 10-. USE ONLY MECHANICAL VIBRATION
<br />TO CONSOLIDATE GROUT.
<br />FOUNDATIOW SITE PREPARATION:
<br />TYPE T7' OR'3' MORTAR SHALL BE USED EXCLUSIVELY ON THIS PROJECT. MORTAR SHALL BE
<br />FOOTINGS WERE DESIGNED FOR AN ALLOWABLE SOIL BEARING PRESSURE OF 2,000 PSI, FOOTING
<br />PROPORTIONED AND MIXED AS OUTLINED UNDER ASTM C-270. HORIZONTAL AND VERTICAL MORTAR JOINTS
<br />EXCAVATIONS AND SLAB SU13 GRADE SHALL BE COMPACTED TO A DRY DENSITY OF AT LEAST 95% OF THE
<br />SHALL BE 3W THICK UNLESS OTHERWISE NOTED. REMOVE MORTAR PROTRUSIONS THAT EXTEND INTO
<br />MODIFIED PROCTOR MAXIMUM DRY DENSITY, DETERMINED IN ACCORDANCE WITH ASTM D-1557. TREAT ALL
<br />SOIL FOR TERMITE PROTECTION.
<br />CELLS TO BE FILLED.
<br />THE OWNER SHALL RETAIN THE SERVICES OF AN INDEPENDENT GEO-TECHNICAL ENGINEER TO VERIFY
<br />SUCCESSFUL COMPLETION OF SITE PREPARATION EFFORTS. LOCATIONS FAILING TO MEET THE
<br />GEO-TECHNICAL ENGINEER'S REQUIREMENTS SHALL BE RE -COMPACTED AND RETESTED AT THE
<br />CONTRACTORS EXPENSE, AND AS DIRECTED BY THE ARCHITECT. WRITTEN CERTIFICATION THAT THE
<br />MINIMUM DESIGN BEARING CAPACITY, AND THAT THE COMPACTION REQUIREMENTS HAVE BEEN MET SHALL
<br />BE MADE BY THE GEO-TECH. ENGINEER.
<br />CONCRETE SHALL ACHIEVE MINIMUM 28 DAY COMPRESSIVE STRENGTHS AS FOLLOWS:
<br />2,500 PSI REGULAR WEIGHT FOR FOOTINGS, AND SLAS-0OWGRADE
<br />3,000 PSI REGULAR WEIGHT FOR BEAMS, COLUMNS, AND 5' STRUCTURAL TERRACE SLAB
<br />CONTRACTOR SHALL SUBMIT PROPOSED MIX DESIGNS, WIN HISTORICAL STRENGTH DATA FOR EACH SEPARATE MIX PRIOR TO
<br />CONCRETE PIACEAENT. CONCRETE SLUMP SHALL NOT EXCEED 5'J- PRIOR TO THE ADDITION OF PLASTICIZER
<br />CONCRETE SHALL COMPLY WITH ALL THE REQUIREMENTS OF ACI 316AND ASTM C9404M OR MFASUMNG, MDAG, TRANSPORTING
<br />ETC. CONCRETE TICKETS SWILL BE TIME STAWPED WHEN CONCRETE IS BATCHED. THE MAXDAM TIME ALLOWED FROM WHEN
<br />WATER IS ADDED TO THE MIX UNTIL IT IS DEPOSITED W ITS FINAL POSITION SHALL NOT EXCEED 90 MNUTES. IF FOR ANY REASON
<br />THERE IS A DELAY IN SUCH THAT ABATCH IS HELD FOR LONGER THAN 90 MINUTES, THE CONCRETE WALL NOT BE PLACED. IT SHALL
<br />BE THE RESPONSIBILITY OF THE TESTING LABORATORY TO NOTIFY THE OWNERS REPRESENTATIVE AND THE CONTRACTOR OF ANY
<br />NON COMPLIANCE WITH THE ABOVE
<br />REQUIRED CONCRETE COVERAGE OVER REBAR SHALL BE AS FOLLOWS:
<br />A. 3-FOR CONCRETE CAST AGANNSTNO PEWMBBLY EXPOSED TO EARTH (FOUNDATIONS):
<br />B. FOR CONCRETE D(POSED TO EARTH AND/OR WEATHER
<br />1-171 FOR 16 AND SMALLER
<br />T FOR#6 AND LARGER
<br />C. FOR CONCRETE NOT EXPOSED TO WEATHER
<br />3W FOR SLABS, WALLS AND JOISTS
<br />1-112' FOR BENT AND COLMBN PRIMARY REINFORCEMENT, TES, STIRRUPS
<br />FILLCM CELLS SOLID WITH GROUT AT ALL CELLS TO RECEIVE EXPANSION ANCHORS AND/OR VERTICAL
<br />REINFORCING.
<br />LAP VERTICAL REBAR 6 X BAR NO. (48 BAR DIAMETERS)., U.N.O
<br />STRUCTURALSTEEL:
<br />THE MATERIAL, FABRICATION, AND ERECTION OF STRUCTURAL STEEL SHALL COMPLY WITH THE
<br />SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS,
<br />BTH EDITION, BY THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION. STRUCTURAL STEEL SHALL BE ASTM
<br />A36/A36M, Fy = 36 kN FOR ANGLES, PLATES, AND WSHAPES. STRUCTURAL TUBING SHALL BE ASTM
<br />A5001ASOOM, GRADE S. Fy = 46 k3l, STRUCTURAL PIPE SHALL BE ASTM A53/A53M, GRADE B, TYPE E OR S, Fy =
<br />35 ksl. TUBE AND PIPE COLUMNS SHALL BE CONCRETE -FILLED IN THE SHOP,
<br />ANCHOR BOLTS AT THE COLUMN BASES SHALL BE ASTM A3G7 BOLTS WITH DOUBLE -NUT LEVELING. ALL
<br />T SHALL E AS F3125/F3125M BOLTS WITH WASHERS UNDER THE TURNED ELEMENT. BOLTS
<br />OTHER BOLTS B TM
<br />SHALL BE TIGHTENED IN ACCORDANCE WITH THE TURN -OFF -THE -NUT METHOD.
<br />ALL ANCHOR BOLTS SHALL BE GALVANIZED STEEL. J-BOLTS ARE TO BE STEEL.
<br />FASTENER SCHEDULE
<br />WINDOW AND
<br />DOOR BUCK
<br />FASTENERS
<br />FASTENER
<br />APPLIGTKKI
<br />SQE
<br />TYPE
<br />SPACMG
<br />REMARKS
<br />APPLICATXXJ
<br />SDE
<br />TYPE
<br />SPACING
<br />I�A10.KK5
<br />Pi iDRRW TO
<br />MASONRY/GONG.
<br />CASE IIIAOENED COA
<br />NAA 11?LONG.
<br />"
<br />GARAGE DOORBUCK
<br />TIPCON I.II.RCrCrl2Y
<br />POti
<br />?fl@EO.,PENDOBT.,
<br />?EDGE GIST.
<br />9GDAL.E%L.DOIXS
<br />p
<br />x T, SEE NOtEe
<br />G4E HARDElED C7A
<br />NAIL 11?LONG.
<br />COC
<br />GERED
<br />WlWNA10ORIFASTENED
<br />GARAGE TO DOCRSUM
<br />IMSOKN/GONG.
<br />1?IXl W/
<br />WASHER
<br />EXPANSro —T
<br />2P O/C
<br />4•EMBEO..PEND 06T.,
<br />3•EDGE05T.
<br />wAxxWeeupc
<br />1x Pr, sEE Noree
<br />CASE NARDEIED ODA
<br />.111?ICING.
<br />,Doow BASTENw
<br />MAW —
<br />META —To
<br />AasoHav/CCNc.
<br />CONTACT THIS ENGINEER FOR SPACING
<br />REQUIREMENTS
<br />EM.SWMG WOIi
<br />.—PTSEENDTES
<br />(1)Bn89K
<br />NDWASHER
<br />'TAPCOM
<br />FASTNER
<br />1P pC
<br />11?EA@ED. B•ENO.
<br />05T.,1 flPELGE OLST.
<br />NON6EARWG W000
<br />ALL TO CONC.9IFD
<br />12^ EXPANSION �, PEMBED.PENp
<br />ASHER DUST., 3"EDGE GIST.
<br />PT 09"w PAF z1? POIC FEND. DUST., 11?
<br />NOTEB
<br />TEEL COL., 9EE I�q/WAGHF.R STAGGERED EDGE-TNOTES
<br />11 STAPLES SHALL NOT BE USED FOR ANY STRUCTURAL APPLICATIONS
<br />2. FASTENING OF GARAGE DOORS, WINDOWS AND EXTERIOR SWING DOORS TO FRAMING BUCKS SHALL BE AS PER MANUFACTURERS SPECS AND / OR NOA
<br />3. ALL FASCIA MATERIAL SHALL BE HAND FRAMED
<br />4. PAF SHALL BE HILT) X-ZF HEAVY DUTY PINS OR EQUAL SAME DIAMETER AS SPECIFIED HEREIN
<br />5. FASTENER SPACING FOR THE BUCKS SHALL BE THE STRICTER REQUIREMENT OF THE NOA OR THE SPACING DETAILED ABOVE
<br />8. WINDOW AND DOOR BUCKS SHALL BE AS WIDE OR WIDER AS THE DOOR OR WINDOW FRAME EXCEPT FOR AN EXTERIOR SWING DOOR WITH A WOOD DOOR FRAME. 1,, MEMBERS ARE NAILED AND
<br />2x MEMBERS ARE SECURED W/ TAPCONS OR PAF TO THE SUBSTRATE.
<br />1441 N. RONALD REAGAN BLVD.
<br />LONGWOOD, FL 32750
<br />PH: 407-774.6078
<br />FAX 407-7744078
<br />www.abdesigngroup.com
<br />AA li: 0003325 J
<br />4
<br />cl
<br />I. V
<br />V
<br />iE
<br />O
<br />1
<br />04
<br />9
<br />SUHDIV. a LOT:
<br />ABBOTT PARK
<br />LOT #31
<br />BLK #12
<br />PROJECT#
<br />04181.000-31121
<br />MODEL:
<br />4EBB
<br />"1828-CALF"
<br />GARAGE EW MG:
<br />LEFT
<br />PAGE:
<br />DETAILS
<br />16 MPH EXP. C
<br />76
<br />SCALE: 1/4"=1'-0"
<br />TYP. EXT. SHEATHING ATTACHMENT
<br />TYP. 314" T&G SUB -FLOOR DECKING GLUED TO ALL EXPOSED MEMBERS
<br />S N1